UPSMON(8)			   NUT Manual			       UPSMON(8)

NAME
     upsmon - UPS monitor and shutdown controller

SYNOPSIS
     upsmon -h

     upsmon -c command [-P pid]

     upsmon [-D] [-F | -B] [-K] [-p] [-u user]

DESCRIPTION
     upsmon  is  the  client  process that is responsible for the most important
     part of UPS monitoring -- shutting down the system when the power goes out.
     It can call out to other helper programs for notification	purposes  during
     power events.

     upsmon  can monitor multiple systems using a single process. Every UPS that
     is defined in the upsmon.conf(5) configuration file  is  assigned	a  power
     value and a type (primary or secondary).

OPTIONS
     -c command
	 Send the command command to the existing upsmon process. Valid commands
	 are:

	 fsd
	     shutdown all primary-mode UPSes (use with caution)

	 stop
	     stop monitoring and exit

	 reload
	     reread  upsmon.conf(5)  configuration file. See "reloading nuances"
	     below if this doesn't work.

     -P pid
	 Send the command signal above using specified PID number,  rather  than
	 consulting the PID file. This can help define service units which start
	 main  upsmon  as  a foreground process so it does not have to rely on a
	 PID file.

     -D
	 Raise the debugging level. upsmon will run in	the  foreground  by  de-
	 fault,  and  will  print  information	on  stdout  about the monitoring
	 process. Use this option multiple times for more details.

     -F
	 upsmon will run in the foreground, regardless of debugging settings.

     -B
	 upsmon will run in the background, regardless of debugging settings.

     -K
	 Test for the shutdown flag. If it exists and contains the magic  string
	 from  upsmon, then upsmon will exit with EXIT_SUCCESS. Any other condi-
	 tion will make upsmon exit with EXIT_FAILURE.

	 You can test for a successful exit from  upsmon  -K  in  your	shutdown
	 scripts to know when to call upsdrvctl(8) to shut down the UPS.

     -p
	 Run  privileged  all  the  time.  Normally  upsmon  will split into two
	 processes. The majority of the code runs as an unprivileged  user,  and
	 only a tiny stub runs as root to eventually call SHUTDOWNCMD if needed.
	 This  switch  will disable that mode, and run the old "all root all the
	 time" system.

	 This is not the recommended mode, and you should not  use  this  unless
	 you have a very good reason.

     -u user
	 Set  the  user for the unprivileged monitoring process. This has no ef-
	 fect when using -p.

	 The default user is set at  build  configuration  time  with  configure
	 --with-user=....  Typically  this  is	nobody (if not otherwise config-
	 ured), which is far from ideal, so  most  packaged  distributions  will
	 probably  have  a specific nut user for this task. If your notification
	 scripts need to run as a specific user, set it here.

	 You can also set this in the upsmon.conf(5) file with	the  RUN_AS_USER
	 directive.

COMMON OPTIONS
     -h
	 Show the command-line help message.

     -V
	 Show  NUT version banner. More details may be available if you also ex-
	 port NUT_DEBUG_LEVEL=1 or greater verbosity level.

     -W secs
	 Set the timeout for initial network connections (by  default  they  are
	 indefinitely non-blocking, or until the system interrupts the attempt).
	 Overrides  the  optional  NUT_DEFAULT_CONNECT_TIMEOUT environment vari-
	 able.

UPS DEFINITIONS
     In the upsmon.conf(5), you must specify at least one UPS that will be moni-
     tored. Use the MONITOR directive like this:

	 MONITOR 'system' 'powervalue' 'username' 'password' 'type'

     The  system  refers  to  a  upsd(8)  server,  in  the  form  upsname[@host-
     name[:port]].  The  default  hostname  is	"localhost", and default port is
     3493. Some examples follow:

     *	 "su700@mybox" means a UPS called "su700" on a	system	called	"mybox".
	 This is the normal form.

     *	 "fenton@bigbox:5678"  is a UPS called "fenton" on a system called "big-
	 box" which runs upsd(8) on port "5678".

     The powervalue refers to how many power supplies on this client system  are
     being  driven  this UPS. This is typically set to 1, but see the section on
     power values below.

     The username is a section in your upsd.users(5) file. Whatever password you
     set in that section must match the password set in this file for the corre-
     sponding data server instance.

     The type set in that section of the data  server  configuration  must  also
     match the type here -- primary or secondary (consider it an "upsmon role").
     In  general,  a  "primary" client process is one running on the system with
     the UPS actually plugged into a serial or USB port, and  a  "secondary"  is
     drawing  power  from the UPS but can't talk to it directly. See the section
     on UPS types for more.

NOTIFY EVENTS
     upsmon senses several events as it monitors each UPS. They are called  "no-
     tify  events",  as  they can be used to tell the users and admins about the
     change in status. See the additional NOTIFY-related sections below for  in-
     formation on customizing the delivery of these messages.

     ONLINE
	 The UPS is back on line.

     ONBATT
	 The UPS is on battery.

     LOWBATT
	 The UPS battery is low (as determined by the driver).

     FSD
	 The UPS has been commanded into the "forced shutdown" mode.

     COMMOK
	 Communication with the UPS has been established.

     COMMBAD
	 Communication with the UPS was just lost.

     SHUTDOWN
	 The local system is being shut down.

     REPLBATT
	 The UPS needs to have its battery replaced.

     NOCOMM
	 The UPS can't be contacted for monitoring.

     NOPARENT
	 upsmon parent process died - shutdown impossible.

     CAL
	 UPS calibration in progress.

     NOTCAL
	 UPS calibration finished.

     OFF
	 UPS administratively OFF or asleep.

     NOTOFF
	 UPS no longer administratively OFF or asleep.

     BYPASS
	 UPS on bypass (powered, not protecting).

     NOTBYPASS
	 UPS no longer on bypass.

     ECO
	 UPS  in  ECO  or  similar  mode (as defined and named by vendor); other
	 names include High Efficiency mode and Energy Saver System.

	 For example, Eaton docs define High Efficiency mode as a sort of  hard-
	 ware-monitored  bypass  with switch-over under 10ms into Online mode in
	 case of troubles (so what was known as Line-Interactive  in  the  older
	 days),  which can be chosen instead of always running in a dual-conver-
	 sion mode (safer, but more wasteful and with a toll on  battery  life).
	 Older devices only implemented one or the other.

     NOTECO
	 UPS no longer in ECO mode (see above).

     ALARM
	 UPS has one or more active alarms (look at ups.alarm for details).

     NOTALARM
	 UPS is no longer in an alarm state (no active alarms).

     OVER
	 UPS is overloaded.

     NOTOVER
	 UPS is no longer overloaded.

     TRIM
	 UPS is trimming incoming voltage.

     NOTTRIM
	 UPS is no longer trimming incoming voltage.

     BOOST
	 UPS is boosting incoming voltage.

     NOTBOOST
	 UPS is no longer boosting incoming voltage.

     OTHER
	 UPS has at least one unclassified status token.

     NOTOTHER
	 UPS has no unclassified status tokens anymore.

     SUSPEND_STARTING
	 OS is entering sleep/suspend/hibernate mode.

     SUSPEND_FINISHED
	 OS  just  finished sleep/suspend/hibernate mode, de-activating obsolete
	 UPS readings to avoid an unfortunate shutdown.

NOTIFY COMMAND
     In upsmon.conf(5), you can configure a program called  the  NOTIFYCMD  that
     will handle events that occur.

     The syntax is: NOTIFYCMD "path to program"

     Example:

     *	 NOTIFYCMD "/usr/local/bin/notifyme"

     Remember  to wrap the path in "double quotes" if it contains any spaces. It
     should probably not rely on receiving any command-line arguments.

     The program you run as your NOTIFYCMD can use the environment variables NO-
     TIFYTYPE and UPSNAME to know what has happened and on which  UPS.	It  also
     receives the notification message (see below) as the first (and only) argu-
     ment, so you can deliver a pre-formatted message too.

     Note  that the NOTIFYCMD will only be called for a given event when you set
     the EXEC flag by using the notify flags, as detailed below.

NOTIFY FLAGS
     By default, all notify events (see above) generate a global message  (wall)
     to all users, plus they are logged via the syslog. Except for Windows where
     upsmon  only  writes to the syslog by default. You can change this with the
     NOTIFYFLAG directive in the configuration file:

     The syntax is: NOTIFYFLAG notifytype flags

     Examples:

     *	 NOTIFYFLAG ONLINE SYSLOG

     *	 NOTIFYFLAG ONBATT SYSLOG+WALL

     *	 NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC

     The flags that can be set on a given notify event are:

     SYSLOG
	 Write this message to the syslog.

     WALL
	 Send this message to all users on the system via wall(1).

     EXEC
	 Execute the NOTIFYCMD.

     IGNORE
	 Don't do anything. If you use this, don't use any of the other flags.

     You can mix these flags; for example, SYSLOG+WALL+EXEC does all three for a
     given event.

NOTIFY MESSAGES
     upsmon comes with default messages for each of the NOTIFY events. These can
     be changed with the NOTIFYMSG directive.

     The syntax is: NOTIFYMSG type "message"

     Examples:

     *	 NOTIFYMSG ONLINE "UPS %s is getting line power"

     *	 NOTIFYMSG ONBATT "Someone pulled the plug on %s"

     The first instance of %s is replaced with the identifier of  the  UPS  that
     generated	the  event.  These  messages  are used when sending walls to the
     users directly from upsmon, and are also passed to the NOTIFYCMD.

	 Note

	 Certain notifications, such as NOTIFY_ALARM and NOTIFY_OTHER,	can  ac-
	 cept a second instance of %s that would be replaced with the alarm text
	 or the unrecognized token, respectively.

POWER VALUES
     The  "current  overall  power  value" is the sum of all UPSes that are cur-
     rently able to supply power to the system hosting upsmon. Any UPS	that  is
     either  on  line or just on battery contributes to this number. If a UPS is
     critical (on battery and low battery) or has been put  into  "forced  shut-
     down" mode, it no longer contributes.

     The syntax is: MONITOR upsname powervalue username password type

     A "power value" on a MONITOR line in the config file is the number of power
     supplies that the UPS runs on the current system.

     *	 Normally, you only have one power supply, so it will be set to 1.

	 Example:

	 *   MONITOR myups@myhost 1 username mypassword primary

     *	 On  a large server with redundant power supplies, the power value for a
	 UPS may be greater than 1. You may also have more than one of them  de-
	 fined.

	 Examples  for	a  server  with  four power supply modules and two UPSes
	 (each feeding two power supplies of that server):

	 *   MONITOR ups-alpha@myhost 2 username mypassword primary

	 *   MONITOR ups-beta@myhost 2 username mypassword primary

     *	 You can also set the power value for a UPS to 0 if it does  not  supply
	 any  power  to that system. This is generally used when you want to use
	 the upsmon notification features for a UPS even though it's  not  actu-
	 ally powering the system that hosts this instance of the upsmon client.

	 Don't	set  this  to "primary" unless you really want to power this UPS
	 off when this instance of upsmon needs to shut down for  its  own  rea-
	 sons.

	 Example:

	 *   MONITOR faraway@anotherbox 0 username mypassword secondary

     The  "minimum power value" is the number of power supplies that must be re-
     ceiving power in order to keep this upsmon client's computer running.

     The syntax is: MINSUPPLIES value

     *	 Typical PCs only have 1, so most users will leave this at the default.

	 Example:

	 *   MINSUPPLIES 1

     *	 If you have a server or similar system with redundant power, then  this
	 value	will  usually  be set higher. One that requires three power sup-
	 plies out of 4 to be running at all times would simply set it to 3.

	 Example:

	 *   MINSUPPLIES 3

	 When the current overall healthy  UPS-protected  external  power  value
	 drops	below  the minimum required power value, upsmon starts the shut-
	 down sequence. This design allows you to lose some of your  power  sup-
	 plies in a redundant power environment without bringing down the entire
	 system, while still working properly for smaller systems.

UPS CONNECTION TYPES AND UPSMON ROLES
     upsmon  and  upsd(8) don't always run on the same system. When they do, any
     UPSes that are directly attached to that upsmon host should be monitored in
     "primary" mode, which makes that upsmon instance take charge of that equip-
     ment, and it will wait for the "secondary"  systems  to  disconnect  before
     shutting down the local system. This allows the distant systems (just moni-
     toring  over  the	network)  to shut down cleanly before upsdrvctl shutdown
     runs locally on the primary system and turns them all off.

     When upsmon runs as a secondary, it is relying on	the  distant  system  to
     tell it about the state of the UPS. When that UPS goes critical (on battery
     and  low  battery), it immediately invokes the local shutdown command. This
     needs to happen quickly. Once all secondaries disconnect from  the  distant
     upsd(8)  server,  its  primary-mode  upsmon  will	start  its  own shutdown
     process. Your secondary systems must all quiesce and shut down  before  the
     primary turns off the shared power source, or filesystem damage may result.

     upsmon  deals  with secondaries that get wedged, hang, or otherwise fail to
     gracefully disconnect from upsd(8) in a timely  manner  with  the	HOSTSYNC
     timer.  During  a shutdown situation, the primary upsmon will give up after
     this interval and it will shut down anyway. This  keeps  the  primary  from
     sitting  there  forever  (which  would  endanger  that host) if a secondary
     should break somehow. This defaults to 15 seconds.

     If your primary system is shutting down too quickly, set the FINALDELAY in-
     terval to something greater than the default 15 seconds. Don't set this too
     high, or your UPS battery may run out of power before  the  primary  upsmon
     process shuts down that system. If you do need more time, consider starting
     the shutdown after a short time on battery, for details see the Timed Shut-
     downs section.

     For  a  more technical take, please see the Shutdown Activity Workflow sec-
     tion.

TIMED SHUTDOWNS
     For those rare situations where the shutdown process can't be completed be-
     tween the time that low battery is signalled and the  UPS	actually  powers
     off the load, use the upssched(8) helper program. You can use it along with
     upsmon to schedule a shutdown based on the "on battery" event. upssched can
     then  come  back to upsmon to initiate the shutdown once it has run on bat-
     tery too long.

     This can be complicated and messy, so stick to  the  default  critical  UPS
     handling if you can.

REDUNDANT POWER SUPPLIES
     If  you  have  more than one power supply for redundant power, you may also
     have more than one UPS feeding your computer. upsmon can  handle  this.  Be
     sure  to  set  the UPS power values appropriately and the MINSUPPLIES value
     high enough so that it keeps running until it  really  does  need	to  shut
     down.

     For  example,  the  HP  NetServer	LH4  by default has 3 power supplies in-
     stalled, with one bay empty. It has two power cords, one per  side  of  the
     box.  This means that one power cord powers two power supply bays, and that
     you can only have two UPSes supplying power.

     Connect UPS "alpha" to the cord feeding two power supplies, and UPS  "beta"
     to the cord that feeds the third and the empty slot. Define alpha as a pow-
     ervalue of 2, and beta as a powervalue of 1. Set the MINSUPPLIES to 2.

     When  alpha  goes on battery, your current overall power value will stay at
     3, as it's still supplying power. However, once it goes critical  (on  bat-
     tery  and	low  battery),	it will stop contributing to the current overall
     power value. That means the value will be 1 (beta	alone),  which	is  less
     than  2. That is insufficient to run the system, and upsmon will invoke the
     shutdown sequence.

     However, if beta goes critical, subtracting its contribution will take  the
     current  overall value from 3 to 2. This is just high enough to satisfy the
     minimum, so the system will continue running as  before.  If  beta  returns
     later,  it  will  be re-added and the current value will go back to 3. This
     allows you to swap out UPSes, change a power configuration, or whatever, as
     long as you maintain the minimum power value at all times.

MIXED OPERATIONS
     Besides being able to monitor multiple UPSes, upsmon can also monitor  them
     as  different roles. If you have a system with multiple power supplies ser-
     viced by separate UPS batteries, it's possible to be a primary on	one  UPS
     and a secondary on the other. This usually happens when you run out of ser-
     ial  or  USB  ports  and  need  to do the monitoring through another system
     nearby.

     This is also complicated, especially when it comes time to power down a UPS
     that has gone critical but doesn't supply the local system. You can do this
     with some scripting magic in your notify command script,  but  it's  beyond
     the scope of this manual.

FORCED SHUTDOWNS
     When  upsmon  is  forced  to bring down the local system, it sets the "FSD"
     (forced shutdown) flag on any UPSes that it is  running  in  primary  mode.
     This  is  used to synchronize secondary systems in the event that a primary
     which is otherwise OK needs to be brought down due to some  pressing  event
     on the UPS manager system.

     You can manually invoke this mode on the system with primary-mode upsmon by
     starting  another	copy  of  the program with -c fsd command line argument.
     This is useful when you want to initiate a  shutdown  before  the	critical
     stage through some external means, such as upssched(8).

     For  a  more technical take, please see the Shutdown Activity Workflow sec-
     tion.

	 Warning

	 Please note that by design, since we require power-cycling the load and
	 don't want some systems to be powered off while others  remain  running
	 if  the  "wall  power"  returns at the wrong moment as usual, the "FSD"
	 flag can not be removed from the  data  server  unless  its  daemon  is
	 restarted.  If we do take the first step in critical mode, then we nor-
	 mally intend to go all the way -- shut down all the servers gracefully,
	 and power down the UPS.

     Keep in mind that some UPS devices and  corresponding  drivers  would  also
     latch  or otherwise resurface the "FSD" state again even if "wall power" is
     available, but the remaining battery charge is below a threshold configured
     as "safe" in the device (usually if you manually power on the UPS	after  a
     long  power  outage). This is by design of respective UPS vendors, since in
     such situation they can not guarantee that if a new power	outage	happens,
     their UPS would safely shut down your systems again. So it is deemed better
     and safer to stay dark until batteries become sufficiently charged.

     When  it  is time to shut down, upsmon creates POWERDOWNFLAG to communicate
     to the operating system that the UPS should be commanded off  late  in  the
     shutdown  sequence.  This file is removed if present when upsmon starts, so
     that the next normal shutdown does not cause the UPS to be turned off. (The
     file can't in general be removed during  shutdown	because  the  filesystem
     might be read only. If the file is in a RAM-backed filesystem, the it won't
     be present and the check to remove it won't fire.)

SIMULATING POWER FAILURES
     To  test  a synchronized shutdown without pulling the plug on your UPS(es),
     you need only set the forced shutdown (FSD) flag on them. You can	do  this
     by calling upsmon again to set the flag, i.e.:

	 :; upsmon -c fsd

     After  that, the primary and the secondary will do their usual shutdown se-
     quence as if the battery had gone critical, while you can time how long  it
     takes  for  them.	This  is much easier on your UPS equipment, and it beats
     crawling under a desk to find the plug.

     Note you can also use a dummy SHUTDOWNCMD setting to just report  that  the
     systems  would  shut  down at this point, without actually disrupting their
     work.

     For inspiration, you can see the setup done by the  NUT  Integration  Tests
     suite under the tests/NIT directory in NUT sources, including references to
     the  shutdown and notification scripts which only log the activity (you may
     have to configure at least a trivial NUT build and run make check-NIT-sand-
     box to generate some of the configuration files -- or  inspect  the  nit.sh
     script  which pieces them together). Notably, see scripts/misc/notifyme-de-
     bug as not only a logger, but optionally a wrapper for  upssched  (in  test
     runs),  and  clients/upssched-cmd	as  a  sample implementation of an upss-
     ched(8) CMDSCRIPT which also focuses on logging.

	 Warning

	 After such "dummy" experiments you may have to  restart  the  NUT  data
	 server  upsd  to  clear  its "FSD" flag for the devices and clients in-
	 volved, and make sure no files  named	by  POWERDOWNFLAG  option  (e.g.
	 /etc/killpower) remain on the upsmon primary systems under test.

SHUTDOWN ACTIVITY WORKFLOW
     Looking  into  clients/upsmon.c  sources as the ultimate authority, you can
     find that the chain of events during a forced shutdown is.  This  can  help
     make  sense of the timing variables involved, and notifications sent (which
     you may want to handle, perhaps with upssched(8)):

     *	 The path to shutdown activity of a host starts when its locally running
	 upsmon client (in any role) decides the power	situation  is  critical,
	 e.g.  by  having  too	few  "healthy"	power supplies in a real outage,
	 and/or  by  seeing  FSD  among  ups.status  tokens  --  possibly  still
	 "latched"  in	the  upsd  data  server while you start a new upsmon in-
	 stance, or when you call upsmon -c fsd on that system to  simulate  the
	 outage;

     *	 Such upsmon instance ends up in forceshutdown() method;

     *	 There it loops over all UPSes it MONITOR`s as a `primary, and calls the
	 setfsd()  method for each (causing a local FSD notification, if one was
	 not sent earlier);

     *	 If there were no such UPSes -- we are a secondary, and go into  doshut-
	 down() method immediately

     *	 Otherwise  we are a primary, and only go into doshutdown() method after
	 first completing the sync_secondaries() method, which:

     *	 runs an infinite loop	until  either  there  are  no  other  persistent
	 clients  logged on to the data server (upsd) for each UPS we are a pri-
	 mary for, or until HOSTSYNC timeout elapses;

     *	 it should issue a SHUTDOWN_HOSTSYNC notification if it is going to wait
	 at all (if there were other clients seen on first loop cycle).

     *	 Finally, in the doshutdown() method, it:

     *	 issues a SHUTDOWN notification;

     *	 waits for FINALDELAY;

     *	 starts the timer for SHUTDOWNEXIT (which may be used  to  force  upsmon
	 process  to  linger  after calling SHUTDOWNCMD -- e.g. can be used by a
	 secondary to block the primary from cutting power too	early  for  some
	 use cases, like safely parking some external machinery);

     *	 calls	the  SHUTDOWNCMD  (either  directly  in mono-process mode, or by
	 telling the root-privileged part to do so in the common case);

     *	 optionally linger, if SHUTDOWNEXIT is so configured;

     *	 ultimately exit the daemon (also causes  the  root-privileged	part  to
	 exit, by breaking the communications pipe between them).

     Note that if your upsmon does split into privileged and unprivileged parts,
     all  notifications  run  in the unprivileged context (your handling scripts
     may have to sudo explicitly if/when/where you want to do something  to  the
     system). Only SHUTDOWNCMD is called in privileged context.

DEAD UPSES
     In  the  event that upsmon can't reach upsd(8), it declares that UPS "dead"
     after some interval controlled by DEADTIME in the upsmon.conf(5).	If  this
     happens  while  that  UPS was last known to be on battery, it is assumed to
     have gone critical and no longer contributes to the overall power value.

     upsmon will alert you to a UPS that can't be contacted for monitoring  with
     a	"NOCOMM" notifier by default every 300 seconds. This can be changed with
     the NOCOMMWARNTIME setting.

     Also upsmon normally reports polling failures for each device that  are  in
     place  for each POLLFREQ loop (e.g. "Data stale" or "Driver not connected")
     to system log as configured. If your devices are expected to be AWOL for an
     extended timeframe, you can use  POLLFAIL_LOG_THROTTLE_MAX  to  reduce  the
     stress  on  syslog traffic and storage, by posting these messages only once
     in every several loop cycles, and when the error condition has  changed  or
     cleared.  A  negative value means standard behavior (log on every loop, ef-
     fectively same as when max=1), and a zero value means to never  repeat  the
     message (log only on start and end/change of the failure state).

     Note  that  this throttle only applies to one latest-active error state per
     monitored device.

UPS ALARMS
     UPS manufacturers and UPS drivers may implement device-specific  alarms  to
     notify  the user about potentially severe conditions of the UPS. The status
     "ALARM" will be set on such UPS as a common denominator for  the  different
     implementations  throughout  the  various UPS drivers and generally anytime
     that a "ups.alarm" variable is seen reported by the specific UPS driver.

     Alarms can be acted upon by the user using the "ALARM" and "NOTALARM" noti-
     fiers, which are reported by the upsmon when the "ALARM" status  occurs  or
     disappears.

     As  alarms  raised  by  the  UPS  are  usually severe in nature, the upsmon
     watches a UPS in such a state more closely, bumping  up  the  polling  fre-
     quency as needed.

     When  connection loss occurs in such an alarm state, the upsmon will by de-
     fault consider the volatile UPS as critical/dead and this may lead to false
     shutdowns if the actual alarm was in fact mundane in nature (e.g. caused by
     a HE/ECO mode). This can be changed by utilizing the ALARMCRITICAL  setting
     within upsmon.conf.

RELOADING NUANCES
     upsmon  usually  gives up root powers for the process that does most of the
     work, including handling signals like SIGHUP to  reload  the  configuration
     file.  This means your upsmon.conf(5) file must be readable by the non-root
     account that upsmon switches to.

     If you want reloads to work, upsmon must run as some user that has  permis-
     sions  to	read the configuration file. We recommend making a new user just
     for this purpose, as making the file  readable  by  "nobody"  (the  default
     user)  would  be a bad idea; packages typically ship with a nut or ups user
     to run NUT daemon services.

     See the RUN_AS_USER section in upsmon.conf(5) for more on this topic.

     Additionally, you can't change the SHUTDOWNCMD or POWERDOWNFLAG definitions
     with a reload due to the split-process model. If you change  those  values,
     you must stop upsmon and start it back up. upsmon will warn you in the sys-
     log if you make changes to either of those values during a reload.

ENVIRONMENT VARIABLES
     NUT_DEBUG_LEVEL  sets  default debug verbosity if no -D arguments were pro-
     vided on command line, but does not request that the daemon runs  in  fore-
     ground mode.

     NUT_CONFPATH  is  the  path name of the directory that contains upsmon.conf
     and other configuration files. If this variable is not set, upsmon  uses  a
     built-in default, which is often /usr/local/etc.

     NUT_QUIET_INIT_UPSNOTIFY=true  can be used to prevent daemons which can no-
     tify service management frameworks (such as systemd)  about  passing  their
     lifecycle	milestones  from  emitting  such  notifications (including those
     about lack of system support for such modern features, once per run).

     NUT_QUIET_INIT_BANNER=true can be used to suppress NUT tool name  and  ver-
     sion  banner.  NOT  recommended for services due to adverse troubleshooting
     impact, but may be helpful in shell profiles or scripts which  process  NUT
     tool outputs.

FILES
     upsmon.conf(5)

SEE ALSO
   Server:
     upsd(8)

   Clients:
     upsc(8), upscmd(8), upsrw(8), upsmon(8)

   CGI programs:
     upsset.cgi(8), upsstats.cgi(8), upsimage.cgi(8)

   Internet resources:
     The NUT (Network UPS Tools) home page: https://www.networkupstools.org/

Network UPS Tools 2.8.5.	   08/04/2026			       UPSMON(8)