UPSMON.CONF(5)			   NUT Manual			  UPSMON.CONF(5)

NAME
     upsmon.conf - Configuration for Network UPS Tools upsmon client

DESCRIPTION
     This  file's primary job is to define the systems that upsmon(8) will moni-
     tor, and to tell it how to shut down the system  when  necessary.	It  will
     contain  passwords,  so  keep  it	secure. Ideally, only the upsmon process
     should be able to read it.

     A minimal configuration should include at least  one  MONITOR  instruction,
     MINSUPPLIES (may be 0 if this system is only monitoring other NUT servers),
     and  a POWERDOWNFLAG if this machine is a "primary" system connected to the
     UPS and drives its late-shutdown power-off command in case of an emergency.

     Additionally, other optional configuration values can be set in this file.

IMPORTANT NOTES
     *	 Contents of this file should be pure  ASCII  (character  codes  not  in
	 range would be ignored with a warning message).

     *	 Balance  the  run-time user permissions to access the file (and perhaps
	 the directory it is in) for only upsmon to be able to	read  it;  write
	 access  is not needed. It is common to use chown root:nut and chmod 640
	 to set up acceptable file permissions.

	 *   Packages (and build recipes) typically prepare one set of user  and
	     group  accounts  for  NUT. Custom builds with minimal configuration
	     might even use nobody:nogroup or similar, which is inherently inse-
	     cure.

	 *   On systems with extra security concerns, NUT drivers, data  server,
	     and any other monitoring, logging, etc. clients, should run as sep-
	     arate user accounts. This would need some daemons to use customized
	     user,  group,  RUN_AS_USER and/or RUN_AS_GROUP settings to override
	     the single built-in value.

	 *   Keep in mind the security of also any backup copies of  this  file,
	     e.g. the archive files it might end up in.

CONFIGURATION DIRECTIVES
     DEADTIME seconds
	 upsmon  allows a UPS to go missing for this many seconds before declar-
	 ing it "dead". The default is 15 seconds.

	 upsmon requires a UPS to provide status information every  few  seconds
	 (see  POLLFREQ and POLLFREQALERT) to keep things updated. If the status
	 fetch fails, the UPS is marked stale. If it stays stale for  more  than
	 DEADTIME seconds, the UPS is marked dead.

	 A  dead  UPS  that  was  last known to be on battery is assumed to have
	 changed to a low battery condition. This may force a shutdown if it  is
	 providing a critical amount of power to your system. This seems disrup-
	 tive, but the alternative is barreling ahead into oblivion and crashing
	 when you run out of power.

	 Note: DEADTIME should be a multiple of POLLFREQ and POLLFREQALERT. Oth-
	 erwise,  you'll  have	"dead" UPSes simply because upsmon isn't polling
	 them quickly enough. Rule of thumb: take the larger of the two POLLFREQ
	 values, and multiply by 3.

     FINALDELAY seconds
	 When handling a forced shutdown (FSD) due to a critical  UPS  state  or
	 explicit  user  signal,  upsmon  waits  this long after sending the NO-
	 TIFY_SHUTDOWN message to warn the users. After the  timer  elapses,  it
	 then runs your SHUTDOWNCMD. By default this is set to 5 seconds.

	 If you need to let your users (or the NOTIFYCMD script) do something in
	 between  those  events,  increase  this number. Remember, at this point
	 your UPS battery is almost depleted, so don't make this too big.

	 Alternatively, you can set this very low so you don't wait around  when
	 it's time to shut down. Some UPSes don't give much warning for low bat-
	 tery and will require a value of 0 here for a safe shutdown.

	     Note
	     If FINALDELAY on the secondary is greater than HOSTSYNC on the pri-
	     mary, the primary will give up waiting for that secondary upsmon to
	     disconnect.

     HOSTSYNC seconds
	 upsmon will wait up to this many seconds in primary mode for the secon-
	 daries  to  disconnect during a shutdown situation. By default, this is
	 15 seconds.

	 When a UPS goes critical (on battery + low battery,  or  "FSD":  forced
	 shutdown),  the  secondary  systems are supposed to disconnect and shut
	 down right away. The HOSTSYNC timer keeps the primary upsmon from  sit-
	 ting there forever if one of the secondaries gets stuck.

	 This value is also used to keep secondary systems from getting stuck if
	 the primary fails to respond in time. After a UPS becomes critical, the
	 secondary  will  wait up to HOSTSYNC seconds for the primary to set the
	 FSD flag. If that timer expires, the secondary upsmon will assume  that
	 the primary (or communications path to it) is broken and will shut down
	 anyway.

	 This keeps the secondaries from shutting down during a short-lived sta-
	 tus change to "OB LB" and back that the secondaries see but the primary
	 misses.

     MINSUPPLIES num
	 Set  the  number of power supplies that must be receiving power to keep
	 this system running. Normal computers have just one  power  supply,  so
	 the default value of 1 is acceptable.

	 Large/expensive server type systems usually have more, and can run with
	 a  few missing. The HP NetServer LH4 can run with 2 out of 4, for exam-
	 ple, so you'd set it to 2. The idea is to keep the box running as  long
	 as possible, right?

	 Obviously  you have to put the redundant supplies on different UPS cir-
	 cuits for this to make sense! See big-servers.txt in the docs subdirec-
	 tory for more information and ideas on how to use this feature.

	 Also see the section on "power values" in upsmon(8).

     MONITOR system powervalue username password type
	 Each UPS that you need to be monitor should have a  MONITOR  line.  Not
	 all  of  these  need supply power to the system that is running upsmon.
	 You may monitor other systems if you want to be able to send  notifica-
	 tions about status changes on them.

	 You must have at least one MONITOR directive in upsmon.conf.

	 *   system is a UPS identifier. It is in this form:

	     <upsname>[@<hostname>[:<port>]]

	     The default hostname is "localhost". Some examples:

	     *	 "su700@mybox"	means  a  UPS  called "su700" on a system called
		 "mybox". This is the normal form.

	     *	 "fenton@bigbox:5678" is a  UPS  called  "fenton"  on  a  system
		 called "bigbox" which runs upsd(8) on port "5678".

	 *   powervalue  is an integer representing the number of power supplies
	     that the UPS feeds on this system. Most normal computers  have  one
	     power  supply,  and  the UPS feeds it, so this value will be 1. You
	     need a very large or special system to have anything higher here.

	     You can set the powervalue to 0 if you want to monitor a  UPS  that
	     doesn't  actually	supply power to this system. This is useful when
	     you want to have upsmon do notifications about status changes on  a
	     UPS without shutting down when it goes critical.

	 *   The  username  and password on this line must match an entry in the
	     upsd server system's upsd.users(5) file.

	     If your username is "observer" and your  password	is  "abcd",  the
	     MONITOR  line  might  look  like this (likely on a remote secondary
	     system):

		 MONITOR myups@bigserver 1 observer abcd secondary

	     Meanwhile, the upsd.users on bigserver would look like this:

		 [observer]
			 password = abcd
			 upsmon secondary

		 [upswired]
			 password = blah
			 upsmon primary

	     And the copy of upsmon on that bigserver would run with the primary
	     configuration:

		 MONITOR myups@bigserver 1 upswired blah primary

	 *   The type refers to the relationship with upsd(8). It can be  either
	     "primary" or "secondary". See upsmon(8) for more information on the
	     meaning  of  these  modes.  The mode you pick here also goes in the
	     upsd.users file, as seen in the example above.

     NOCOMMWARNTIME seconds
	 upsmon will trigger a NOTIFY_NOCOMM after this many seconds if it can't
	 reach any of the UPS entries in this configuration file. It keeps warn-
	 ing you until the situation is fixed. By default this is 300 seconds.

     POLLFAIL_LOG_THROTTLE_MAX count
	 upsmon normally reports polling failures for each device  that  are  in
	 place	for  each  POLLFREQ  loop (e.g. "Data stale" or "Driver not con-
	 nected") to system log as configured. If your devices are  expected  to
	 be  AWOL for an extended timeframe, you can use this throttle to reduce
	 the stress on syslog traffic and storage,  by	posting  these	messages
	 only  once  in  every several loop cycles, and when the error condition
	 has changed or cleared.

	 A negative value means standard behavior (log	on  every  loop,  effec-
	 tively  same as when max=1), and a zero value means to never repeat the
	 message (log only on start and end/change of the failure state).

	 Note that this throttle only applies to one latest-active  error  state
	 per monitored device.

     NOTIFYCMD command
	 upsmon calls this to send messages when things happen.

	 This  command	is called with the full text of the message as one argu-
	 ment. The environment string NOTIFYTYPE will contain the type string of
	 whatever caused this event to happen.

	 If you need to use upssched(8), then you must make it your NOTIFYCMD by
	 listing it here.

	 Note that this is only called for NOTIFY events that have EXEC set with
	 NOTIFYFLAG. See NOTIFYFLAG below for more details.

	 Making this some sort of shell script might not be a bad idea. For more
	 information and ideas, see docs/scheduling.txt

	 Remember, this command also needs to be one element in  the  configura-
	 tion file, so if your command has spaces, then wrap it in quotes.

	 NOTIFYCMD "/path/to/script --foo --bar"

	 This  script  is run in the background--that is, upsmon forks before it
	 calls out to start it. This means that your NOTIFYCMD may have multiple
	 instances running simultaneously if a lot of stuff happens all at once.
	 Keep this in mind when designing complicated notifiers.

     NOTIFYMSG type message
	 upsmon comes with a set of stock messages for various events.	You  can
	 change them if you like.

	     NOTIFYMSG ONLINE "UPS %s is getting line power"

	     NOTIFYMSG ONBATT "Someone pulled the plug on %s"

	 Note that %s is replaced with the identifier of the UPS in question.

	 The  message  must  be  one element in the configuration file, so if it
	 contains spaces, you must wrap it in quotes.

	     NOTIFYMSG NOCOMM "Someone stole UPS %s"

	 Possible values for type:

	 ONLINE
	     UPS is back online

	 ONBATT
	     UPS is on battery

	 LOWBATT
	     UPS is on battery and has a low battery (is critical)

	 FSD
	     UPS is being shutdown by the primary (FSD = "Forced Shutdown")

	 COMMOK
	     Communications established with the UPS

	 COMMBAD
	     Communications lost to the UPS

	 SHUTDOWN
	     The system is being shutdown

	 SHUTDOWN_HOSTSYNC
	     This primary system began the shutdown, and is waiting  for  secon-
	     daries

	 REPLBATT
	     The UPS battery is bad and needs to be replaced

	 NOCOMM
	     A UPS is unavailable (can't be contacted for monitoring)

	 NOPARENT
	     upsmon parent process died - shutdown impossible

	 CAL
	     UPS calibration in progress

	 NOTCAL
	     UPS calibration finished

	 OFF
	     UPS administratively OFF or asleep

	 NOTOFF
	     UPS no longer administratively OFF or asleep

	 BYPASS
	     UPS on bypass (powered, not protecting)

	 NOTBYPASS
	     UPS no longer on bypass

	 ECO
	     UPS  in  ECO  or similar mode (as defined and named by vendor); for
	     more details see upsmon(8).

	 NOTECO
	     UPS no longer in ECO mode (see above)

	 ALARM
	     UPS has one or more active alarms (check ups.alarm); for this noti-
	     fication, the message can contain a second %s placeholder	to  sub-
	     stitute the current value of ups.alarm.

	 NOTALARM
	     UPS is no longer in an alarm state (no active alarms)

	 OVER
	     UPS is overloaded

	 NOTOVER
	     UPS is no longer overloaded

	 TRIM
	     UPS is trimming incoming voltage

	 NOTTRIM
	     UPS is no longer trimming incoming voltage

	 BOOST
	     UPS is boosting incoming voltage

	 NOTBOOST
	     UPS is no longer boosting incoming voltage

	 OTHER
	     UPS  has at least one unclassified ups.status token; for this noti-
	     fication, the message can contain a second %s placeholder	to  sub-
	     stitute the current collection of such tokens.

	 NOTOTHER
	     UPS has no unclassified status tokens anymore

	 SUSPEND_STARTING
	     OS is entering sleep/suspend/hibernate mode

	 SUSPEND_FINISHED
	     OS  just finished sleep/suspend/hibernate mode, de-activating obso-
	     lete UPS readings to avoid an unfortunate shutdown

     NOTIFYFLAG type flag[+flag]...
	 By default, upsmon sends walls global messages to all logged in  users)
	 via  /bin/wall  and writes to the syslog when things happen. Except for
	 Windows where upsmon only writes to the Event Log by default.	You  can
	 change this.

	 Examples:

	     NOTIFYFLAG ONLINE SYSLOG
	     NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC

	 Possible values for the flags:

	 SYSLOG
	     Write the message to the syslog

	 WALL
	     Write the message to all users with /bin/wall

	 EXEC
	     Execute NOTIFYCMD (see above) with the message

	 IGNORE
	     Don't do anything

	     If you use IGNORE, don't use any other flags on the same line.

     POLLFREQ seconds
	 Normally  upsmon  polls  the upsd(8) server every 5 seconds. If this is
	 flooding your network with activity, you can make it  higher.	You  can
	 also make it lower to get faster updates in some cases.

	 There	are  some  catches. First, if you set the POLLFREQ too high, you
	 may miss short-lived power events entirely. You  also	risk  triggering
	 the DEADTIME (see above) if you use a very large number.

	 Second,  there is a point of diminishing returns if you set it too low.
	 While upsd normally has all of the data available to it instantly, most
	 drivers only refresh the UPS status once every 2 seconds.  Polling  any
	 more than that usually doesn't get you the information any faster.

	     Note
	     This  setting is different from a pollfreq supported by some of the
	     NUT driver programs, such as usbhid-ups(8)  (about  how  often  the
	     driver polls a particular device).

     POLLFREQALERT seconds
	 This  is the interval that upsmon waits between polls if any of its UP-
	 Ses are on battery. You can use this along with POLLFREQ above to  slow
	 down  polls  during normal behavior, but get quicker updates when some-
	 thing bad happens.

	 This should always be equal to or lower than the POLLFREQ value. By de-
	 fault it is also set 5 seconds.

	 The warnings from the POLLFREQ entry about too-high and too-low  values
	 also apply here.

     POWERDOWNFLAG filename
	 upsmon  creates  this	file  when  running in primary mode when the UPS
	 needs to be powered off. You should check for this file  in  your  late
	 shutdown  scripts  and  call upsdrvctl shutdown if it exists; note that
	 upsmon -K may be called for this effect, if NUT configuration files re-
	 main readable at that point (file systems mostly unmounted  or  changed
	 to read-only).

	 Historically  it  was often /etc/killpower but nowadays you may want it
	 in a temporary filesystem (e.g. under (/var)/run or  even  a  dedicated
	 (/var)/run/nut location).

	 Note  that  double  backslashes  must	be  used for Windows paths, e.g.
	 C:\\Temp\\killpower (modern Windows may  also	accept	forward  slashes
	 like C:/Temp/killpower but YMMV).

	 This is done to forcibly reset the secondary systems, so they don't get
	 stuck	at the "halted" stage even if the power returns during the shut-
	 down process. This usually does not work well on contact-closure  UPSes
	 that use the genericups driver.

	     Warning
	     The upsmon binary program does not have a built-in default, so this
	     setting  MUST  be	specified in the configuration, in order for the
	     late shutdown integration to work on  the	particular  primary-mode
	     system!
	 See  the config-notes.txt file in the docs subdirectory for more infor-
	 mation. Refer to the section:

	 "Configuring automatic shutdowns for low battery events", or  refer  to
	 the online version.

     OFFDURATION seconds
	 NUT  supports	an  "administrative  OFF" for power devices which can be
	 managed to turn off their application workload, while the UPS	or  ePDU
	 remains accessible for monitoring and management. This toggle allows to
	 delay	propagation  of such state into a known loss of a feed (possibly
	 triggering FSD on upsmon clients which MONITOR the device  and  are  in
	 fact still alive -- e.g. with multiple power sources or because they as
	 the  load  are  not really turned off), because when some devices begin
	 battery calibration, they report "OFF" for a few seconds and only  then
	 they  might  report  "CAL" after switching all the power relays -- thus
	 causing false-positives for upsmon FSD trigger.

	 A negative value means to disable decreasing  the  counter  of  working
	 power	supplies  in such cases, and a zero makes the effect of detected
	 "OFF" state immediate. Built-in default value is 30 (seconds),  to  put
	 an  "OFF"  state  into effect (decrease known-fed supplies count) if it
	 persists for this many seconds.

	     Note
	     So far we support the device reporting an "OFF" state which usually
	     means completely un-powering the  load;  a  bug-tracker  issue  was
	     logged  to  design similar support for just some manageable outlets
	     or outlet groups.

     OVERDURATION seconds
	 This setting handles how a UPS that is overloaded should be treated  in
	 situations  when  it is not fully communicating. Because such a UPS may
	 be in a potentially severe state, some users may want their systems  to
	 be  shutdown either immediately or after a set timeout has elapsed. The
	 OVERDURATION setting defines this timeout (in seconds), after which  an
	 overloaded UPS that is not communicating will be considered critical.

	 A negative value means an overloaded UPS will never be considered crit-
	 ical  (at  least  not	because of the overload itself). A value of zero
	 means the UPS will instantly be considered critical when overloaded and
	 not communicating. Built-in default value is -1 (seconds).

	     Note
	     This setting only affects the behavior when a  UPS  is  both  over-
	     loaded  and  not  communicating. When the UPS is communicating nor-
	     mally, an overload condition  may	raise  notifications  but  won't
	     trigger a system shutdown on its own.

     OBLBDURATION seconds
	 NUT  normally	raises alarms for immediate shutdown (FSD) for consumers
	 of an UPS known to be on battery ("OB") and achieving the  low  battery
	 status  ("LB"), if that is their last remaining power source to satisfy
	 their MINSUPPLIES setting. In some special cases, users may want to de-
	 lay raising the alarm (using the OBLBDURATION option) at their  discre-
	 tion and risk of an ungraceful shutdown.

	 A positive value puts "OB LB" state into effect only if it persists for
	 this  many  seconds.  A  non-positive value makes the FSD effect of de-
	 tected "OB LB" state immediate. Built-in default value is 0 (seconds).

	     Note
	     If both OBLBDURATION and HOSTSYNC options are set on the same (sec-
	     ondary) upsmon client system, and HOSTSYNC is shorter, it would  be
	     effectively  ignored: upsmon would wait for up to OBLBDURATION sec-
	     onds for the "OB LB" state to clear, and then the secondary  client
	     logic would fall through to immediate shutdown. If the primary sys-
	     tem  issues an FSD on this UPS, that would take an even higher-pri-
	     ority effect as soon as seen.

     RBWARNTIME seconds
	 When a UPS says that it needs to have its battery replaced, upsmon will
	 generate a NOTIFY_REPLBATT event. By default, this happens every  43200
	 seconds (12 hours).

	 If you need another value, set it here.

     ALARMCRITICAL 0 | 1
	 NUT normally considers UPS with active alarms as volatile, meaning they
	 are  observed	more closely and may be considered critical/dead earlier
	 than in other regular UPS statuses. This is especially true for no-com-
	 munication situations, where UPS in an ALARM status will be  considered
	 lost and system shutdowns may be triggered as a product.

	 As  there  is	no  common  standard for what constitutes an alarm, such
	 alarm states may in fact be mundane in nature and  the  behavior  above
	 unwanted due to possibly resulting in unwarranted system shutdowns.

	 When  this  setting is disabled, upsmon will consider a UPS in an alarm
	 state as not volatile and make it treat the ALARM status as any other.

     RUN_AS_USER username
	 upsmon normally splits into two processes, keeping a small  part  which
	 remains  owned by root to initiate the system shutdown by calling SHUT-
	 DOWNCMD when/if the time comes, and runs the bulk of the monitoring du-
	 ties under another user ID after dropping root privileges. On most cus-
	 tom-built systems this means it runs as "nobody", since that's the  de-
	 fault	from  compile-time; packages often deliver a "nut" or "ups" user
	 to run NUT service daemons.

	 The catch is that the	system-default	"nobody"  can't  read  your  up-
	 smon.conf  file, since by default it is installed so that only root can
	 open it (because this file can contain sensitive data like  remote  NUT
	 data  server  credentials).  This means you won't be able to reload the
	 configuration file, since it will be unavailable  to  the  unprivileged
	 part of the upsmon daemon.

	 The  solution is to create a new user just for upsmon, then make it run
	 as that user. It may be the same account as that used for the NUT  dri-
	 vers  or  data  server, but does not have to be. On systems with higher
	 concerns about security and privilege separation we  suggest  "nutmon",
	 but  you can use anything that isn't already taken on your system. Just
	 create a regular user with no	special  privileges  and  an  impossible
	 password.

	 Then, tell upsmon to run as that user, and make upsmon.conf readable by
	 it. Your reloads will work, and your config file will stay secure.

	 This  file  should  not  be writable by the upsmon user, as it would be
	 possible to exploit a hole, change the SHUTDOWNCMD to	something  mali-
	 cious,  then  wait  for  upsmon to be restarted. So typically you would
	 also create a group for NUT daemons (which the user would be  a  member
	 of)  and  allow that group read-only access to root-owned configuration
	 files.

	 That said, other variants may be possible -- e.g. run all of upsmon  as
	 a single process initially started and owned by nut and call a shutdown
	 script  prefixed by sudo, pfexec or other RBAC tools. This however adds
	 more "moving parts" and fragility (e.g. the sudoers settings  may  live
	 in LDAP, and that server could be unavailable at shutdown when the rack
	 is  half  powered  off,  at just the time you need it here), and is not
	 available on all platforms -- so such setups are  something  users  ex-
	 plore	on their own so far (we would welcome posts on NUT Wiki or links
	 to blogs though).

     SHUTDOWNCMD command
	 upsmon runs this command when the system needs to be brought  down.  If
	 it  is  a  secondary,	it will do that immediately whenever the current
	 overall power value drops below the MINSUPPLIES value above.

	 When upsmon is a primary, it will allow any secondaries to log out  be-
	 fore starting the local shutdown procedure.

	 Note  that  the  command needs to be one element in the config file. If
	 your shutdown command includes spaces, then put it in quotes to keep it
	 together, i.e.:

	     SHUTDOWNCMD "/sbin/shutdown -h +0"

     SHUTDOWNEXIT boolean|number
	 After initiating shutdown, should this upsmon daemon  itself  exit?  By
	 doing	so  NUT  secondary  systems can tell the NUT primary that it can
	 proceed with its own shutdown and eventually tell the UPS to cut  power
	 for the load. ("Yes" by default)

	 Some  "secondary" systems with workloads that take considerable time to
	 stop (e.g. virtual machines or large databases) can  benefit  from  re-
	 porting  (by virtue of logging off the data server) that they are ready
	 for the "primary" system to begin its own shutdown  and  eventually  to
	 tell  the  UPS  to  cut the power -- not as soon as they have triggered
	 their own shutdown, but at a later point (e.g. when the upsmon  service
	 is stopped AFTER the heavier workloads).

	 Note  that  the actual ability to complete such shutdown depends on the
	 remaining battery run-time at the moment when UPS power  state  becomes
	 considered  critical and the shutdowns begin. You may also have to tune
	 HOSTSYNC on the NUT primary to be long enough for those secondaries  to
	 stop  their  services. In practice, it may be worthwhile to investigate
	 ways to trigger shutdowns earlier on these systems, e.g. by setting  up
	 upssched  integration,  or dummy-ups driver with overrides for stricter
	 battery.charge or battery.runtime triggers than used  by  the	rest  of
	 your servers.

	 This	 option   supports   Boolean-style   strings   (yes/on/true   or
	 no/off/false) or numbers to define a delay (in seconds) between calling
	 SHUTDOWNCMD and exiting the daemon.  Zero  means  immediate  exit  (de-
	 fault), negative values mean never exiting on its own accord.

     CERTPATH certificate database
	 When  compiled with SSL support, you can enter the certificate database
	 path here.

	 With NSS:
	     Certificates are stored in a dedicated database (data  split  in  3
	     files). Specify the path of the database directory.

	 With OpenSSL:
	     Directory	containing CA certificates in PEM format, used to verify
	     the server certificate presented by the upsd server. The files each
	     contain one CA certificate. The files are looked up by the CA  sub-
	     ject name hash value, which must hence be available.

	     Alternatively,  with  OpenSSL the CERTPATH can specify a particular
	     PEM file with a collection of multiple CA certificates, e.g.

		 CERTPATH /etc/ssl/certs/ca-certificates.crt

     CERTFILE certificate file
	 When compiled with SSL support with OpenSSL backend (since NUT v2.8.6),
	 you can enter the client certificate file here.  No-op  in  NSS  builds
	 which use CERTPATH for all purposes.

	 The certificates must be in PEM format and must be sorted starting with
	 the  subject's certificate (server certificate), followed by intermedi-
	 ate CA certificates (if applicable) and the highest level (root) CA. It
	 should end with the server's private key corresponding to the	certifi-
	 cate.	See docs/security.txt in NUT sources, or the Security chapter of
	 the NUT User manual, for more information on the SSL support in NUT.

     CERTIDENT certificate name database password
	 When compiled with SSL support, you can specify the certificate name to
	 retrieve from the database, for the client to authenticate itself,  and
	 the  password	required  to access the private key related to that cer-
	 tificate.

	 Up until NUT release v2.8.5 this was a no-op when built  with	OpenSSL.
	 Now  this  feature  is supported with both OpenSSL (fully with 1.1.0 or
	 newer, just for private key password with older 1.0.2+ library  and  an
	 empty "certificate name") and NSS backends.

	     Note
	     Be  sure  to enclose the "certificate name" in double-quotes if you
	     are using a value with spaces in it.

     CERTHOST hostname certificate name certverify forcessl
	 When compiled with SSL support, you can specify the security  directive
	 for each server you can contact.

	 Each  entry  maps  a server name with the expected certificate name and
	 flags indicating if the server certificate must be  "verified"  (should
	 the  secure connection attempt be aborted upon mismatch or inability to
	 verify?), and if the connection must be "secured" (should there  be  no
	 fallback to plain-text?)

	 Up  until  NUT release v2.8.5 this was a no-op when built with OpenSSL.
	 Now this feature is supported with both OpenSSL >= 1.1.0 and NSS  back-
	 ends.

	     Note
	     Be  sure  to enclose "certificate name" in double-quotes if you are
	     using a value with spaces in it.

     CERTVERIFY 0 | 1
	 When compiled with SSL support, make upsmon verify all connections with
	 certificates.

	 Without this, there is no guarantee that the upsd is  the  right  host.
	 Enabling  this  greatly  reduces the risk of man-in-the-middle attacks.
	 This effectively forces the use of SSL, so don't use this unless all of
	 your upsd hosts are ready for SSL and have their certificates in order.

	 When compiled with NSS support of SSL (also OpenSSL since  NUT  release
	 v2.8.6),  this  can  be  overridden  for certain hosts specified with a
	 CERTHOST directive.

     FORCESSL 0 | 1
	 When compiled with SSL, specify that a secured connection must be  used
	 to communicate with upsd.

	 If  you  don't use CERTVERIFY 1, then this will at least make sure that
	 nobody can sniff your sessions without a  large  effort.  Setting  this
	 will  make  upsmon  drop connections if the remote upsd doesn't support
	 SSL, so don't use it unless all of them have it running.

	 When compiled with NSS support of SSL (also OpenSSL since  NUT  release
	 v2.8.6),  this  can  be  overridden  for certain hosts specified with a
	 CERTHOST directive.

     DEBUG_MIN INTEGER
	 Optionally specify a minimum debug level for upsmon  daemon,  e.g.  for
	 troubleshooting  a  deployment,  without  impacting foreground or back-
	 ground running mode directly. Command-line option -D can only	increase
	 this verbosity level.

	     Note
	     If  the  running  daemon receives a reload command, presence of the
	     DEBUG_MIN NUMBER value in the configuration file  can  be	used  to
	     tune  debugging verbosity in the running service daemon (it is rec-
	     ommended to comment it away or set the  minimum  to  explicit  zero
	     when  done,  to  avoid huge journals and I/O system abuse). Keep in
	     mind that for this run-time tuning, the DEBUG_MIN value present  in
	     reloaded configuration files is applied instantly and overrides any
	     previously set value, from file or CLI options, regardless of older
	     logging  level being higher or lower than the newly found number; a
	     missing (or commented away) value however does not change the  pre-
	     viously active logging verbosity.

SEE ALSO
     upsmon(8), upsd(8), nutupsdrv(8).

   Internet resources:
     The NUT (Network UPS Tools) home page: https://www.networkupstools.org/

Network UPS Tools 2.8.5.	   08/04/2026			  UPSMON.CONF(5)