GENERIC_MODBUS(8)		   NUT Manual		       GENERIC_MODBUS(8)

NAME
     generic_modbus  -	Driver for contact (direct) signal UPS devices connected
     via modbus remote I/O gateways

SYNOPSIS
     generic_modbus -h

     generic_modbus -a DEVICE_NAME [OPTIONS]

	 Note

	 This man page only documents the specific features of the  generic_mod-
	 bus driver. For information about the core driver, see nutupsdrv(8).

SUPPORTED HARDWARE
     This is a generic modbus driver expected to work with contact (direct) sig-
     nal  UPS  devices,  connected  via modbus RIO (remote I/O) either serial or
     TCP/IP.

     The driver has been tested against  PULS  UPS  (model  UB40.241)  via  MOXA
     ioLogikR1212 (RS485) and ioLogikE1212 (TCP/IP).

     More information about this UPS can be found here:
	 https://products.pulspower.com/ca/ubc10-241-n1.html

     More information about Moxa ioLogik R1212, E1212 can be found here:
	 https://www.moxa.com/en/products/industrial-edge-connectivity/con-
	 trollers-and-ios

     The PULS UPS UB40.241 supports the following signals:

	 Ready contact	    (DO) <--> HB
	 Buffering contact  (DO) <--> OL | OB
	 Battery-low	    (DO) <--> LB
	 Replace Battery    (DO) <--> RB
	 Inhibit	    (DI) <--> FSD

     Digital port direction (DI/DO) assumes the device perspective

     The  driver's concept is to map the UPS states (as defined in NUT) onto UPS
     contacts' states. The driver has an extended configuration interface imple-
     mented using variables defined in ups.conf.

HARDWARE INTERCONNECTION
     The commission of modbus remote I/O server as well as UPS device is carried
     out following the corresponding instruction manuals. The  following  figure
     depicts the anticipated communication path and hardware interconnection:

	 +------+	+----------------+	 +------------+       +------------+
	 | UPSD | <---> | GENERIC_MODBUS | <---> | MODBUS RIO | <---> | UPS DEVICE |
	 +------+  (1)	+----------------+  (2)  +------------+  (3)  +------------+
	    |			|
	    +-------------------+
	       HOST CONTROLLER

	 (1) Unix IPC
	 (2) RS232 | TCP/IP
	 (3) contacts

EXTRA ARGUMENTS
     This  driver  supports  the  following optional settings in the ups.conf(5)
     file:

   Generic:
     device_mfr=value
	 A string specifying the manufacturer of the  UPS  device  (default  UN-
	 KNOWN).

     device_model=value
	 A string specifying the model of the UPS device (default UNKNOWN).

   Serial:
     ser_baud_rate=value
	 A integer specifying the serial port baud rate (default 9600).

     ser_data_bit=value
	 A integer specifying the serial port data bit (default 8).

     ser_parity=value
	 A character specifying the serial port parity (default N).

     ser_stop_bit=value
	 An integer specifying the serial port stop bit (default 1).

   Modbus:
     rio_slave_id=value
	 An integer specifying the RIO modbus slave ID (default 1).

   States (X = OL, OB, LB, HB, RB, CHRG, DISCHRG, FSD)
     <X>_addr=value
	 A number specifying the modbus address for the X state.

     <X>_regtype=value
	 A number specifying the modbus register type for the X state

     Default values:

	     1 for X = OL, OB, LB ,HB, RB, CHRG, DISCHRG
	     0 for X = FSD

     Valid values:

	     0:COIL, 1:INPUT_B, 2:INPUT_R, 3:HOLDING

     <X>_noro=value
	 A  number specifying the contact configuration for the X state (default
	 1).

     Valid values:

	     0:NC, 1:NO

	     Note
	     NO stands for normally open and NC for normally closed contact

   Shutdown
     FSD_pulse_duration=value
	 A number specifying the duration in milliseconds for the inhibit pulse.
	 If it's not defined,  signal  has  only  one  transition  depending  on
	 FSD_noro configuration.

	 Examples for FSD signal configuration:

	 FSD_noro = 1
	 FSD_pulse_duration = 150

			      +-----+
			      |     |
	 inhibit pulse	>-----+     +------------------>
			       <--->
			       150ms

	 FSD_noro = 0

	 inhibit pulse	>-----+
			      |
			      +------------------------>

CONFIGURATION
     Here is an example of generic_modbus driver configuration in ups.conf file:

	 [generic_modbus]
	   driver = generic_modbus
	   port = /dev/ttyUSB0
	   desc = "generic ups driver"
	   # device info
	   device_mfr = "PULS"
	   device_model = "UB40.241"
	   # serial settings
	   ser_baud_rate = 9600
	   ser_parity = N
	   ser_data_bit = 8
	   ser_stop_bit = 1
	   # modbus slave id
	   rio_slave_id = 5
	   # UPS signal state attributes
	   OB_addr = 0x0
	   OB_regtype = 1
	   OB_noro = 0
	   LB_addr = 0x1
	   LB_regtype = 1
	   HB_addr = 0x2
	   HB_regtype = 1
	   RB_addr = 0x3
	   RB_regtype = 1
	   FSD_addr = 0x0
	   FSD_regtype = 0
	   FSD_pulse_duration = 150

INSTANT COMMANDS
     This driver support the following instant commands:

     load.off
	 executes "instant poweroff"

INSTALLATION
     This  driver  may	be  not built by default. You can build it by installing
     libmodbus and running configure --with-modbus=yes.

     You also need to give proper permissions on the local  serial  device  file
     (/dev/ttyUSB0 for example) to allow the run-time NUT driver user account to
     access it.

OTHER NOTES
     The  generic_modbus driver intends to support generic UPS devices with con-
     tact signals through modbus TCP/RTU gateways (also known as RIO  --  remote
     I/Os). The data and signal path looks like this:

	 [UPSD] <--- IPC ---> [GENERIC_UPS] <--- modbus TCP/RTU ---> MODBUS-RIO <--- contacts ---> [UPS DEVICE]

     On  the  other hand, you can setup any kind of modbus server, and configure
     the generic_modbus driver to connect and read or write specific  registers.
     Your  application	/  modbus server could then drive NUT statuses (e.g. OL,
     OB, HB etc) by writing over those registers.

KNOWN ISSUES
   Using host names for UPS NMC
     An UPS network management card may be assigned a fixed/static IP address or
     a dynamic one (e.g. by DHCP) in your network. Due to this, you may want  or
     have  to use a dynamic naming service to access the UPS. Note that this may
     become a problem specifically during large outages and shutdowns, when your
     DHCP/DNS server might already go down while the driver needs to resolve the
     name involved (especially during late-shutdown hooks, when a  new	instance
     of  the  driver program might start just to tell the UPS to power off or to
     power-cycle).

     It may be wise to ensure your OS name service client can cache the UPS name
     sufficiently long,  or  to  use  fixed  IP  addressing  (and  an  entry  in
     /etc/hosts  for  good  measure,  so  you  only  have one spot to eventually
     re-configure this).

AUTHOR
     Dimitris Economou <dimitris.s.economou@gmail.com>

SEE ALSO
   The core driver:
     nutupsdrv(8), ups.conf(5)

   Internet resources:
     *	 The NUT (Network UPS Tools) home page: https://www.networkupstools.org/

     *	 libmodbus home page: http://libmodbus.org

Network UPS Tools 2.8.5.	   08/04/2026		       GENERIC_MODBUS(8)