BLAZER_SER(8)			   NUT Manual			   BLAZER_SER(8)

NAME
     blazer_ser - Driver for Megatec/Q1 protocol serial based UPS equipment

SYNOPSIS
     blazer_ser -h

     blazer_ser -a UPS_NAME [OPTIONS]

NOTE
     This  man	page only documents the hardware-specific features of the blazer
     driver. For information about the core driver, see nutupsdrv(8).

NOTE
     Please note that this driver is deprecated and will not receive new  devel-
     opment.  If it works for managing your devices -- fine, but if you are run-
     ning it to try setting up a new device,  please  consider	the  newer  nut-
     drv_qx(8) instead, which should handle all Q* protocol variants for NUT.

     Please  do  also  report  if  your  device works with this driver, but nut-
     drv_qx(8) would not actually support it with any subdriver!

SUPPORTED HARDWARE
     The blazer driver is known to work with various UPSes from  Blazer,  Energy
     Sistem,  Fenton Technologies, General Electric, Mustek and many others. The
     NUT compatibility table lists all the known supported models. Keep in mind,
     however, that other models not listed there  may  also  be  supported,  but
     haven't been tested.

     All  devices  with  a serial interface (use the blazer_ser driver) and many
     with a USB interface (use the blazer_usb driver) are supported.

EXTRA ARGUMENTS
     You may need to override or provide defaults for some values, depending  on
     the make and model of your UPS. The following are the ones that most likely
     will need changing (see ups.conf(5)):

     default.battery.voltage.high = value
	 Maximum  battery  voltage  that  is  reached after about 12 to 24 hours
	 charging. If  you  want  the  driver  to  report  a  guesstimated  bat-
	 tery.charge,  you  need  to specify this (see BATTERY CHARGE GUESSTIMA-
	 TION).

     default.battery.voltage.low = value
	 Minimum battery voltage just before the UPS automatically  shuts  down.
	 If  you  want	the  driver to report a guesstimated battery.charge, you
	 need to specify this (see BATTERY CHARGE GUESSTIMATION).

     default.battery.voltage.nominal = value, override.battery.voltage.nominal =
     value
	 Some devices show a wrong nominal battery voltage (or none at all),  so
	 you may need to override or set a default value.

     override.battery.packs = value
	 Some  devices report a part of the total battery voltage. For instance,
	 if battery.voltage.nominal is 24 V, but it reports a battery.voltage of
	 around 2 V, the number of battery.packs to correct this  reading  would
	 be  12.  The  driver  will attempt to detect this automatically, but if
	 this fails somehow, you may want to override this value.

     ondelay = value
	 Time to wait before switching on the UPS (minutes). Note that	a  value
	 below	3  minutes, may cause earlier firmware versions to not switch on
	 automatically, so it defaults to 3 minutes.  The  acceptable  range  is
	 0..9999 minutes.

     offdelay = value
	 Time  to  wait  before  shutting  down the UPS (seconds). This value is
	 truncated to units of 6 seconds (less than 60 seconds)  or  60  seconds
	 (more than 60 seconds). Defaults to 30 seconds. The acceptable range is
	 12..600 seconds.

     norating
	 Some  UPSes will lock up if you attempt to read rating information from
	 them. Setting this flag will make the driver skip this step.

     novendor
	 Some UPSes will lock up if you attempt to read vendor information  from
	 them. Setting this flag will make the driver skip this step.

     protocol = string
	 Skip  autodetection  of the protocol to use and only use the one speci-
	 fied. Supported values are megatec, megatec/old, mustek and zinto.

     runtimecal = value,value,value,value
	 Parameter used in the (optional) runtime  estimation.	This  takes  two
	 runtimes  at  different loads. Typically, this uses the runtime at full
	 load and the runtime at half load. For instance,  if  your  UPS  has  a
	 rated runtime of 240 seconds at full load and 720 seconds at half load,
	 you would enter

	     runtimecal = 240,100,720,50

	 The  first  load  should  always be higher than the second. If you have
	 values available for loads other than 100 and 50  %  respectively,  you
	 can use those too, but keep them spaced apart as far as reasonably pos-
	 sible.  Just  don't get too close to no load (prediction of runtime de-
	 pends more on idle load for the battery then).

     chargetime = value
	 The time needed to fully recharge the battery after  being  fully  dis-
	 charged.  If  not  specified,	the driver defaults to 43200 seconds (12
	 hours). Only used if runtimecal is also specified.

     idleload = value
	 Minimum battery load used by the driver to estimate the runtime. If not
	 specified, the driver defaults to 10%. Only used if runtimecal is  also
	 specified.

   SERIAL INTERFACE ONLY
     cablepower = string
	 By  default the driver will set DTR and clear RTS (normal). If you find
	 that your UPS isn't detected or the communication with the UPS is unre-
	 liable, you may try if clear DTR and set RTS (reverse), set DTR and RTS
	 (both) or clear DTR and RTS (none) improves this situation.

UPS COMMANDS
     This driver supports some instant commands (see upscmd(8)):

     beeper.toggle
	 Toggle the UPS beeper. (Not available on some hardware.)

     load.on
	 Turn on the load immediately.

     load.off
	 Turn off the load immediately (see KNOWN PROBLEMS).

     shutdown.return
	 Turn off the load and return when power is back. Uses	the  timers  de-
	 fined by ondelay and offdelay.

     shutdown.stayoff
	 Turn  off  the load and remain off (see KNOWN PROBLEMS). Uses the timer
	 defined by offdelay.

     shutdown.stop
	 Stop a shutdown in progress.

     test.battery.start.deep
	 Perform a long battery test (Not available on some hardware.)

     test.battery.start.quick
	 Perform a (10 second) battery test.

     test.battery.start value
	 Perform a battery test for the duration of value minutes.

     test.battery.stop
	 Stop a running battery test (not available on some hardware.)

BATTERY CHARGE GUESSTIMATION
     Due to  popular  demand,  this  driver  will  report  a  guesstimated  bat-
     tery.charge  value and optionally battery.runtime, provided you specified a
     couple of the EXTRA ARGUMENTS listed above.

     If  you  specify  both  battery.voltage.high  and	battery.voltage.low   in
     ups.conf(5),  but	don't enter runtimecal, it will guesstimate the state of
     charge by looking at the battery voltage alone. This is not reliable  under
     load, as this only gives reasonably accurate readings if you disconnect the
     load,  let  the  battery  rest for a couple of minutes and then measure the
     open cell voltage. This just isn't practical if the power went out and  the
     UPS is providing power for your systems.

			      battery.voltage - battery.voltage.low
	 battery.charge =  ------------------------------------------ x 100 %
			   battery.voltage.high - battery.voltage.low

     There  is	a way to get better readings without disconnecting the load, but
     this requires one to keep track on how much (and how fast) current is going
     in- and out of the battery. If you specified  the	runtimecal,  the  driver
     will attempt to do this. Note however, that this heavily relies on the val-
     ues  you  enter  and  that the UPS must be able to report the load as well.
     There are quite a couple of devices that report  0%  (or  any  other  fixed
     value) at all times, in which case this obviously doesn't work.

     The  driver  also	has no way of determining the degradation of the battery
     capacity over time, so you'll have to deal with this yourself (by adjusting
     the values in runtimecal). Also note that the driver  guesses  the  initial
     state  of	charge	based  on  the battery voltage, so this may be less than
     100%, even when you are certain that they are full. There is just no way to
     reliably measure this between 0 and 100% full charge.

     This is better than nothing (but not by much). If any of the above calcula-
     tions are giving you incorrect readings, remember that you are the one  who
     put  in  the values in ups.conf(5), so don't complain to the author. If you
     need something better, consider buy an UPS that reports battery.charge  and
     battery.runtime all by itself without the help of a NUT driver.

NOTES FOR THE PREVIOUS USER OF MEGATEC DRIVERS
     The  blazer  drivers  having  replaced the megatec ones, some configuration
     changes may be required by users switching to blazer.

     Part of this, the following  megatec  options,  in  ups.conf,  have  to  be
     changed:

     battvolts
	 You  need to use default.battery.voltage.high and default.battery.volt-
	 age.low

     dtr and rts
	 You need to use cablepower

     ignoreoff
	 This parameter can simply be discarded, since it  was	a  wrong  under-
	 standing of the specification.

KNOWN PROBLEMS
     Some UPS commands aren't supported by all models. In most cases, the driver
     will send a message to the system log when the user tries to execute an un-
     supported	command. Unfortunately, some models don't even provide a way for
     the driver to check for this, so the  unsupported	commands  will	silently
     fail.

     Both  the	load.off and shutdown.stayoff instant commands are meant to turn
     the load off indefinitely. However, some UPS models don't allow this.

     Some models report a bogus value for the beeper status (will always be  en-
     abled or disabled). So, the beeper.toggle command may appear to have no ef-
     fect  in  the  status  reported  by the driver when, in fact, it is working
     fine.

     The temperature and load value is known to be bogus in some models.

AUTHORS
     *	 Arjen de Korte <adkorte-guest at alioth.debian.org>

     *	 Alexander Gordeev <lasaine at lvk.cs.msu.su>

SEE ALSO
     blazer_usb(8), nutupsdrv(8), upsc(8), upscmd(8), upsrw(8)

   Internet Resources:
     *	 The NUT (Network UPS Tools) home page: https://www.networkupstools.org/

     *	 The NUT HCL: https://www.networkupstools.org/stable-hcl.html

Network UPS Tools 2.8.5.	   08/04/2026			   BLAZER_SER(8)