NAME
     oneac - Driver for Oneac UPS equipment

SYNOPSIS
     oneac -h

     oneac -a UPS_NAME [OPTIONS]

	 Note

	 This  man  page  only	documents  the hardware-specific features of the
	 oneac driver. For information about the core driver, see nutupsdrv(8).

SUPPORTED HARDWARE
     This driver supports various Oneac UPS families:

     *	 EG (late 80s, early 90s, plug-in serial interface card)

     *	 ON (early and mid-90s, plug-in serial interface card)

     *	 OZ (mid-90s on, DB-25 std., interface slot)

     *	 OB (early 2000's on, big cabinet, DB-25 std., interface slot)

     If your UPS is equipped with the  Basic  Interface  card,	use  the  gener-
     icups(8) driver.

EXTRA ARGUMENTS
     This  driver  supports  the  following optional settings in the ups.conf(5)
     file:

     testtime=num
	 Change battery test time from the 2 minute default.

     offdelay=num
	 Change shutdown delay time from 0 second default.

INSTANT COMMANDS
     This driver supports the following Instant Commands. (See upscmd(8))

   All UPS units
     shutdown.return
	 Turn off the load possibly after a delay and return when power is back.

     shutdown.stop
	 Stop a shutdown in progress.

     shutdown.reboot
	 Shut down the load briefly while rebooting the UPS.

     test.failure.start
	 Starts a 15 second long simulation of an input power failure.

     test.battery.start.quick
	 Start a "quick" battery test. The default time is 2 minutes. This  time
	 can be set in the ups.conf file. See testime above.

     test.battery.stop
	 Stops a battery test that is in progress.

   All ON UPS units
     reset.input.minmax
	 Reset	the minimum and maximum input line voltage values seen since the
	 last reset or power on.

   Newer ON UPS units
     test.panel.start
	 Start testing the UPS panel.

     test.battery.start.deep
	 Start a "deep" battery test. This test runs the UPS until the low  bat-
	 tery point and then returns to the AC line.

     reset.input.minmax
	 Reset	the minimum and maximum input line voltage values seen since the
	 last reset or power on.

     beeper.enable
	 Enable UPS beeper/buzzer.

     beeper.disable
	 Disable UPS beeper/buzzer.

     beeper.mute
	 Mutes the UPS beeper/buzzer for the current alarm condition(s).

WRITABLE VARIABLES
     See upsrw(8) to see what variables are writable for the UPS.

	 Note

	 If your UPS supports writing battery.runtime.low, the new set value  is
	 to  be entered in minutes (up to 99) but the reported value is reported
	 in seconds (set value * 60).

	 Note

	 If your UPS supports input.transfer.low and input.transfer.high,  those
	 values  are  used  to create an allowable output range. The UPS will do
	 what it can to keep the output voltage value within the  defined  range
	 (for example: tap change or switch to inverter).

AUTHORS
     *	 Bill Elliot <bill@wreassoc.com>

     *	 Eric Lawson <elawson@inficad.com>

SEE ALSO
   The core driver:
     nutupsdrv(8)

   Internet resources:
     The NUT (Network UPS Tools) home page: https://www.networkupstools.org/

Network UPS Tools 2.8.5.	   08/04/2026				ONEAC(8)