APCUPSD.CONF(5) 	       File Formats Manual		 APCUPSD.CONF(5)

NAME
     apcupsd.conf -- apcupsd(8) configuration file

DESCRIPTION
     apcupsd.conf  is  the  configuration  file for the apcupsd(8) program.  The
     file is a plain ASCII text file which comprises a number  of  configuration
     directives  which	control how the apcupsd program behaves when controlling
     most American Power Conversion Corp (APC) UPSes.  The configuration file is
     also used for the apctest(8) program when bulk programming the EEPROM in  a
     Smart-UPS model.

     It  will  almost certainly be necessary to customise the information in the
     configuration file to suit your particular configuration and operating  re-
     quirements.

     Note  that the apcupsd daemon must be restarted in order for changes to the
     configuration file to become active.

     The configuration file directives are explained in the subsections below.

   GENERAL CONFIGURATION DIRECTIVES
     UPSNAME <string>

	      Specify a name for the UPS for log files, status reports etc.

     UPSCABLE [ simple | smart | ether | usb | 940-0119A | 940-0127A | 940-0128A
	      | 940-0020B | 940-0020C | 940-0023A  |  940-0024B  |  940-0024C  |
	      940-1524C  |  940-0024G  |  940-0095A  |	940-0095B  | 940-0095C |
	      940-0625A | MAM-04-02-2000 ]

	      The type of cable used to connect the UPS to the computer.

     UPSTYPE [ dumb | apcsmart | net | usb | snmp | pcnet | modbus |test ]

	      The type of APC UPS that you have.

     DEVICE <name>

	      The name of the device used for communication between the UPS  and
	      the computer. For a USB UPS, you should leave the DEVICE directive
	      blank and apcupsd will figure out where the device is located.

	      *   apcsmart : /dev/tty** (serial connection)
	      *   usb : leave blank! (USB connection)
	      *   net : hostname:port (NIS connection)
	      *   snmp : hostname:port:vendor:community (SNMP connection)
	      *   dumb : /dev/tty** (serial connection)
	      *   pcnet : ipaddr:username:passphrase (AP9617 SmartSlot card)
	      *   modbus : /dev/tty** (serial connection)
	      *   modbus : leave blank (USB connection)

	      If  you  have problems, please see the apcupsd manual for more de-
	      tailed information and comprehensive troubleshooting advice.

     POLLTIME <seconds>

	      The rate in seconds that the daemon  polls  the  UPS  for  status.
	      This  rate  is  automatically set to 1 second when the UPS goes on
	      battery and reset to the specified value when  the  utility  power
	      returns.	This setting applies both to directly-attached UPSes and
	      networked UPSes.	A low setting will improve the daemon's  respon-
	      siveness	to certain events at the cost of higher CPU utilisation.
	      The default of 60 is appropriate for most situations.

     LOCKFILE <path>

	      apcupsd creates a lockfile for the serial or USB port in the spec-
	      ified directory.	It must be changed when running  more  than  one
	      copy of apcupsd on the same computer to control multiple UPSes.

     SCRIPTDIR <path>

	      Directory  in which apccontrol and event scripts are located.  De-
	      faults to /usr/local/etc/apcupsd.  It must be changed when running
	      more than one copy of apcupsd on the same computer to control mul-
	      tiple UPSes.

     PWRFAILDIR <path>

	      Directory in which apcupsd writes the powerfail flag file  created
	      when apcupsd initiates a system shutdown. The directory is checked
	      in  halt	scripts to determine if turning off the UPS output power
	      is required.  Defaults to /var/run.  It must be changed when  run-
	      ning more than one copy of apcupsd on the same computer to control
	      multiple UPSes.

     NOLOGINDIR <path>

	      Directory in which apcupsd writes the nologin file which tells the
	      OS  to  disallow	new  logins.  Defaults	to /var/run.  It must be
	      changed when running more than one copy of  apcupsd  on  the  same
	      computer to control multiple UPSes.

   NIS CONFIGURATION DIRECTIVES
     NETSERVER [ on | off ]

	      Turns  the  network  information	server (NIS) on or off. When on,
	      apcupsd serves status and  event	information  over  the	network.
	      This information is also used by the web-based CGI monitoring pro-
	      grams. The default is set to on.

     NISIP <IP address>

	      Specifies the IP address of the network interface on which apcupsd
	      will listen for incoming connections. The default value is 0.0.0.0
	      which means the NIS will listen for connections on all network in-
	      terfaces.  If  the  computer  has more than one interface, you can
	      specify the IP of a single interface to limit connections to  that
	      interface.  Specifying the loopback address (127.0.0.1) will cause
	      the NIS daemon to accept connections only from the local computer.

     NISPORT <port>

	      Specifies  the  port  to be used by the NIS daemon. The default is
	      3551 which has been received from IANA  as  the  official  apcupsd
	      networking  port.   It  must be changed when running more than one
	      copy of apcupsd on the same computer to control multiple UPSes.

     EVENTSFILE <filename>

	      If you want NIS to provide the last 10 events via the network, you
	      must specify a file where apcupsd will save these events. The  de-
	      fault  is: /var/log/apcupsd.events.  apcupsd will save at most the
	      last 50 events to this file. When more than 50  events  are  saved
	      and  a  network request for the events arrives, apcupsd will trun-
	      cate the file to the most recent 10 events.  It  must  be  changed
	      when running more than one copy of apcupsd on the same computer to
	      control multiple UPSes.

   LOGGING CONFIGURATION DIRECTIVES
     STATTIME <seconds>

	      Specifies  the time interval between writes to the status file. If
	      set to zero, the status file will not be written. The status  file
	      will  disappear  in a future  apcupsd version as its functionality
	      has been replaced by the Network Information Server and the apcac-
	      cess(8) program.

     STATFILE <file>

	      Specifies the file to be used when writing the status information.
	      The default is /etc/apcupsd/apcupsd.status.  It  must  be  changed
	      when running more than one copy of apcupsd on the same computer to
	      control multiple UPSes.

     LOGSTATS [ on | off ]

	      Activate	log file. This generates a lot of output, so if you turn
	      this on, be sure that  the  file	defined  in  syslog.conf(5)  for
	      LOG_NOTICE is a named pipe.

     DATATIME <seconds>

	      Specifies  the  time interval between writes of the APC PowerChute
	      software-like data information to the log file.

     FACILITY <log-facility>

	      Change the system logging (syslog) facility. The default	is  dae-
	      mon.   This  parameter  can  be  useful  if you wish to direct the
	      apcupsd system logging information to other than your  system  de-
	      fault files.  See syslog.conf(5) for details of other possible fa-
	      cilities and general system logging configuration.

   POWER FAILURE CONFIGURATION DIRECTIVES
     ONBATTERYDELAY <seconds>

	      The  number of seconds from when a power failure is detected until
	      apcupsd reacts with an onbattery event.

     BATTERYLEVEL <percentage>

	      apcupsd will shutdown the system during a power failure  when  the
	      remaining  battery  charge  falls  below the specified percentage.
	      The default is 5.

     MINUTES <minutes>

	      apcupsd will shutdown the system during a power failure  when  the
	      remaining runtime on batteries as internally calculated by the UPS
	      falls below the specified minutes. The default is 3.

     TIMEOUT <seconds>

	      After a power failure occurs, apcupsd will shutdown the system af-
	      ter  the	specified  number of seconds have expired.  For a Smart-
	      UPS, this should normally be set to zero so that the shutdown time
	      will be determined by the battery level or remaining runtime  (see
	      above).  This  command is, however, useful for a Back-UPS or other
	      simple signalling UPS which does not report battery level  or  the
	      remaining  runtime.  It is also useful for testing apcupsd because
	      you can force a rapid shutdown by setting a small  value	(eg  60)
	      and turning off the power to the UPS.

	      TIMEOUT,	BATTERYLEVEL,  and  MINUTES can all be set without prob-
	      lems.  apcupsd will initiate a shutdown when the	first  of  these
	      conditions becomes valid.

     ANNOY <seconds>

	      Specifies  the time in seconds between broadcast messages request-
	      ing logged in users to log off from the system. This timer  starts
	      only  when  the UPS is running on battery. The default is 300 sec-
	      onds (5 minutes).

     ANNOYDELAY <seconds>

	      Specifies the delay time in seconds before broadcast messages  re-
	      questing	logged	in  users to log off from the system. This timer
	      starts only after the UPS is running on battery power. This  timer
	      is reset when the power returns. The default is 60 seconds (ie the
	      first  request  to  log  off  occurs  after  60 seconds on battery
	      power).

     NOLOGON [ disable | timeout | percent | minutes | always ]

	      Specifies when apcupsd should create the nologon file  to  prevent
	      users from logging on to the system.

	      "disable" prevents apcupsd from creating the nologin file.

	      "timeout"  specifies  a  specific wait time before apcupsd creates
	      the nologin file.

	      "percent" specifies the percentage of battery charge remaining be-
	      fore apcupsd creates the nologin file.

	      "minutes" specifies the battery runtime remaining  before  apcupsd
	      creates the nologin file.

	      "always" specifies that apcupsd should create the nologin file im-
	      mediately after a power failure occurs.

	      This directive is important for allowing systems with BIG UPSes to
	      run  normally  until  the system administrator determines the need
	      for dumping users.  It also allows  the  system  administrator  to
	      hold the "ANNOY" factor until the /etc/nologin file is created.

     KILLDELAY <seconds>

	      Specifies  the  number  of seconds for which apcupsd will continue
	      running after a shutdown has been requested. After  the  specified
	      time,  apcupsd will attempt to put the UPS into hibernate mode and
	      kill the power to the computer. This is for use on operating  sys-
	      tems  where  apcupsd  cannot  regain  control after a shutdown (eg
	      FreeBSD) to issue an apcupsd --killpower command. Setting the  de-
	      lay to 0 disables it.

   SHARE-UPS CONFIGURATION DIRECTIVES
     UPSCLASS [ standalone | shareslave | sharemaster ]

	      The  default  is "standalone" and should be used for all computers
	      powered by the UPS,  with a direct connection to the UPS and where
	      there are no other computers dependent on power from the UPS. This
	      is the "normal" case.

	      Use "shareslave" if you are using a Share-UPS  interface	expander
	      and connected to the BASIC port (simple signalling).

	      Use "sharemaster", if you are using a Share-UPS interface expander
	      and connected to the ADVANCED port (smart signalling).

     UPSMODE [ disable | share ]

	      Set  to "disable" for normal standalone operation to indicate that
	      you are disabling the Share-UPS interface expander support.

	      Set to "share" for two to seven additional simple signalling ports
	      on a Share-UPS interface expander. This  code  may  not  be  fully
	      tested in every new release.

   APCTEST EEPROM CONFIGURATION DIRECTIVES
     These  directives have no effect on the operation of apcupsd(8) but are re-
     served for use by apctest(8) when bulk programming the values  of	the  UPS
     EEPROM configuration variables in a Smart-UPS model.

     UPSNAME <string>

	      Name of UPS. Maximum of 8 characters.

     BATTDATE [ mm/dd/yy | dd/mm/yy ]

	      Last battery replacement date. Maximum of 8 characters.

     SENSITIVITY [ H | M | L ]

	      H : High (most sensitive setting)
	      M : Medium
	      L : Low (least sensitive setting)

     WAKEUP [ 000 | 060 | 180 | 300 ]

	      The  time  delay in seconds that the UPS waits after the return of
	      utility power before "waking up" and restoring power to  the  con-
	      nected equipment.

     SLEEP [ 020 | 180 | 300 | 600 ]

	      The  time delay in seconds for which the UPS waits or "sleeps" af-
	      ter it receives a request to power off the connected system.

     LOTRANSFER <voltage>

	      Low line voltage causing transfer to battery power  or  activation
	      of  SmartBoost.  Allowable values depend on the last letter of the
	      firmware or APCMODEL.  Typical values are:

		D  106	103  100  097
		M  177	172  168  182
		A  092	090  088  086
		I  208	204  200  196

	      where D = domestic (USA), M = Canada, A = Asia and  I  =	Interna-
	      tional.

     HITRANSFER <voltage>

	      High  line voltage causing transfer to battery power or activation
	      of SmartTrim.  Allowable values depend on the last letter  of  the
	      firmware or APCMODEL.  Typical values are:

		D  127	130  133  136
		M  229	234  239  224
		A  108	110  112  114
		I  253	257  261  265

	      where  D	=  domestic (USA), M = Canada, A = Asia and I = Interna-
	      tional.

     RETURNCHARGE [ 00 | 15 | 50 | 90 ]

	      Percentage of battery charge needed for the UPS to  restore  power
	      to the connected equipment.

     BEEPSTATE [ 0 | T | L | N ]

	      Alarm delay.

	      0 : Zero delay after power fails.
	      T : When power fails plus 30 seconds.
	      L : When low battery occurs.
	      N : Never.

     LOWBATT <minutes>

	      Low  battery  warning  occurs when the specified number of minutes
	      remains before the UPS estimates battery power will be  exhausted.
	      There are four user-changeable settings: 2, 5, 7, or 10 minutes

     OUTPUTVOLTS <voltage>

	      UPS  nominal  output  voltage  when running on battery.  Allowable
	      values depend on the last letter	of  the  firmware  or  APCMODEL.
	      Typical values are:

		D  115
		M  208
		A  100
		I  230	240  220  225

	      where  D	=  domestic (USA), M = Canada, A = Asia and I = Interna-
	      tional.

     SELFTEST [ 336 | 168 | ON | OFF ]

	      Self test interval in hours (336 = 2 weeks, 168 = 1 week, ON =  at
	      power on, OFF = never).

EXAMPLES
     Note  that  in the following examples, the device names assume that you are
     using Linux. Device names for serial devices in *BSD  and	other  operating
     systems will be different.

   Minimal USB Configuration for a USB UPS
	  UPSCABLE usb
	  UPSTYPE usb
	  DEVICE
	  LOCKFILE /var/lock
	  UPSCLASS standalone
	  UPSMODE disable

     Notice no device name is specified.  apcupsd(8) will try all the well known
     USB ports. Only specify a specific USB device name if you know what you are
     doing.  For detailed information on setting up a USB UPS, refer to the "USB
     Configuration" section of the apcupsd manual.

   Minimal Serial Configuration for a Smart UPS
	  UPSCABLE smart
	  UPSTYPE apcsmart
	  DEVICE /dev/ttyS0
	  LOCKFILE /var/lock
	  UPSCLASS standalone
	  UPSMODE disable

     Normally there would be more configuration directives  to	completely  cus-
     tomise your installation, but this example shows the minimum required.

   Minimal Serial Configuration for a Dumb UPS
	  UPSCABLE <number of the cable used>
	  UPSTYPE dumb
	  DEVICE /dev/ttyS0
	  LOCKFILE /var/lock
	  UPSCLASS standalone
	  UPSMODE disable

     If  your  cable does not have low battery detection (eg such cables include
     the APC 940-0020B and 940-0023A), you will also need to define the  TIMEOUT
     <seconds>	configuration  directive to set the number of seconds on battery
     during a power failure after which apcupsd will do a system shutdown.

     Normally there would be more configuration directives  to	completely  cus-
     tomise your installation, but this example shows the minimum required.

FILES
     /etc/apcupsd/apcupsd.conf default configuration file

SEE ALSO
     syslog.conf(5), apcupsd(8), apctest(8).

     The  HTML	apcupsd  manual  installed on your system or available online at
     http://www.apcupsd.org/

AUTHORS
     Trevor Roydhouse (current)
     Andre M. Hedrick
     Christopher J. Reimer

apcupsd.conf v3.14.6		January 10, 2009		 APCUPSD.CONF(5)