APCCONTROL(8)		     System Manager's Manual		   APCCONTROL(8)

NAME
     apccontrol -- apcupsd(8) event handler script

SYNOPSIS
     apccontrol { <event> <ups-name> <connected> <powered> }

DESCRIPTION
     When apcupsd(8) detects anomalies from the UPS being monitored, it triggers
     an event which usually results in one or more calls to the apccontrol shell
     script.   Each  event  causes apccontrol to take a particular action. These
     actions default to sane behaviour for all the events that apcupsd is likely
     to encounter. However, you can change the behaviour of every single action.

     When apcupsd detects an event, it calls the apccontrol script with the fol-
     lowing four arguments:

     event	 This is the event that occurred. Refer to the list of	possible
		 events below.

     ups-name	 This	is   the   name   of   the   UPS  as  specified  in  the
		 /etc/apcupsd/apcupsd.conf configuration file - not the name  in
		 the EEPROM of a smart UPS.

     connected	 This  is  1  if apcupsd is connected to the UPS via a serial or
		 USB port.  In the case of a slave machine where apcupsd is  not
		 directly connected to the UPS, this value will be 0.

     powered	 This  is  1 if the computer on which apcupsd is running is pow-
		 ered by the UPS and 0 if not. This is not currently implemented
		 and always defaults to 0.

     Events are sent to the system log and, optionally, to the temporary  events
     file  (/etc/apcupsd/apcupsd.events),  and	they  also  generate  a  call to
     apccontrol which in turn will call any  scripts  you  have  placed  in  the
     /etc/apcupsd directory.

   LIST OF EVENTS AND DEFAULT ACTIONS
     annoyme	  apcupsd generates this event when a shutdown is scheduled, and
		  the  time  specified by the ANNOYME configuration directive in
		  the /etc/apcupsd/apcupsd.conf file has expired.

		  Default action -- sends "Power  problems  please  logoff."  to
		  wall(1) and then exits.

     battattach   apcupsd generates this event when it detects that the UPS bat-
		  tery has been reconnected after a battdetach event.

		  Default action: does nothing.

     battdetach   apcupsd generates this event when it detects that the UPS bat-
		  tery has been disconnected.

		  Default action: does nothing.

     changeme	  apcupsd  generates this event when it detects that the utility
		  power is on, but the battery	is  not  functioning  correctly.
		  This is repeated every 9 hours.

		  Default  action -- sends "Emergency! UPS batteries have failed
		  Change them NOW" to wall and then exits.

     commfailure  apcupsd generates this event each time it loses  communication
		  with	the  monitored UPS. This event is not detected on simple
		  signalling UPSes like the Back-UPS 650.

		  Default action -- sends "Communications  with  UPS  lost."  to
		  wall and then exits.

     commok	  apcupsd  generates  this  event after a commfailure event when
		  communication with the UPS is re-established.

		  Default action -- sends "Communications with UPS restored." to
		  wall and then exits.

     doreboot	  This event is deprecated and should not be used.

		  Default action -- sends "Beginning Reboot  Sequence"	to  wall
		  and  then calls shutdown(8) with the "-r now" command line ar-
		  guments to reboot the computer.

     doshutdown   apcupsd generates this event to shutdown the computer when the
		  UPS is running on battery power and one of the  limits  (time,
		  run, load) is reached.

		  Default  action -- sends "Beginning Shutdown Sequence" to wall
		  and then calls shutdown(8) with the command line arguments "-h
		  now" to shutdown the computer.

     emergency	  apcupsd generates this event when the UPS is on battery power,
		  the battery is low and the utility power is on: a sure sign of
		  battery failure!

		  Default action -- sends "Emergency Shutdown. Possible UPS bat-
		  tery failure." to wall. Immediately after this, apcupsd gener-
		  ates a doshutdown event to shutdown the system.

     failing	  apcupsd generates this event when the UPS is running	on  bat-
		  teries and the UPS sets the low battery signal indicating that
		  battery  power  is nearly exhausted. After this event, apcupsd
		  will immediately generate a doshutdown event.

		  Default action -- sends "UPS battery	power  exhausted.  Doing
		  shutdown." to wall and then exits.

     killpower	  apcupsd  does not normally generate this event. Instead, it is
		  invoked directly from the system halt  script  as  'apccontrol
		  killpower'  because  the killpower event needs to be performed
		  as late in system shutdown as possible.

		  Default action -- sends "UPS now committed to  shut  down"  to
		  wall,  waits	for  10  seconds  and  then  issues  the command
		  "apcupsd --killpower" to put the UPS into hibernate  mode  and
		  shut	off  power to the connected equipment.	In the case of a
		  smart UPS, the UPS will then wait for the expiry of  any  con-
		  figured  shutdown time delay specified by the SLEEP configura-
		  tion directive.  In hibernate mode, the UPS will restore util-
		  ity power to the connected equipment	subject  to  the  values
		  specified for the RETURNCHARGE and WAKEUP configuration direc-
		  tives.

     loadlimit	  apcupsd  generates this event when the battery discharge limit
		  specified by the BATTERYLEVEL configuration directive has been
		  reached.

		  Default action -- sends "UPS battery discharge limit	reached.
		  Doing  shutdown"  to	wall  and  then exits. After this event,
		  apcupsd will immediately generate a doshutdown event.

     mainsback	  apcupsd generates this event when the  utility  power  returns
		  after  a  powerout  event. The doshutdown event may or may not
		  have been generated depending on the parameters you  have  de-
		  fined and the length of the power outage. Attempting cancella-
		  tion of a doshutdown event should never be tried as it is very
		  unlikely  to succeed and will almost certainly leave your com-
		  puter in an indeterminate state.

		  Default action -- if the file /var/run/powerfail exists, sends
		  "Continuing with shutdown." to wall and then exits. Otherwise,
		  does nothing.

     onbattery	  apcupsd generates this event if a power failure has  been  de-
		  tected  and the UPS is still on battery power at the expiry of
		  the delay specified by the ONBATTERYDELAY configuration direc-
		  tive.

		  Default action -- sends "Power failure. Running on UPS batter-
		  ies." to wall and then exits.

     offbattery   apcupsd generates this event when the  utility  power  returns
		  if, and only if, the onbattery event has been generated.

		  Default -- sends ""Power has returned..." to wall and then ex-
		  its.

     powerout	  apcupsd  generates  this event as soon as apcupsd detects that
		  the UPS has switched to battery power and it is  not	a  self-
		  test.

		  Default action -- does nothing.

     remotedown   apcupsd  generates  this  event on a slave machine when it de-
		  tects either (1) that the master has shutdown, or (2) that  an
		  onbattery event has occurred and communication with the master
		  has been lost.

		  Default action: sends "Remote Shutdown. Beginning Shutdown Se-
		  quence."  to	wall  and exits. Immediately after this, apcupsd
		  generates a doshutdown event to shutdown the system.

     runlimit	  apcupsd generates this event when the remaining runtime  limit
		  specified by the MINUTES configuration directive expires while
		  the  UPS  is on battery power as the result of a utility power
		  outage. The remaining runtime is internally calculated by  the
		  UPS and monitored by apcuspd.

		  Default  action -- sends "UPS battery runtime percent reached.
		  Doing shutdown." to wall and then  exits.  After  this  event,
		  apcupsd will immediately generate a doshutdown event.

     timeout	  apcupsd  generates  this  event when the time specified by the
		  TIMEOUT configuration directive expires while the  UPS  is  on
		  battery  power  as  the result of a utility power outage. This
		  configuration directive is not normally used with smart  UPSes
		  which  would	instead rely on the more reliable remaining run-
		  time (MINUTES) or the battery level (BATTERYLEVEL)  configura-
		  tion directives.

		  Default  action  --  send "UPS battery runtime limit exceeded.
		  Doing shutdown." to wall and then  exits.  After  this  event,
		  apcupsd will immediately generate a doshutdown event.

     startselftest  apcupsd  generates this event when it detects the start of a
		  UPS self test.

		  Default action: does nothing.

     endselftest  apcupsd generates this event when it detects the end of a  UPS
		  self test.

		  Default action: does nothing.

   CUSTOMISING EVENT ACTIONS
     Do  not  modify apccontrol directly as it will be overwritten the next time
     you upgrade to a new release of apcupsd.

     The recommended way to customise an event action is simply to create an ex-
     ecutable program or script file with the same name as  the  event	and  put
     that  file  in the /etc/apcupsd directory. Now, when the selected event oc-
     curs, apccontrol will execute your program or script.

     If you want apccontrol to also execute its default action for the	selected
     event, your program or script should exit with an exit status of 0 (zero).

     If  you  do  not want apccontrol to also execute its default action for the
     selected event, your program or script must exit with an exit status of 99.
     Be aware that if you completely override the default action, you  must  en-
     sure the proper shutdown of your computer if this is necessary.

     Some  sample  scripts (changeme, commfailure, commok, offbattery and onbat-
     tery) that email messages to root instead of broadcasting messages  to  all
     logged-in users may be found in /etc/apcupsd after an installation and also
     in the platforms/etc directory of the apcupsd source code.

FILES
     /etc/apcupsd/apccontrol

SEE ALSO
     wall(1), apcupsd.conf(5), apcupsd(8), shutdown(8).

     The  HTML	apcupsd  manual  installed on your system or available online at
     http://www.apcupsd.org/

AUTHORS
   This page
     Trevor Roydhouse

   Software
     Adam Kropelin (current Project Manager and Code Maintainer)
     Kern Sibbald (former Project Manager and Code Maintainer)
     Riccardo Facchetti (former Project Manager and Code Maintainer)
     Andre M. Hedrick (Project Founder and former Code Maintainer)

   Contributors
     An enormous number of users who have devoted their time and energy to  this
     project -- thanks.

apccontrol v3.14.6		January 10, 2009		   APCCONTROL(8)