PHOENIXCONTACT_MODBU(8) 	   NUT Manual		 PHOENIXCONTACT_MODBU(8)

NAME
     phoenixcontact_modbus - Driver for Phoenix Contact

SYNOPSIS
     phoenixcontact_modbus -h

     phoenixcontact_modbus -a DEVICE_NAME [OPTIONS]

	 Note

	 This  man  page  only	documents  the hardware-specific features of the
	 phoenixcontact_modbus driver. For information about  the  core  driver,
	 see nutupsdrv(8).

SUPPORTED HARDWARE
     This  driver should support the PhoenixContact QUINT-UPS industrial DC UPS,
     model 2320461 and all compatible models. More information	about  this  UPS
     can be found among Internet resources below.

     phoenixcontact_modbus  uses  the  libmodbus project, for Modbus implementa-
     tion.

HOW TO CONFIGURE THE UPS
     Note: this UPS and its manual refers to Low-Batt as "Shutdown Event".

     You need the "IFS-RS232-DATACABLE" to communicate with the UPS in Linux  as
     the  IFS-USB  cable doesn't seem to be supported. FYI communication parame-
     ters are: 115200,E,8,1.

     You also need the UPS-CONF Windows  software  (free;  download  from  their
     site), to configure the UPS signals and timers.

      1. Run the UPS-CONF

      2. Go to SettingsaTime Setting

      3. Choose "state of charge shutdown delay"

      4. Choose Remote starts PC-Shutdown in Mains and Battery mode

      5. On the PC-Shutdown enter the maximum value (5 minutes)

       6. On  the  PC-Restart delay enter the time you want the UPS to leave the
	 output power off before restarting (e.g. 60 seconds), after mains power
	 is restored.

      7. On the UPS, turn the screw to the "PC-MODE" position

     Configuring the above way ensures that:

     *	 When power is lost, UPS constantly calculates remaining battery time

     *	 When remaining battery time is less than 5  minutes  (PC-Shutdown  set-
	 ting), it will raise the "Shutdown" event (seen as LOW-BATT in NUT)

     *	 From  that moment even if input power is restored, the UPS will cut the
	 output power to its load after 5 minutes

     *	 When the input power is restored, the UPS will restore output power af-
	 ter 60 seconds (PC-RESTART delay setting).

     Meaning of settings:

     *	 PC-Shutdown: How long before output  cutoff  the  UPS	will  raise  the
	 "shutdown  event" signal. Max value for this is 5 minutes. So PC should
	 be able to shutdown within 5 minutes.

     *	 PC-Restart: How long to delay output power after power is restored. Max
	 is 60 seconds.

EXTRA ARGUMENTS
     This driver doesn't support any optional settings.

INSTALLATION
     This driver may be not built by default. You can  build  it  by  installing
     libmodbus and running configure --with-modbus=yes.

     You  also	need  to give proper permissions on the local serial device file
     (/dev/ttyS0 for example) to allow the NUT user to access it.

INSTANT COMMANDS
     This driver doesn't support any instant commands.

CONFIGURABLE VARIABLES
     The following variables can be set in the NUT  configuration  as  default.*
     values  to override or monitor UPS behavior using the phoenixcontact_modbus
     driver.

	 Note

	 As of NUT v2.8.4, there is currently no support for run-time setting of
	 these values (e.g. with upsrw(8)). Currently they are	only  considered
	 once, during driver initialization.

     battery.energysave.delay=num
	 Time after entering battery mode before PC shutdown signal is triggered
	 by the UPS (in seconds).

     ups.timer.shutdown=num
	 Time allowed for PC to shutdown (in seconds). Maximum is 300 seconds.

     ups.timer.start=num
	 Duration for which output power remains turned off before rebooting the
	 PC system back on (in seconds).

     ups.delay.start=num
	 Delay	before	switching back to mains after power is restored (in sec-
	 onds). The mains voltage must be within the threshold for this time, to
	 initiate automatic PC restart.

     experimental.ups.mode.selector=num
	 UPS operating mode. For example, 9 corresponds to  PC-Mode  (vendor-de-
	 fined).

     experimental.battery.warning_soh=num
	 Battery warning threshold for State of Health, in percent.

     input.voltage.low.critical=num
	 Threshold  voltage  (in  V)  below which the UPS will switch to battery
	 mode.

     input.voltage.high.critical=num
	 Voltage threshold (in V) above which the UPS will consider mains  power
	 restored (see also below).

AUTHORS
     *	 Spiros Ioannou <sivann@gmail.com>

     *	 Ricardo Rodriguez <rikyrod2001@gmail.com>

     *	 Ulfat Hasangarayev <ulfathasangarayev@gmail.com>

SEE ALSO
   The core driver:
     nutupsdrv(8)

   Internet resources:
     *	 The NUT (Network UPS Tools) home page: https://www.networkupstools.org/

     *	 libmodbus home page: http://libmodbus.org

     *	 More  information  about  PhoenixContact  QUINT-UPS  industrial DC UPS,
	 model 2320461 UPS series can  be  found  here:  https://www.phoenixcon-
	 tact.com/online/portal/us?uri=pxc-oc-itemdetail:pid=2320461

Network UPS Tools 2.8.5.	   08/04/2026		 PHOENIXCONTACT_MODBU(8)