APCSMART-OLD(8) 		   NUT Manual			 APCSMART-OLD(8)

NAME
     apcsmart-old  -  Driver  for  American  Power Conversion Smart Protocol UPS
     equipment

SYNOPSIS
     apcsmart-old -h

     apcsmart-old -a UPS_NAME [OPTIONS]

	 Note

	 This man page only documents the hardware-specific features of the apc-
	 smart-old driver. For information about the core  driver,  see  nutups-
	 drv(8).

SUPPORTED HARDWARE
     apcsmart-old  should recognize all recent APC models that use a serial pro-
     tocol at 2400 bps. This is primarily the Smart-UPS, Matrix-UPS and Back-UPS
     Pro lines.

     The driver attempts to support every bell and whistle of the APC  reporting
     interface, whether or not this is strictly sensible.

     Some older hardware may only report a handful of variables. This is usually
     not a bug--they just don't support anything else.

CABLING
     This driver expects to see a 940-0024C cable or a clone by default. You can
     switch  to the 940-0095B dual-mode cable support with the cable= definition
     described below.

     If your 940-0024C cable is broken or missing, use this diagram to	build  a
     clone:

     https://www.networkupstools.org/cables/940-0024C.jpg

EXTRA ARGUMENTS
     This driver supports the following optional settings in the ups.conf(5):

     cable=940-0095B
	 Configure the serial port for the APC 940-0095B dual-mode cable.

     sdtype=num
	 Use shutdown type num, according to this table:

	 0
	     soft shutdown or powerdown, depending on battery status

	 1
	     soft shutdown followed by powerdown

	 2
	     instant power off

	 3
	     power off with grace period

	 4
	     "force OB" hack method for CS 350

     Modes 0 and 1 will power up the load when power returns. Modes 2 and 3 will
     keep the load turned off when the power returns.

     Mode 4 exploits an oddity in the CS 350 models since they only seem to sup-
     port the S command, but then only when running on battery. As a result, the
     driver  will force the UPS to go on battery if necessary before sending the
     shutdown command. This ensures that the load gets reset.

BUGS
     Some older APC UPS models return bogus data in the status register during a
     front panel test. This is usually detected and discarded,	but  some  other
     unexpected values have occasionally slipped through.

     APC  UPS  models  with both USB and serial ports require a power cycle when
     switching from USB communication to serial, and perhaps vice versa.

AUTHORS AND HISTORY
     Nigel Metheringham <Nigel.Metheringham@Intechnology.co.uk> (drawing heavily
     on the original apcsmart driver by Russell Kroll).

     This driver was called newapc for a time and was renamed in the 1.5 series.

     In 2.6.2 the driver was renamed to apcsmart-old, being  superseded  by  up-
     dated version with new features which currently holds the apcsmart name.

SEE ALSO
   The core driver:
     nutupsdrv(8)

   Internet resources:
     The NUT (Network UPS Tools) home page: https://www.networkupstools.org/

Network UPS Tools 2.8.5.	   08/04/2026			 APCSMART-OLD(8)