APCMICROLINK(8) 		   NUT Manual			 APCMICROLINK(8)

NAME
     apcmicrolink  -  Driver  for APC Smart-UPS units using the Microlink serial
     protocol

SYNOPSIS
     apcmicrolink -h

     apcmicrolink -a UPS_NAME [OPTIONS]

	 Note

	 This man page documents the hardware-specific features  of  the  apcmi-
	 crolink  driver. For general information about NUT drivers, see nutups-
	 drv(8).

DESCRIPTION
     The apcmicrolink driver talks the APC Microlink protocol used by newer ser-
     ial-connected Smart-UPS families such as SMT and SMX  units  with	the  Mi-
     crolink RJ45 serial port.

     This  driver  is  currently experimental. It discovers most values from the
     device descriptor blob at runtime and maps supported Microlink objects onto
     standard NUT variables where possible. Unknown descriptor fields  can  also
     be published for debugging and reverse-engineering.

SUPPORTED HARDWARE
     This  driver is intended for APC Smart-UPS models that expose the Microlink
     serial protocol, notably SMT and SMX units with the vendor Microlink serial
     cable.

     Tested support currently targets:

     *	 APC Smart-UPS SMT/SMX Microlink models

     Other APC Microlink devices may work if they expose a compatible descriptor
     layout.

CONFIGURATION
     The driver is configured via ups.conf(5).

     A minimal configuration:

	 [apc-microlink]
	     driver = apcmicrolink
	     port = /dev/ttyUSB0

   Optional settings
     baudrate=num
	 Set the serial line speed. The default is 9600.

     showinternals=yes|no
	 Publish additional internal Microlink runtime values. By  default  this
	 follows  the driver debug level and is enabled automatically when debug
	 logging is on.

     showunmapped=yes|no
	 Publish descriptor values that do not currently map to a  standard  NUT
	 variable. By default this follows the driver debug level and is enabled
	 automatically when debug logging is on.

     cmdsrc=rj45|usb|localuser|smartslot1|internalnetwork1
	 Select  the  Microlink command source used for outgoing command writes.
	 The default is rj45.

IMPLEMENTED FEATURES
     The driver publishes standard identity, status,  runtime  and  outlet-group
     data  when  these objects are present in the Microlink descriptor. Descrip-
     tor-backed values are  interpreted  as  strings,  hex  identifiers,  dates,
     times,  fixed-point numbers, and enum or bitfield maps depending on the Mi-
     crolink type reported by the device.

     Writable descriptor-backed variables are exposed as  read-write  NUT  vari-
     ables  when  the  device  reports them as modifiable. Depending on the con-
     nected model, this can include values such as:

     *	 ups.id

     *	 ups.display.language

     *	 ups.test.interval

     *	 battery.date

     *	 input.transfer.delay

     *	 input.transfer.high

     *	 input.transfer.low

     *	 outlet.group.N.timer.shutdown

     *	 outlet.group.N.timer.reboot

     *	 outlet.group.N.timer.start

     *	 outlet.group.N.delay.shutdown

     *	 outlet.group.N.delay.reboot

     *	 outlet.group.N.delay.start

     *	 outlet.group.N.minimumreturnruntime

     *	 outlet.group.N.lowruntimewarning

     *	 outlet.group.N.name

     Supported instant commands currently include:

     *	 test.battery.start

     *	 test.battery.stop

     *	 test.panel.start

     *	 test.panel.stop

     Driver-assisted shutdown is not yet implemented.

CABLING
     Use the APC Microlink serial cable appropriate for the  UPS.  USB-to-serial
     adapters  can  work  if they present a standard TTY device to the operating
     system.

AUTHORS
     *	 Lukas Schmid <lukas.schmid@netcube.li>

SEE ALSO
   The core driver
     nutupsdrv(8), ups.conf(5)

   Internet resources
     The NUT (Network UPS Tools) home page: https://www.networkupstools.org/

Network UPS Tools 2.8.5.	   08/04/2026			 APCMICROLINK(8)