NUT(7)				   NUT Manual				  NUT(7)

NAME
     nut - Overview of the Network UPS Tools (NUT)

DESCRIPTION
     The  Network  UPS	Tools (NUT) project provides a free and open source tool
     kit for monitoring and managing different types of power  distribution  de-
     vices,  first  released under such name in 1999 and following up from a few
     earlier projects. Since then, NUT has expanded to cover  thousands  of  de-
     vices  from  hundreds  of vendors, and to handle various device types (UPS,
     ePDU, ATS/STS, solar, blade server IPMI as a sort of PDU  for  the  blades,
     etc.)  all  with a consistent API and data model, which has since been pub-
     lished as The "UPS management protocol", Informational RFC 9271.

     While the project is in active development to support  ever  newer  devices
     and  their  firmwares, as well as operating system releases, one of the in-
     ternally recognized goals is to remain  compatible  with  the  systems  NUT
     could  have been once deployed on: even if vendors of those boxes and oper-
     ating systems no longer exist, the venerable hardware deserves to be  still
     protected with new UPS devices.

     Although  the  original development involved POSIX-compliant operating sys-
     tems, over time NUT for Windows support was also implemented (however as of
     NUT release v2.8.3, it remains not 100% complete) so it is possible to  run
     the whole server and client stack as native Windows programs.

     Most  operating  systems  deliver	NUT as packages built from a certain re-
     lease, which for the project is just a better-tested snapshot  of	on-going
     development with an opinionated choice of build and run-time system config-
     uration options. Some OS distribution maintainers pick fixes from later re-
     leases  to  update their software packages while nominally remaining on the
     same base line version that the corresponding major release of that distri-
     bution originally went with. This allows them to balance delivering  stable
     programs with well-known qualities and minimal downsides for a long stretch
     of  time that this OS release is supported (does not cause headaches during
     minor updates), but misses out on new capabilities, features (and yes,  new
     bugs),  which  the  on-going development regularly adds to the current code
     base du-jour.

     As such, NUT community support for releases (or any other non-current code)
     is generally limited to suggestions based on experience, but any fixes hap-
     pen on the main development branch (there are no release-tracking	branches
     to port such solutions into), and custom builds of NUT would be required to
     apply them in an end-user environment. This workflow is highly automated in
     the project code base (its recipes and scripts), and the packaged dependen-
     cies  or  toolkits needed for a build are documented for numerous platforms
     (see links at the end of this page).

     Thanks to this, the NUT project  is  also	a  wider  open-source  community
     leader  and  reference  in the area of build recipes and testing automation
     for low-level multi-platform Autotools/C/C++ projects in general.

   NUT Architecture
     The project follows a multi-tiered architecture which may seem a  bit  com-
     plex,  but  allows  for flexibility with very different real-life setups to
     handle. In practice, this involves numerous programs (and their  configura-
     tion files) running on the same or different systems (the "network" part in
     the name).

     Many  deployment scenarios are explored in the famous NUT Configuration Ex-
     amples book maintained by Roger Price.

     NUT Drivers

	 The lowest tier comprises NUT drivers, which are programs that can talk
	 a particular protocol over certain media. Some protocols follow an  in-
	 dustry  standard  (like USB HID or SNMP), or are dialects of a de-facto
	 standard (like the originally Megatec "Q*" family of protocols used  by
	 many  other vendors), but many others are vendor-specific. Some devices
	 support several media connection types (e.g. Serial and/or  USB  ports,
	 and/or SNMP for networked management), so there may be several suitable
	 NUT drivers to choose from.

	 The  NUT  drivers  are responsible for translation between NUT standard
	 data point or instant command names and whatever  strings  need  to  be
	 pulled  for  that  particular device. The data is exposed to other pro-
	 grams on the same machine following the NUT Driver/Server Socket Proto-
	 col, which relies on operating system access controls for the UNIX  lo-
	 cal socket file or a Windows named pipe.

	 For  each  monitored  power  distribution device, a NUT driver instance
	 should be running on a machine that has a communication  link	to  that
	 device.

	     Note

	     There  is	currently  no  support for "multiplexing" information or
	     commands for devices  with  multiple-media/multiple-driver  access,
	     e.g.  to gain redundant connection or a better data collection than
	     any one driver provides. For some devices it may be possible to run
	     several drivers independently (probably for your monitoring  system
	     to  cherry-pick data points from one driver or another), while oth-
	     ers might only enable any one link exclusively.

     NUT Data Server

	 A NUT Data Server (upsd(8)) represents one or more NUT drivers that run
	 on the same machine as itself, to provide  networked  access  to  their
	 data or pass around the instant command requests and replies.

	 On  one  side the data server connects to one or more UNIX local socket
	 files or Windows named pipes (one for each running driver), and on  an-
	 other	side  it listens on the TCP/IP network (port 3493 by default) to
	 communicate with local or remote client programs. It is also  responsi-
	 ble  for  communication security for driver access, whether by defining
	 the NUT user account names and  assigned  protocol  access  permissions
	 (for  value-setting  or commands; read access is anonymous), or by han-
	 dling the TLS/SSL part where enabled.

     NUT Clients

	 Practical work visible to end-users is  done  by  a  multitude  of  NUT
	 clients, many of which are delivered by the project itself and more are
	 created and maintained by the community at large. Some standard clients
	 of note include:

	 *   upsmon(8)	is a daemon to monitor primarily the states of UPSes (as
	     opposed to other device types that NUT can handle) which power some
	     power source units of this particular system, and based on how many
	     PSUs are required for the system to run -- initiates a local  shut-
	     down  when too many UPSes are not in a healthy condition. Instances
	     of this client allow a single UPS powering a whole rack or desk  of
	     computers to be seen by each of them (through a data server running
	     on  one  of them, on a machine actually connected to the UPS -- the
	     "primary" system).

		 Note
		 The upsmon client typically splits into two processes:  an  un-
		 privileged one running with credentials of its RUN_AS_USER con-
		 figured  in the upsmon.conf(5) file (or a built-in/packaged de-
		 fault like nut, ups, monuser or nobody) which does most of  the
		 work  (including notification scripts called via NOTIFYCMD set-
		 ting), and the part which remains owned by root to initiate the
		 system shutdown by calling SHUTDOWNCMD when/if the time comes.
	     NUT deployments which desire higher-fidelity control (e.g.  differ-
	     ent  systems  shutting  down after different time spent on battery)
	     often couple the upsmon(8) with upssched(8) as their NOTIFYCMD han-
	     dler.

	     The upsmon primary system waits for secondary systems to disconnect
	     as part of their shut down, and is  usually  also	responsible  for
	     commanding  the  managed  UPS to shut itself down and power up when
	     the "wall power" returns (or to reset the load  if  it  is  already
	     back),  subject  to UPS hardware capabilities. Most client integra-
	     tions also stall the ultimate reboot/power-off of their machine, if
	     its shut down was triggered by upsmon, and reboot after a long  de-
	     lay  (if the machine is still alive). This combined approach allows
	     to avoid the "power race condition", when systems	would  otherwise
	     remain  shut  down  indefinitely  (until  someone comes and reboots
	     them) just because external power returned when the shut down spree
	     had already started.

	 *   upsc(8) is a command-line client for  anonymous  read-only  access,
	     used  to list devices served by a NUT data server, or to query data
	     points reported by a particular device.

	 *   NUT-Monitor(8) is a GUI client for read-only or read-write access.

	 *   A suite of CGI clients can run on a web server like Apache or nginx
	     to provide a simple HTML interface to your devices.

	 Many monitoring systems integrate with NUT (and through it  --  with  a
	 varied  assortment  of power devices), using either simple clients like
	 upsc or upslog, or libraries and bindings provided by the  project  it-
	 self  (e.g.  C,  C++,	Python,  Java  in  a  nearby  repository)  or by
	 third-party efforts (e.g. Perl, Go, C#, REST API).

     NUT Drivers during shutdown

	 Arguably another layer in this three-layer stack is a separate role for
	 the NUT Driver programs on the upsmon(8) primary  system  as  mentioned
	 above:  actually  telling the UPS to turn off or power-cycle as part of
	 your computer's emergency shut down.

	 While the long-running services for the NUT drivers,  data  server  and
	 clients  are  stopped	as  part  of common OS shutdown, there may be an
	 "endgame" integration such as high-numbered  SysV  init  scripts  (e.g.
	 /etc/rc0.d/K99nut) or the systemd shutdown hook facility, or even some-
	 thing	built  into the initrd or similar RAM disk image that originally
	 launched the end-user visible OS and regains control when the	OS  says
	 it  is  done.	Please note that not all operating systems offer ways of
	 such integration, and may resort to other  solutions  (perhaps  calling
	 such logic from the stop method of upsmon init script or service defin-
	 ition).

	 Either  way, this integration has the effect of detecting that the cur-
	 rently processed shutdown is due to an upsmon FSD activity  (e.g.  that
	 the  flag  file  specified by POWERDOWNFLAG configuration option in up-
	 smon.conf(5) exists and is valid), and launches  the  NUT  driver  pro-
	 gram(s)  again  to connect to the UPS(es) that this system is a primary
	 manager of (and has possibly out-of-band connections to), just to  send
	 them the requested command and exit.

	 For  an example of such end-game integration please see the nutshutdown
	 script if available in your packaged distribution, or	its  sources  at
	 https://github.com/networkupstools/nut/blob/master/scripts/systemd/nut-
	 shutdown.in  which  also implements a solution to avoid the "power race
	 condition" (for operating systems that do not	limit  the  duration  of
	 shutdown activity).

   NUT Run-time Nuances
     For  many more notes, please see the Frequently Asked Questions document in
     NUT sources or on the web site. A copy may be delivered by your packaging.

     "File or directory not found" messages

	 When NUT daemon programs start, they check  for  existence  of  certain
	 files they would create themselves (PID files, local sockets, etc.) and
	 report  when  such file does not exist. Similarly, some programs try to
	 signal an earlier instance (if the PID is known) and  would  report  if
	 that failed.

	 While	this does look scary and confusing to people who use NUT for the
	 first time and it greets them with what looks like error  messages  (we
	 did work on improving the wording during the NUT v2.8.x release lineage
	 due  to  frequent  questions),  these messages are in fact just a trou-
	 bleshooting aspect that is useful at that point in program life  cycle:
	 if you expect "other" program instances to be running when they are not
	 seen, this message helps catch the error:

	 *   If  this is a first run, so no artifacts from "another" instance of
	     this program should be there, the message says just that.

	 *   If your program starts and sees an older instance already	running,
	     further  behavior	depends  on  the situation (e.g. did you start a
	     copy to signal the already running daemon with  some  command?  did
	     you start a new copy and so any old one is assumed stuck and should
	     be terminated automatically?)

	 The "directory" part of the wording, which may be present in these mes-
	 sages,  comes	from  the  standard system library. It does not mean you
	 should blindly create a directory (or any other object)  for  the  file
	 names listed in such reports.

	 That  said,  NUT  does use directories (known in code and the configure
	 script    options    as    --with-pidpath,    --with-altpidpath     and
	 --with-statepath)  which should be created and assigned certain permis-
	 sions each (the latter two may overlap). Generally this is done  either
	 by packaging, or by manual steps according to documentation when build-
	 ing  NUT  from  sources. On some platforms (e.g. Linux with systemd and
	 its systemd-tmpfiles subsystem) they may be maintained at  run-time  by
	 configuration files delivered to the system.

	 The  message  can  also be seen from upsmon(8) being unable to populate
	 the POWERDOWNFLAG if the location it points to (/etc/killpower  by  de-
	 fault) does not exist or is read-only, or from a late shutdown integra-
	 tion  script  like the nutshutdown hook if that location was un-mounted
	 by the time it runs. It is recommended to store that file on a volatile
	 file system (under /var/run or /run on most modern distributions; typi-
	 cally the pidpath is located there too), which remains until reboot and
	 disappears during reboot.

     User/Group Accounts

	 Generally NUT daemon programs avoid running as a highly-privileged root
	 account (on POSIX platforms), although they anticipate being started as
	 such (most system services are) and drop privileges to run as the  con-
	 figured user and group accounts such as nut:nut.

	 *   One  notable  exception is the upsmon(8) daemon which splits into a
	     root-owned process which may trigger the OS shutdown  routine,  and
	     an unprivileged process which does everything else.

	 *   Default  user  and group accounts are built-in, selected as options
	     for the configure script when it prepares the build of  NUT.  Those
	     settings  can  be	overridden by configuration file or command-line
	     options of respective NUT daemons, whether to run	as  a  different
	     unprivileged user account (it may be possible to constrain each NUT
	     service  to  run in their dedicated accounts), or to remain capable
	     of everything as root (rarely, drivers are configured this way tem-
	     porarily to troubleshoot local device access).

     File system permissions

	 When using NUT drivers with local communications media (USB  or  Serial
	 ports),  you  must  ensure  that the unprivileged run-time account like
	 nut:nut is allowed access to those device file system	nodes.	On  many
	 platforms  this  can be automated with subsystems like udev, devd, hot-
	 plug, upower; on others (older ones) you may have to  chmod/chown/chgrp
	 particular  devfs nodes (whether on the persistent filesystem, or using
	 an init-script for volatile implementations).

	 Note that there are several run-time  locations  for  data  and  socket
	 files of NUT's privileged and unprivileged programs, and for configura-
	 tion  files. Access to these directories and individual files should be
	 secured according to NUT documentation. NUT daemons will warn about lax
	 permissions in their syslog or console  messages.  Generally,	root:nut
	 and 0640 permissions are correct for most of the files (so the run-time
	 NUT  programs	may only read them but can not rewrite them, not even if
	 there happens to be an exploitable code problem discovered in them over
	 time).

	 It is also important to note that (except for upslog(8)) no NUT daemons
	 leave log files on their own: they send syslog messages,  or  write  to
	 stdout/stderr, and either or both of these streams can be saved to disk
	 by the OS service integration (or a redirection from an init-script).

     NUT Drivers as Service instances

	 Starting with NUT v2.8.0, on systems with service management frameworks
	 (like	Linux  systemd	or Solaris/illumos SMF) you may be even inadver-
	 tently using the nut-driver-enumerator(8) (also known as "NDE")  facil-
	 ity.  This  is  a  script,  which may be also called automatically (via
	 packaging on supported platforms) at start-up or may be running contin-
	 uously as a service, to process the ups.conf(5) file and  maintain  the
	 service  units  (with their dependencies) for each driver section sepa-
	 rately.

	 This sometimes raises eyebrows when end-users try to manually	start  a
	 NUT  driver  program  (either directly or using upsdrvctl(8) tool), and
	 this either fails (because the device is already busy) or gets to  con-
	 flict	with  the  copy of the driver running as a service instance, and
	 they begin to terminate each other.

     Configuring NUT Drivers

	 To get started with the NUT server  system,  you  should  populate  the
	 ups.conf(5)  file with a section per device, which informs both the re-
	 spective drivers, and tools like service-aware upsdrvsvcctl(8) and nut-
	 driver-enumerator(8) or the legacy upsdrvctl(8), and the  upsd(8)  data
	 server, to name a few.

	 In  many  typical cases, the nut-scanner(8) tool can get you started by
	 discovering supported USB, Serial, SNMP, NetXML, IPMI devices,  or  re-
	 mote  NUT  deployments  using	Avahi mDNS or the good old port-knocking
	 scan. This tool would propose a complete section content that	you  can
	 copy-paste  into your ups.conf file (possibly review and adapt the con-
	 tents first, to e.g. add a description meaningful to you like	"UPS  in
	 garage", etc.)

     Other configuration files

	 NUT  sample  configuration  files  (packaged  or  seen in sources under
	 https://github.com/networkupstools/nut/tree/master/conf      directory)
	 start	with  a  heading comment about the minimal set of their required
	 options. Note that many of these files can contain credentials  (either
	 for NUT roles, or for networked power devices as part of their NUT dri-
	 ver  section  configuration) and so these files and any of their backup
	 copies should be secured accordingly.

	 The nut.conf(5) may be used by init-scripts or other system integration
	 code (it notably contains the MODE setting to choose which  profile  of
	 NUT services to start or not on this particular system).

	 On  the  NUT  server  you  would  need  at  least minimally configured:
	 ups.conf(5), upsd.conf(5), upsd.users(5).

	 On the majority of NUT clients (meaning each system monitoring the  UPS
	 state	so  it knows when to trigger its local shutdown), you would need
	 upsmon.conf(5) and depending on your setup, may need a custom NOTIFYCMD
	 or  SHUTDOWNCMD  (if  you  script  something  complex),  and/or   upss-
	 ched.conf(5) and a custom CMDSCRIPT for it.

	 For  NUT  CGI	clients  several files may need to be adapted and placed
	 into	certain   directories	according   to	 their	  documentation:
	 hosts.conf(5)	and  upsset.conf(5) for configuration, and upsstats-sin-
	 gle.html and upsstats.html for HTML UI templates.

	 Other clients, whether delivered by NUT project  (NUT-Monitor(8)  GUI),
	 or   co-located   (WMNut),   or   third-party	(see  https://networkup-
	 stools.org/projects.html), would probably support saving their settings
	 or "favorites". Do not forget to secure access to those files and their
	 copies as well.

USER MANUAL PAGES
	 Note

	 This build of NUT was configured to deliver only manual pages for  pro-
	 grams	that were actually built. For more information about the ecosys-
	 tem  please  see  the	NUT  website   listing	 at   https://networkup-
	 stools.org/docs/man/index.html   or  the  sources  of	these  pages  at
	 https://github.com/networkupstools/nut/tree/master/docs/man

   Configuration files
     *	 nut.conf(5)

     *	 ups.conf(5)

     *	 upsd.conf(5)

     *	 upsd.users(5)

     *	 upsmon.conf(5)

     *	 upssched.conf(5)

     *	 hosts.conf(5)

     *	 upsset.conf(5)

     *	 upsstats.html(5)

   Daemons
     *	 upsd(8)

     *	 upsmon(8)

     *	 upssched(8)

     *	 upslog(8)

   Clients commands
     *	 upsc(8)

     *	 upscmd(8)

     *	 upsrw(8)

     *	 NUT-Monitor(8)

   Configuration commands
     *	 nutconf(8)

     *	 nut-scanner(8)

   CGI programs
     *	 upsimage.cgi(8)

     *	 upsset.cgi(8)

     *	 upsstats.cgi(8)

   Platform management
     Windows

	 *   nut.exe(8)

   Driver control
     *	 upsdrvctl(8)

   Drivers
     *	 nutupsdrv(8)

     *	 adelsystem_cbi(8)

     *	 al175(8)

     *	 apc_modbus(8)

     *	 apcmicrolink(8)

     *	 apcsmart-old(8)

     *	 apcsmart(8)

     *	 apcupsd-ups(8)

     *	 bcmxcp(8)

     *	 bcmxcp_usb(8)

     *	 belkin(8)

     *	 belkinunv(8)

     *	 bestfcom(8)

     *	 bestfortress(8)

     *	 bestuferrups(8)

     *	 bestups(8)

     *	 bicker_ser(8)

     *	 blazer_ser(8)

     *	 blazer_usb(8)

     *	 clone-outlet(8)

     *	 clone(8)

     *	 dummy-ups(8)

     *	 etapro(8)

     *	 everups(8)

     *	 failover(8)

     *	 gamatronic(8)

     *	 generic_modbus(8)

     *	 genericups(8)

     *	 huawei-ups2000(8)

     *	 isbmex(8)

     *	 ivtscd(8)

     *	 liebert-esp2(8)

     *	 liebert-gxe(8)

     *	 liebert(8)

     *	 masterguard(8)

     *	 meanwell_ntu(8)

     *	 metasys(8)

     *	 mge-shut(8)

     *	 mge-utalk(8)

     *	 microdowell(8)

     *	 microsol-apc(8)

     *	 must_ep2000pro(8)

     *	 netxml-ups(8)

     *	 nhs_ser(8)

     *	 nut-upower(8)

     *	 nutdrv_atcl_usb(8)

     *	 nutdrv_hashx(8)

     *	 nutdrv_qx(8)

     *	 nutdrv_siemens-sitop(8)

     *	 oneac(8)

     *	 optiups(8)

     *	 phoenixcontact_modbus(8)

     *	 powercom(8)

     *	 powerman-pdu(8)

     *	 powerpanel(8)

     *	 powervar_cx_ser(8)

     *	 powervar_cx_usb(8)

     *	 ragtech(8)

     *	 rhino(8)

     *	 richcomm_usb(8)

     *	 riello_ser(8)

     *	 riello_usb(8)

     *	 safenet(8)

     *	 sms_ser(8)

     *	 snmp-ups(8)

     *	 socomec_jbus(8)

     *	 solis(8)

     *	 tripplite(8)

     *	 tripplite_usb(8)

     *	 tripplitesu(8)

     *	 upscode2(8)

     *	 usbhid-ups(8)

     *	 ve-direct(8)

     *	 victronups(8)

DEVELOPER MANUAL PAGES
     *	 libupsclient-config(1)

     *	 nut-recorder(8)

     *	 skel(8)

     *	 sockdebug(8)

   Client library
     *	 libnutclient(3)

     *	 libnutclient_commands(3)

     *	 libnutclient_devices(3)

     *	 libnutclient_general(3)

     *	 libnutclient_misc(3)

     *	 libnutclient_tcp(3)

     *	 libnutclient_variables(3)

     *	 upsclient(3)

     *	 upscli_add_host_cert(3)

     *	 upscli_cleanup(3)

     *	 upscli_connect(3)

     *	 upscli_tryconnect(3)

     *	 upscli_disconnect(3)

     *	 upscli_fd(3)

     *	 upscli_get(3)

     *	 upscli_init(3)

     *	 upscli_set_default_connect_timeout(3)

     *	 upscli_get_default_connect_timeout(3)

     *	 upscli_init_default_connect_timeout(3)

     *	 upscli_list_next(3)

     *	 upscli_list_start(3)

     *	 upscli_readline(3)

     *	 upscli_sendline(3)

     *	 upscli_splitaddr(3)

     *	 upscli_splitname(3)

     *	 upscli_ssl(3)

     *	 upscli_strerror(3)

     *	 upscli_upserror(3)

     *	 upscli_str_add_unique_token(3)

     *	 upscli_str_contains_token(3)

   Device discovery library
     *	 nutscan(3)

     *	 nutscan_add_device_to_device(3)

     *	 nutscan_add_ip_range(3)

     *	 nutscan_add_option_to_device(3)

     *	 nutscan_cidr_to_ip(3)

     *	 nutscan_display_parsable(3)

     *	 nutscan_display_sanity_check(3)

     *	 nutscan_display_sanity_check_serial(3)

     *	 nutscan_display_ups_conf(3)

     *	 nutscan_display_ups_conf_with_sanity_check(3)

     *	 nutscan_free_device(3)

     *	 nutscan_free_ip_ranges(3)

     *	 nutscan_get_serial_ports_list(3)

     *	 nutscan_init(3)

     *	 nutscan_init_ip_ranges(3)

     *	 nutscan_ip_ranges_iter_inc(3)

     *	 nutscan_ip_ranges_iter_init(3)

     *	 nutscan_new_device(3)

     *	 nutscan_scan_avahi(3)

     *	 nutscan_scan_eaton_serial(3)

     *	 nutscan_scan_ipmi(3)

     *	 nutscan_scan_nut(3)

     *	 nutscan_scan_nut_simulation(3)

     *	 nutscan_scan_snmp(3)

     *	 nutscan_scan_usb(3)

     *	 nutscan_scan_xml_http_range(3)

     *	 nutscan_stringify_ip_ranges(3)

INTERNET RESOURCES
     *	 The NUT (Network UPS Tools) home page: https://www.networkupstools.org/
	 and specifically the NUT Documentation collection with the FAQ page and
	 several books on different aspects of NUT usage and development,  main-
	 tained as part of the project code base

     *	 The NUT Configuration Examples book, maintained by Roger Price

     *	 Project     GitHub	repository,	wiki	and    issue	tracker:
	 https://github.com/networkupstools/nut

     *	 Commonly referenced articles include:

	 *   The NUT FAQ page

	 *   Changing NUT daemon debug verbosity should be your  first	step  in
	     any troubleshooting

	 *   Build  prerequisites  to make NUT from scratch on various Operating
	     Systems documents the packages you might need to build NUT on about
	     a dozen operating system distributions (most of those  the  NUT  CI
	     farm tests each development iteration on)

	 *   Building  NUT for in-place upgrades or non-disruptive tests details
	     how to build a newer version of NUT than your system packaging pro-
	     vides (as a potential replacement of the older installation),  e.g.
	     to  test  if  some  issue got resolved or if an updated driver sees
	     more information from your device; most  such  tests  can	be  done
	     without  installing  the  new build into your system (not until you
	     like it better than the current deployment)

	 *   Specific bits of know-how and caveats regarding NUT for Windows

     *	 Related projects

     *	 We are on Wikipedia: https://en.wikipedia.org/wiki/Network_UPS_Tools

     *	 The "UPS management protocol", Informational  RFC  9271:  https://data-
	 tracker.ietf.org/doc/html/rfc9271

Network UPS Tools 2.8.5.	   08/04/2026				  NUT(7)