FAILOVER(8)			  NUT Manual			   FAILOVER(8)

NAME
       failover	- UPS Failover Driver

SYNOPSIS
       failover	-h

       failover	-a UPS_NAME [OPTIONS]

	   Note

	   This	man page only documents	the specific features of the failover
	   driver. For information about the core driver, see nutupsdrv(8).

DESCRIPTION
       The failover driver acts	as a smart proxy for multiple "real" UPS
       drivers.	It connects to and monitors these underlying UPS drivers
       through their local UNIX	sockets	(or Windows named pipes), continuously
       evaluating health and suitability for "primary" duty according to a set
       of user configurable rules and priorities.

       At any given time, failover designates one UPS driver as	the primary,
       and presents its	commands, variables and	status to the outside world as
       if it were directly talking to that UPS.	From the perspective of	the
       clients (such as	upsmon(8) or upsc(8)), the failover driver behaves
       like any	single UPS, abstracting	away the underlying redundancy,	and
       allowing	for seamless transitioning between all monitored UPS drivers
       and their datasets.

       The driver dynamically promotes or demotes the primary UPS driver based
       on:

          Socket availability and communication status

          Data	freshness and UPS online/offline indicators

          User-defined	status filters (e.g., presence or absence of OL, LB,
	   ...)

          Administrative override via control commands	(force.primary,
	   force.ignore)

       If the current primary becomes unavailable or no	longer meets the
       criteria, the driver automatically fails	over to	a more suitable
       driver. During transitions, it ensures that any data is switched	out
       instantly, without the upsd(8) considering it as	stale or the clients
       acting on any previously	degraded status.

       When no suitable	primary	is available, a	configurable fallback state is
       entered:

          Keep	last primary and declare the data as stale

          Raise ALARM and declare the data as stale

          Raise ALARM and set forced shutdown (FSD)

       Different communication media can be used to connect to individual UPS
       drivers (e.g., USB, Serial, Ethernet). failover communicates directly
       at the socket level and therefore does not rely on upsd(8) being
       active.

EXTRA ARGUMENTS
       This driver supports the	following settings:

       port=drivername-devicename,drivername2-devicename2,...
	   Required. Specifies the local sockets (or Windows named pipes) of
	   the underlying UPS drivers to be tracked. Entries must either be a
	   path	or follow the format drivername-devicename, as used by NUT's
	   internal socket naming convention (e.g.  usbhid-ups-myups).
	   Multiple entries are	comma-separated	with no	spaces.

       inittime=seconds
	   Optional. Sets a grace period after driver startup during which the
	   absence of a	primary	is tolerated. This allows time for underlying
	   drivers to initialize. For networked	connections or drivers that
	   require "lock-picking" their	communication protocol,	consider
	   increasing this value to accommodate	potential longer delays.
	   Defaults to 30 seconds.

       deadtime=seconds
	   Optional. Sets a grace period in seconds after which	a
	   non-responsive UPS driver is	considered dead. Defaults to 30
	   seconds.

       relogtime=seconds
	   Optional. Time interval in which repeated connection	failure	logs
	   are emitted for a UPS, reducing log spam during unstable
	   conditions. Defaults	to 5 seconds.

       noprimarytime=seconds
	   Optional. Duration to wait without a	suitable primary UPS driver
	   before entering the configured fallback mode	(fsdmode). Defaults to
	   15 seconds.

       maxconnfails=count
	   Optional. Number of consecutive connection failures allowed per UPS
	   driver before entering into the cooldown period (coolofftime).
	   Defaults to 5.

       coolofftime=seconds
	   Optional. Cooldown period during which the driver pauses reconnect
	   attempts after exceeding maxconnfails. Defaults to 15 seconds.

       fsdmode=0|1|2
	   Optional. Defines the behavior when no suitable primary UPS driver
	   is found after noprimarytime	has elapsed. Defaults to 0.

	      0: Do not demote	the last primary, but mark its data as stale.
	       This is similar to how a	regular	UPS driver would behave	when
	       it loses	its connection to the target UPS device.  upsmon(8)
	       will act	on the last known (online or not) status, and decide
	       itself whether that UPS should be considered critical.

	      1: Demote the primary, raise ALARM, and mark the	data as	stale
	       after an	additional few seconds have elapsed (ensuring full
	       propagation).  This will	cause upsmon(8)	to detect that a
	       device previously in an alarm state has lost its	connection,
	       consider	the UPS	driver critical, and possibly trigger a	forced
	       shutdown	(FSD) due to depletion of MINSUPPLIES.

	      2: Demote the primary, raise ALARM, and immediately set FSD.
	       This will set FSD from the driver side and preempt upsmon(8)
	       from raising it itself. This mode is for	setups where immediate
	       shutdown	is warranted, regardless of anything else, and getting
	       FSD out to the clients as fast as just possible.

       checkruntime=0|1|2|3
	   Optional. Controls how battery.runtime values are used to break
	   ties	between	non-fully-online UPS devices at	priority 3 or lower.
	   Has no effect on initial priority selection or when strictfiltering
	   is enabled. Defaults	to 1.

	      0: Disabled.  No	runtime	comparison is done. The	first
	       candidate with the best priority	is selected according to the
	       order of	the port argument.

	      1: Compare battery.runtime.  The	UPS with the higher value is
	       preferred. If the value is missing or invalid, the UPS cannot
	       win the tie-break.

	      2: Compare battery.runtime.low.	The UPS	with the higher	value
	       is preferred. If	the value is missing or	invalid, the UPS
	       cannot win the tie-break.

	      3: Compare both variables strictly.  The	UPS is preferred only
	       if it has both a	higher battery.runtime and battery.runtime.low
	       value. If either	is missing or invalid, the UPS cannot win the
	       tie-break.

       strictfiltering=0|1
	   Optional. If	set to 1, only UPS drivers matching the	configured
	   status filters are considered for promotion to primary. If set to
	   0, the hard-coded default logic is also considered when no status
	   filters match (read more about this in the section PRIORITIES).
	   Defaults to 0.

       status_have_any=OL,CHRG,...
	   Optional. If	any of these comma-separated tokens are	present	in a
	   UPS driver's	ups.status, it passes this status filtering criteria.
	   Defaults to unset.

       status_have_all=OL,CHRG,...
	   Optional. All listed	comma-separated	tokens must be present in
	   ups.status for the UPS driver to pass this status filtering
	   criteria. Defaults to unset.

       status_nothave_any=OB,OFF,...
	   Optional. If	any of these comma-separated tokens are	present	in
	   ups.status, the UPS driver does not pass this status	filtering
	   criteria. Defaults to unset.

       status_nothave_all=OB,LB,...
	   Optional. If	all of these comma-separated tokens are	present	in
	   ups.status, the UPS driver does not pass this status	filtering
	   criteria. Defaults to unset.

	   Note

	   The status_*	arguments are primarily	intended to adjust the
	   weighting of	UPS drivers, allowing some to be prioritized over
	   others based	on their status. For example, a	driver reporting OL
	   might be preferred over one reporting ALARM OL. While
	   strictfiltering can be enabled, status filters are most effective
	   when	used in	combination with the default set of connectivity-based
	   PRIORITIES. For more	details, see the respective section further
	   below.

IMPLEMENTATION
       The port	argument in the	ups.conf(5) should reference the local driver
       sockets (or Windows named pipes)	that the "real"	UPS drivers are	using.
       A basic default setup with multiple drivers could look like this:

	     [realups]
		driver = usbhid-ups
		port = auto

	     [realups2]
		driver = usbhid-ups
		port = auto

	     [failover]
		driver = failover
		port = usbhid-ups-realups,usbhid-ups-realups2

       Any upsmon(8) clients would be set to monitor the failover UPS.

       The driver fully	supports setting variables and performing instant
       commands	on the currently elected primary UPS driver, which are proxied
       and with	end-to-end tracking also being possible	(upscmd(8) and
       upsrw(8)	-w). You may notice some variables and commands	will be
       prefixed	with upstream.,	this is	to clearly separate the	upstream
       commands	from those of failover itself.

       For your	convenience, additional	administrative commands	are exposed to
       directly	influence and override the primary election process, e.g. for
       maintenance:

          <socketname>.force.ignore [seconds] prevents	the specified UPS
	   driver from being selected as primary for the given duration, or
	   permanently if a negative value is used. A value of 0 resets	this
	   override and	re-enables selection.

          <socketname>.force.primary [seconds]	forces the specified UPS
	   driver to be	treated	with the highest priority for the given
	   duration, or	permanently if a negative value	is used. A value of 0
	   resets this override.

       Calling either command without an argument has the same effect as
       passing 0, but only for that specific override -	it does	not affect the
       other.

PRIORITIES
       As outlined above, primaries are	dynamically elected based on their
       current state and according to a	strict set of user influenceable
       priorities, which are:

          0 (highest):	UPS driver was forced to the top by administrative
	   command.

          1: UPS driver has passed the	user-defined status filters.

          2: UPS driver has fresh data	and is online (in status OL).

          3: UPS driver has fresh data, but may not be	fully online.

          4 (lowest): UPS driver is alive, but	may not	have fresh data.

       The UPS driver with the highest calculated priority is chosen as
       primary,	ties are resolved through order	of the socket names given
       within the port argument.

       For the user-defined status filters, the	following internal order is
       respected:

	1. status_nothave_any (first)

	2. status_have_all

	3. status_nothave_all

	4. status_have_any (last)

       If strictfiltering is enabled, priorities 2 to 4	are not	applicable.

       If no user-defined status filters are set, the priority 1 is not
       applicable.

	   Note

	   The base requirement	for any	election is the	UPS socket being
	   connectable and the UPS driver having published at least one	full
	   batch of data during	its lifetime. UPS driver not fulfilling	that
	   requirement are always disqualified.

RATIONALE
       In complex power	environments, presenting a single, consistent source
       of UPS information to upsmon(8) is sometimes preferable to monitoring
       multiple	independent drivers directly. The failover driver serves as a
       bridge, allowing	upsmon(8) to make decisions based on the most suitable
       available data, without having to interpret conflicting inputs or
       degraded	sources.

       Originally designed for use cases such as dual-PSU systems or redundant
       communication paths to a	single UPS, failover also supports more
       advanced	setups - for example, when multiple UPSes feed a shared
       downstream load (via STS/ATS switches), or when drivers vary in
       reliability. In these cases, the	driver can be combined with external
       logic or	scripting to dynamically adjust	primary	selection and
       facilitate graceful degradation.	Such setups may	also benefit from
       further integration with	the clone family of drivers, such as clone(8)
       or clone-outlet(8), for greater granularity and monitoring control down
       to the outlet level.

       Additionally, in	more niche scenarios, some third-party NUT
       integrations or graphical interfaces may	be limited to monitoring a
       single UPS device. In such cases, failover can help by exposing only
       the most	relevant or highest-priority data source, allowing those tools
       to operate within their constraints without missing critical
       information.

       Ultimately, this	driver enables more nuanced power monitoring and
       control than binary online/offline logic	alone, allowing	administrators
       to respond to degraded conditions early - before	they escalate into
       critical	events or require upsmon(8) to take action.

LIMITATIONS
       When using failover for redundancy between multiple UPS drivers
       connected to the	same underlying	UPS device, data is not	multiplexed
       between the drivers. As a result, some data points may be available in
       some drivers but	not in others.

       For checkruntime	considerations,	the unit of both battery.runtime and
       battery.runtime.low is assumed to be seconds. UPS drivers that report
       these values using different units are considered non-compliant with
       the NUT variable	standards and should be	reported to the	NUT developers
       as faulty.

AUTHOR
       Sebastian Kuttnig <sebastian.kuttnig@gmail.com>

SEE ALSO
       upscmd(8), upsrw(8), ups.conf(5), upsc(8), upsmon(8), nutupsdrv(8),
       clone(8), clone-outlet(8)

   Internet Resources:
       The NUT (Network	UPS Tools) home	page: https://www.networkupstools.org/

Network	UPS Tools 2.8.4.	  11/02/2025			   FAILOVER(8)