NAME
     nutdrv_siemens-sitop - Driver for the Siemens SITOP UPS500 series UPS

SYNOPSIS
     nutdrv_siemens-sitop -h

     nutdrv_siemens-sitop -a UPS_NAME [OPTIONS]

	 Note

	 This man page only documents the hardware-specific features of the nut-
	 drv_siemens-sitop  driver.  For  information about the core driver, see
	 nutupsdrv(8).

SUPPORTED HARDWARE
     nutdrv_siemens-sitop supports Siemens UPS models from the SITOP UPS500  se-
     ries.  Some  models  have a serial port, others have a USB port. The models
     with USB port actually contain a serial-over-USB chip, so as  far	as  this
     driver  is concerned, all models are serial models. This driver should work
     with all models in the SITOP UPS500 series, as long as your kernel has sup-
     port for the serial port device (see section USB driver below).

	 Note

	 This driver has only been tested with the SITOP  UPS500S-2.5  with  USB
	 port (Siemens product number 6EP1933-2EC41).

DEVICE SETTINGS
     The UPS is configured via DIP-switches. For correct functioning in combina-
     tion with NUT, set the DIP-switches to the following:

     switch 1-4
	 Choose  whatever  suits  your situation. Any combination will work with
	 NUT.

     switch 5 (a / t)
	 Set to OFF (t). This ensures that the UPS will not cut power unless NUT
	 tells it to do so (or unless the batteries are exhausted).

     switch 6-10 (delay)
	 Set to OFF (minimum delay). Setting a higher delay will  actually  also
	 work, but any command from NUT will be delayed as well before being ex-
	 ecuted  by  the  UPS.	With the minimum setting, it will already take 5
	 seconds before a command from NUT is executed.

     switch 11 (INTERR.)
	 Set to ON (interrupt the output after the timer expires). This  ensures
	 that  the  UPS  briefly  interrupts the output power in response to the
	 shutdown.return command. See the section Instant Commands below.

     switch 12 (ON/OFF)
	 set to ON (enable the UPS functionality). Without this,  the  UPS  will
	 never supply power from its batteries.

USB DRIVER
     The  USB-versions	of the UPS contain an FTDI USB-to-serial converter chip.
     It is programmed with a non-standard product ID  (for  example  0403:e0e3),
     but can still be used with the normal ftdi_sio driver.

	 Note

	 The following hints may be specific to GNU/Linux.

     Use lsusb to figure out which product ID is used in your model, and replace
     all  occurrences  of e0e3 in the following examples with the actual Product
     ID.

	 modprobe ftdi_sio
	 echo 0403 e0e3 > /sys/bus/usb-serial/drivers/ftdi_sio/new_id

     If your system uses udev, this can be automated via an udev rule:

	 ACTION=="add", ATTRS{idVendor}=="0403", ATTRS{idProduct}=="e0e3", \
	   RUN+="/sbin/modprobe ftdi_sio", \
	   RUN+="/bin/sh -c 'echo 0403 e0e3 > /sys/bus/usb-serial/drivers/ftdi_sio/new_id'"

     You can use the following udev rule to obtain a  predictable  device  name,
     for example /dev/ttyUPS:

	 SUBSYSTEM=="tty" ATTRS{idVendor}=="0403", ATTRS{idProduct}=="e0e3" SYMLINK+="ttyUPS"

POLLING
     The  UPS  does  not have a special get status command. Instead, it continu-
     ously sends out status update messages (tens of messages per second). Every
     pollinterval, these messages are read from the serial port buffer.

     In order to react quickly on status changes from the UPS,	and  to  prevent
     the  serial  buffer from overflowing, pollinterval should be set to a rela-
     tively low value. The recommended value is 1 (second).

EXTRA ARGUMENTS
     This driver supports the following optional settings:

     max_polls_without_data=num
	 The serial port is polled periodically for new data (see  Polling).  If
	 there is no valid new data after num polls, it is assumed that communi-
	 cation with the UPS is lost.

	 The default value is 2. Lower values may cause spurious Data stale mes-
	 sages, especially at startup.

INSTANT COMMANDS
     shutdown.return
	 The behavior of this command depends on the line state:

	 *   on  line:	after 5 seconds (or longer, if DIP switches 6-10 are not
	     OFF), the UPS will shut off its output. After  another  5	seconds,
	     the output is activated again.

	 *   on  battery:  after  5 seconds (or longer, if DIP switches 6-10 are
	     not OFF), the UPS will shut off its output. The  output  will  stay
	     off, until the line voltage has returned.

     shutdown.stayoff
	 The behavior of this command depends on the line state:

	 *   on  line:	after 5 seconds (or longer, if DIP switches 6-10 are not
	     OFF), the UPS will shut off its output. The output stays off, until
	     the line voltage has been removed for at least 1  second,	and  has
	     been re-applied.

	 *   on battery: this command behaves the same as shutdown.return.

INSTALLATION
     Make  sure  that  your operating system has created a serial device for the
     UPS. See the section USB driver for more information.

     Next, make sure that NUT has access rights to this device file.  For  exam-
     ple, by creating an udev rule that grants permission to the NUT user, or by
     adding  the  NUT  user to a user group that can access serial devices (e.g.
     the dialout group on Debian-based systems).

DIAGNOSTICS
     You can verify the correct functioning of the hardware, by  monitoring  the
     serial port with a terminal program, for example picocom:

	 :; picocom -b 9600 -d 8 -p n /dev/ttyUPS

     NUT  must	not be running when you do this. You should now see a continuous
     stream of 5-character texts coming in, for example:

	 BUFRD
	 BA>85
	 DC_OK

     To exit picocom, use Ctrl-A Ctrl-X.

KNOWN ISSUES AND BUGS
     Untested models
	 As mentioned under Supported hardware, this driver has not been  tested
	 with all models in the SITOP UPS500 series.

     Data stale messages
	 The  firmware	in these UPSes is quite buggy. After sending data to the
	 UPS, it sometimes stops sending status updates. This  driver  tries  to
	 prevent this (e.g. by sending commands twice, and by sending additional
	 LF characters after each command).

	 Once  the  UPS  is in this state, communication can only be restored by
	 rebooting the UPS, or by unplugging and reconnecting the USB cable.

	 During normal operation, no commands are sent to the UPS at  all  (only
	 at  shutdown),  so  this issue is expected to have little impact on us-
	 ability.

	 It is not certain if the serial models are affected by  this  issue  as
	 well.

AUTHOR
     Matthijs H. ten Berge

SEE ALSO
   The core driver:
     nutupsdrv(8)

   Internet resources:
     The NUT (Network UPS Tools) home page: https://www.networkupstools.org/

Network UPS Tools 2.8.5.	   08/04/2026		  NUTDRV_SIEMENS-SITO(8)