BESTUPS(8)			   NUT Manual			      BESTUPS(8)

NAME
     bestups - Driver for Best Power / SOLA (Phoenixtec protocol) UPS equipment

SYNOPSIS
     bestups -h

     bestups -a UPS_NAME [OPTIONS]

	 Note

	 This  man  page  only	documents  the hardware-specific features of the
	 bestups driver. For information about	the  core  driver,  see  nutups-
	 drv(8).

NOTE
     Please  note that this driver is deprecated and will not receive new devel-
     opment. If it works for managing your devices -- fine, but if you are  run-
     ning  it  to  try	setting  up a new device, please consider the newer nut-
     drv_qx(8) instead, which should handle all Q* protocol variants for NUT.

     If your device works with this driver, but does not work with nutdrv_qx(8),
     please report this via the mailing list or issue tracker.

SUPPORTED HARDWARE
     bestups was designed to monitor Best Power UPS hardware like the  Fortress,
     Fortress  Telecom, Axxium Rackmount and Patriot Pro. It also recognizes and
     supports SOLA units such as the 325, 520 and 620. In addition, the Best 610
     is supported using the `ID' option.

     Other UPS hardware using the Phoenixtec protocol should also work, but they
     will generate a warning since their battery information is not known.

     This driver does  not  support  some  older  Best/SOLA  units.  (For  older
     Fortress units, see bestfortress(8).)

EXTRA ARGUMENTS
     This driver supports the following optional settings in the ups.conf(5):

     nombattvolt=num
	 Override the battery float voltage which is normally determined by ask-
	 ing  the  hardware.  This is useful if your UPS constantly reports bat-
	 tery.charge values just below 100% even when it's completely charged.

	 If you have this problem, set this to whatever battery.voltage  reports
	 when the UPS is known to be completely charged with a good battery.

	 The author's Best Fortress 750 uses nombattvolt=27.4.

     battvoltmult=num
	 Multiply  the reported battery voltage by this number. Some devices re-
	 port only a fraction of the total battery voltage.

	 For example, the SOLA 610 700VA UPS (with a 24V  battery)  reports  the
	 single  cell voltage (about 2.27V when fully charged). In this particu-
	 lar case you can set battvoltmult = 12 in ups.conf(5) to fix this.

     ID=string
	 Set the Identification response string. This should only be  used  with
	 hardware that supports the Phoenixtec protocol status inquiry commands,
	 but  not  the "ID" command, such as the Best/SOLA 610. Format of the ID
	 string is: AAA,BBBB,CCC,DDD,EE.E,FF.F

	 AAA is the three-character identification for the UPS model.

	 BBBB is the output power in VA (volt amperes). B is an  integer  number
	 ranging from 0 to 9.

	 CCC is the Nominal Input Voltage. C is an integer number ranging from 0
	 to 9. The unit is Volts AC.

	 DDD  is the Nominal Output Voltage. D is an integer number ranging from
	 0 to 9. The unit is Volts AC.

	 EE.E is the Battery Voltage that will cause the UPS to shut itself off.
	 E is an integer number ranging from 0 to 9. Then unit is Volts DC and a
	 decimal point is present.

	 FF.F or FFF.F is the Battery Voltage at full charge. F  is  an  integer
	 number  ranging  from	0  to  9.  Then unit is Volts DC. Typically, for
	 700VA, 1KVA and 1.5KVA units, the format is FF.F.  For  2KVA  and  3KVA
	 units, the format is FFF.F.

	 Example:    a	 Best	610   1.5KVA   unit   would   use   the   string
	 "610,1500,120,120,10.0,48.0".

BUGS
     The battery charge percentage value (in battery.charge) is derived from the
     voltage data that the UPS returns, since the UPS doesn't return that  value
     directly.	On some hardware, the charge will remain at 100% for a long time
     and then drops quickly shortly before the battery runs out. You can confirm
     from the battery.voltage readings that this is a problem with the	UPS  and
     not this driver.

     Similarly,  the  float  from  the charger in some models forces the battery
     charge percentage back up to 100%	immediately  after  the  UPS  goes  back
     on-line, so you can't tell when it is really recharged.

     Finally,  some  models give one value for the battery's nominal voltage and
     yet actually have a nominal voltage slightly  below  that.  This  leads  to
     things  such  as  the  perpetual 98.7% charge on the author's Fortress 750,
     even when it's been  charging  for  weeks.  You  can  use	nombattvolt=  in
     ups.conf(5) to fix this.

AUTHORS
     *	 Russell Kroll

     *	 Jason White

SEE ALSO
   The core driver:
     nutupsdrv(8)

   Internet resources:
     The NUT (Network UPS Tools) home page: https://www.networkupstools.org/

Network UPS Tools 2.8.5.	   08/04/2026			      BESTUPS(8)