GENERICUPS(8)			   NUT Manual			   GENERICUPS(8)

NAME
     genericups - Driver for contact-closure UPS equipment

SYNOPSIS
     genericups -h

     genericups -a UPS_NAME [OPTIONS]

	 Note

	 This  man  page  only documents the specific features of the genericups
	 driver. For information about the core driver, see nutupsdrv(8).

SUPPORTED HARDWARE
     This driver supports hardware from many different manufacturers as it  only
     uses  the	very  simplest of signaling schemes. Contact closure refers to a
     kind of interface where basic high/low signals  are  provided  to	indicate
     status. This kind of UPS can only report line power and battery status.

     This means that you will only get the essentials in ups.status: OL, OB, and
     LB  (some	UPSes  may also support RB and BYPASS). Anything else requires a
     smarter UPS.

CABLING
     Cabling is different for every kind of UPS. See the table below for  infor-
     mation on what is known to work with a given UPS type.

EXTRA ARGUMENTS
     This driver supports the following settings in the ups.conf(5):

     upstype=type
	 Required. Configures the driver for a specific kind of UPS. See the UPS
	 Types	section  below	for more information on which entries are avail-
	 able.

     mfr=string
	 Optional. The very nature of a generic UPS driver sometimes means  that
	 the stock manufacturer data has no relation to the actual hardware that
	 is  attached.	With  the  mfr setting, you can change the value that is
	 seen by clients that monitor this UPS.

     model=string
	 Optional. This is like mfr above, but it overrides the model string in-
	 stead.

     serial=string
	 Optional. This is like mfr above and intended to record the identifica-
	 tion string of the UPS. It is	titled	"serial"  because  usually  this
	 string is referred to as the serial number.

     sdtime=value
	 Optional. The driver will sleep for this many seconds after setting the
	 shutdown  signal.  This is necessary for some hardware which requires a
	 sustained level to activate the shutdown sequence.

	 The default behavior of the driver is	to  exit  immediately.	If  this
	 doesn't reliably trigger a shutdown in your UPS hardware, use this set-
	 ting to give it more time to react.

	 Note

	 Very  large  values for sdtime may create warnings from upsdrvctl if it
	 gets tired of waiting for the driver to return.

CUSTOM CONFIGURATIONS
     You may override the values for CP, OL, LB, and SD by defining them in  the
     ups.conf(5) after the upstype setting.

     For  example,  to	set  the cable power to DTR and the low battery value to
     DCD, it would look like this:

		 CP = DTR

		 LB = DCD

     Recognized values for input lines are CTS, DCD, and RNG. Recognized  values
     for  output lines are DTR, RTS, and ST. See below for more about what these
     signals mean.

     These values may be negated for active low signals. That is, LB=-DCD recog-
     nizes a low battery condition when DCD is not held high.

TYPE INFORMATION
     The essence of a UPS definition in this driver is how it  uses  the  serial
     lines that are available. These are the abbreviations you will see below:

     OL
	 On line (no power failure) (opposite of OB -- on battery)

     LB
	 Low battery

     RB
	 Replace battery

     BYPASS
	 Battery bypass active or no battery installed

     SD
	 Shutdown load

     CP
	 Cable power (must be present for cable to have valid reading)

     CTS
	 Clear to Send. Received from the UPS.

     RTS
	 Ready to Send. Sent by the PC.

     DCD
	 Data Carrier Detect. Received from the UPS.

     RNG
	 Ring indicate. Received from the UPS.

     DTR
	 Data Terminal Ready. Sent by the PC.

     DSR
	 Data Set Ready. Received from the UPS.

     ST
	 Send a BREAK on the transmit data line

     NULL
	 Disable  this	signal. Disabled signal will always be low except for OL
	 which will always be high.

     none
	 Alias to NULL which matches some other documentation.

     A - in front of a signal name (like -RNG) means that the  indicated  condi-
     tion  is  signaled  with an active low signal. For example, [LB=-RNG] means
     the battery is low when the ring indicate line goes low, and that the  bat-
     tery is OK when that line is held high.

UPS TYPES
     0 = UPSonic LAN Saver 600

	 [CP=DTR+RTS] [OL=-CTS] [LB=DCD] [SD=DTR]

     1 = APC Back-UPS/Back-UPS Pro/Smart-UPS with 940-0095A/C cable

	 [CP=DTR] [OL=-RNG] [LB=DCD] [SD=RTS]

     2	= APC Back-UPS/Back-UPS Pro/Smart-UPS with 940-0020B cable (Note: Type 2
     has also been reported to work with the 940-0020C cable).

	 [CP=RTS] [OL=-CTS] [LB=DCD] [SD=DTR+RTS]

     3 = PowerTech Comp1000 with DTR cable power

	 [CP=DTR] [OL=CTS] [LB=DCD] [SD=DTR+RTS]

     4 = Generic RUPS Model

	 [CP=RTS] [OL=CTS] [LB=-DCD] [SD=-RTS]

     5 = Tripp Lite UPS with Lan2.2 interface (black 73-0844 cable)

	 [CP=DTR] [OL=CTS] [LB=-DCD] [SD=DTR+RTS]

     6 = Best Patriot with INT51 cable

	 [CP=DTR] [OL=CTS] [LB=-DCD] [SD=RTS]

     7 = CyberPower Power99 Also Upsonic Power Guardian  PG-500,  Belkin  Belkin
     Home Office, F6H350-SER, F6H500-SER, F6H650-SER, Eaton Management Card Con-
     tact -- Config3 with cable 66033 (shutdown does not work)

	 [CP=RTS] [OL=CTS] [LB=-DCD] [SD=DTR]

     8 = Nitram Elite 500

	 [CP=DTR] [OL=CTS] [LB=-DCD] [SD=???]

     9 = APC Back-UPS/Back-UPS Pro/Smart-UPS with 940-0023A cable

	 [CP=none] [OL=-DCD] [LB=CTS] [SD=RTS]

     10 = Victron Lite with crack cable

	 [CP=RTS] [OL=CTS] [LB=-DCD] [SD=DTR]

     11 = Powerware 3115

	 [CP=DTR] [OL=-CTS] [LB=-DCD] [SD=ST]

     12 = APC Back-UPS Office with 940-0119A cable

	 [CP=RTS] [OL=-CTS] [LB=DCD] [SD=DTR]

     13 = RPT Repoteck RPT-800A/RPT-162A

	 [CP=DTR+RTS] [OL=DCD] [LB=-CTS] [SD=ST]

     14 = Online P-series

	 [CP=DTR] [OL=DCD] [LB=-CTS] [SD=RTS]

     15 = Powerware 5119, 5125

	 [CP=DTR] [OL=CTS] [LB=-DCD] [SD=ST]

     16 = Nitram Elite 2002

	 [CP=DTR+RTS] [OL=CTS] [LB=-DCD] [SD=???]

     17 = PowerKinetics 9001

	 [CP=DTR] [OL=CTS] [LB=-DCD] [SD=???]

     18 = TrippLite Omni 450LAN with Martin's cabling

	 [CP=DTR] [OL=CTS] [LB=DCD] [SD=none]

     19 = Fideltronic Ares Series

	 [CP=DTR] [OL=CTS] [LB=-DCD] [SD=RTS]

     20 = Powerware 5119 RM (check docs/cables/powerware.txt in NUT sources)

	 [CP=DTR] [OL=-CTS] [LB=DCD] [SD=ST]

     21 = Generic RUPS 2000 (Megatec M2501 cable)

	 [CP=RTS] [OL=CTS] [LB=-DCD] [SD=RTS+DTR]

     22 = Gamatronic All models with alarm interface (also CyberPower SL series)

	 [CP=RTS] [OL=CTS] [LB=-DCD] [SD=DTR]

     23 = Generic FTTx (Fiber to the x) battery backup with 4-wire telemetry in-
     terface

	 [CP=RTS] [OL=CTS] [LB=-DCD] [RB=-RNG] [BYPASS=-DSR] [SD=none]

SIMILAR MODELS
     Many  different UPS companies make models with similar interfaces. The RUPS
     cable seems to be especially popular in the "power strip"	variety  of  UPS
     found in office supply stores. If your UPS works with an entry in the table
     above,  but  the  model  or manufacturer information don't match, don't de-
     spair. You can fix that easily by using the mfr and model	variables  docu-
     mented above in your ups.conf(5).

TESTING COMPATIBILITY
     If  your  UPS  isn't listed above, you can try going through the list until
     you find one that works. There is a lot of cable and interface reuse in the
     UPS world, and you may find a match.

     To do this, first make sure nothing important is plugged into  the  outlets
     on  the  UPS,  as you may inadvertently switch it off. Definitely make sure
     that the computer you're using is not plugged into that UPS. Plug in  some-
     thing  small  like  a  lamp so you know when power is being supplied to the
     outlets.

     Now, you can either attempt to make an educated guess based on the documen-
     tation your manufacturer has provided (if any), or just  start  going  down
     the list.

   Step 1
     Pick a driver to try from the list (run genericups -h) and go to step 2.

   Step 2
     Start the driver with the type you want to try, e.g.:

	 genericups -x upstype=n /dev/port

     Let upsd(8) sync up (watch the syslog), and then run upsc(8) to see what it
     found.  If  the  STATUS is correct (should be "OL" for online), continue to
     Step 3, otherwise go back to step 1.

     Alternatively, you can run genericups in debug mode, e.g.:

	 genericups -DDDDD -x upstype=n /dev/port

     In this mode it will be running in the foreground and continuously  display
     the line and battery status of the UPS.

   Step 3
     Disconnect the UPS from the wall/mains power. This is easiest if you have a
     switched  outlet in between it and the wall, but you can also just pull the
     plug to test. The lamp should stay lit, and the  status  should  switch  to
     "OB".  If the lamp went out or the status didn't go to "OB" within about 15
     seconds, go to Step 1. Otherwise, continue to Step 4.

   Step 4
     At this point, we know that OL and OB work. If  nothing  else  beyond  this
     point works, you at least know what your OL/OB value should be.

     Wait for the UPS to start complaining about a low battery. Depending on the
     size  of  your  UPS battery and the lamp's bulb, this could take awhile. It
     should start complaining audibly at some point. When this	happens,  STATUS
     should show "OB LB" within 15 seconds. If not, go to Step 1, otherwise con-
     tinue to Step 5.

   Step 5
     So far: OL works, OB works, and LB works.

     With  the	UPS  running  on  battery, run the genericups driver with the -k
     switch to shut it down.

	 genericups -x upstype=n -k /dev/port

     If the UPS turns off the lamp, you're done. At this point, you  have  veri-
     fied  that the shutdown sequence actually does what you want. You can start
     using the genericups driver with this type number for normal operations.

     You should use your findings to add a section to your ups.conf. Here  is  a
     quick example:

	 [myups]
		 driver = genericups
		 port = /dev/ttyS0
		 upstype = 1

     Change the port and upstype values to match your system.

NEW SUPPORT
     If the above testing sequence fails, you will probably need to create a new
     entry to support your hardware. All UPS types are determined from the table
     in the genericups.h file in the source tree.

     On  a  standard  9  pin serial port, there are 6 lines that are used as the
     standard "high/low" signal levels. 4 of them are incoming (to the PC,  from
     the UPS), and the other 2 are outgoing (to the UPS, from the PC). The other
     3 are the receive/transmit lines and the ground.

     Be  aware	that many manufacturers remap pins within the cable. If you have
     any doubts, a quick check with a multimeter should confirm whether the  ca-
     ble  is straight-through or not. Another thing to keep in mind is that some
     cables have electronics in them to do special things. Some  have  resistors
     and  transistors on board to change behavior depending on what's being sup-
     plied by the PC.

SPECIFIC MODEL NOTES
     These have been contributed by users of this driver.

     The Centralion CL series may power down the load if the  driver  starts  up
     with  the	UPS  running on battery as the default line settings contain the
     shutdown sequence. - Neil Muller

     The Tripp-Lite Internet Office 700 must be used with the black 73-0844  ca-
     ble  instead  of the gray 73-0743 cable. This entry should work with any of
     their models with the Lan 2.2 interface -- see the sticker by the DB9  con-
     nector on the UPS. - Stephen Brown

     Type  5  should  work with the Tripp-Lite Lan 2.1 interface and the 73-0724
     cable. This was tested with the OmniSmart 675 PNP on Red Hat 7.2. - Q Giese

     Types 7 and 10 should both work with the PhoenixTec A1000.

BUGS
     There is no way to reliably detect a contact-closure UPS.	This  means  the
     driver will start up happily even if no UPS is detected. It also means that
     if  the connection between the UPS and computer is interrupted, you may not
     be able to sense this in software.

     Most contact-closure UPSes will not power down the load if the  line  power
     is  present. This can create a race when using secondary upsmon(8) systems.
     See the upsmon(8) man page for more information.

     The solution to both of these problems is to upgrade to  a  smart	protocol
     UPS of some kind that allows detection and proper load cycling on command.

SEE ALSO
   The core driver
     nutupsdrv(8)

   Internet resources:
     The NUT (Network UPS Tools) home page: https://www.networkupstools.org/

Network UPS Tools 2.8.5.	   08/04/2026			   GENERICUPS(8)