CLONE(8)			  NUT Manual			      CLONE(8)

NAME
       clone - Clone an	UPS, treating its outlet as if it were an UPS (with
       shutdown	INSTCMD	support)

SYNOPSIS
       clone -h

       clone -a	UPS_NAME [OPTIONS]

	   Note

	   This	man page only documents	the specific features of the clone
	   driver. For information about the core driver, see nutupsdrv(8).

DESCRIPTION
       This driver, which sits on top of another driver's local	UNIX socket
       file (or	Windows	named pipe), allows users to group clients to a
       particular outlet of a device and deal with this	output as if it	were a
       normal UPS.

       Unlike the clone-outlet(8) driver, this driver represents a manageable
       device that can be used both for	monitoring and for client computer and
       UPS/ePDU	outlet shutdowns (it supports sending relevant instant
       commands	during run time).

       Unlike dummy-ups(8), this driver	does not require a running upsd	data
       server nor use the networked NUT	protocol to talk to the	"real" driver
       (which may be remote in case of dummy-ups repeater mode).

       This driver does	not create a completely	new virtual device, but
       replaces	or extends some	of the original	readings reported by the
       "real" driver using information from the	specified outlet, and relays
       all other readings as they were.

       Remote clients like upsmon can MONITOR the device entry presented by
       the data	server with this driver	(and the "real"	driver)	running	and
       published.

       A larger	deployment with	one or more lower-priority devices collected
       on a manageable outlet of an UPS	or ePDU	would likely see several
       drivers set up on the system actually capable of	interactions with the
       UPS and running the NUT data server upsd(8) (and	likely powered by
       another outlet):

          a "real" driver talking to the UPS;

          a clone driver talking to the "real"	driver and issuing outlet
	   power-off (or power-cycle) based on relatively high thresholds for
	   remaining battery charge and/or runtime of the actual UPS (or
	   explicit instant commands), with such operations first setting the
	   respective timers for the outlet on the "real" driver, and the
	   "FSD" flag among states of the virtual UPS status;

          possibly a clone-outlet driver which	is read-only and interprets
	   the outlet timer values as triggers for "FSD" or "OFF" flags
	   reported among states of the	virtual	UPS status.

       With this approach, the lower-priority systems collected	on such	outlet
       would run the NUT upsmon(8) client to MONITOR the virtual UPS presented
       by the read-only	clone-outlet driver and	shut down as soon as the "FSD"
       flag is raised (fairly early, based on charge and/or runtime thresholds
       configured for that driver) allowing the	higher-priority	devices
       (likely including the NUT server) to enjoy a longer on-battery life.

       The clone driver	responsible for	outlet power state changes would not
       normally	be monitored directly (e.g. to avoid unfortunate direct
       shutdown	requests from those clients), although it can be (instead of
       clone-outlet) in	sufficiently trusted networks.

EXTRA ARGUMENTS
       This driver supports the	following settings:

       port=drivername-devicename
	   Required. The standard NUT driver port setting, here	it provides
	   the name of the local Unix socket file (or Windows named pipe) for
	   connection to the "real" device driver.

       load.off=command
	   Recommended.	Set the	command	on the "real" UPS driver that will be
	   used	to switch off the outlet. You need both	load.off and load.on
	   in order to power cycle the outlet. Otherwise, shutting down	the
	   clients powered by an outlet	is a one way street (see IMPORTANT).

       load.on=command
	   Recommended.	Set the	command	on the "real" UPS driver that will be
	   used	to switch on the outlet. You need both load.off	and load.on in
	   order to power cycle	the outlet. Otherwise, shutting	down the
	   clients powered by an outlet	is a one way street (see IMPORTANT).

       load.status=value
	   Recommended.	Set the	variable on the	"real" UPS driver that will be
	   used	to indicate the	outlet status (i.e. on/off). If	not specified,
	   the clone driver will attempt to keep track of the outlet status,
	   but this is less reliable.

       offdelay=num
	   Set the timer (in seconds) before the outlet	is turned off after
	   the shutdown	condition (OB LB) for this outlet is met or a command
	   to shutdown was issued. Defaults to 120 seconds.

       ondelay=num
	   Set the timer (in seconds) for the outlet to	switch on in case the
	   power returns after the outlet has been switched off. Defaults to
	   30 seconds.

       mincharge=value
	   Set the remaining battery level when	the clone UPS switches to LB
	   (percent).

       minruntime=value
	   Set the remaining battery runtime when the clone UPS	switches to LB
	   (seconds).

IMPLEMENTATION
       The port	specification in the ups.conf(5) should	reference the local
       driver socket (or Windows named pipe) that the "real" UPS driver	is
       using. For example:

	     [realups]
		driver = usbhid-ups
		port = auto

	     [clone-outlet-1]
		driver = clone
		port = usbhid-ups-realups
		load.on	= outlet.1.load.on
		load.off = outlet.1.load.off
		load.status = outlet.1.status
		desc = "Outlet 1 of the	Real UPS"
		[...]

       This driver supports instant commands to	initiate a forced shutdown for
       upsmon or similar clients which MONITOR this virtual UPS	device,	if the
       outlet status is	currently on and no other shutdown was initiated yet
       (setting	the virtual UPS	shutdown delay timer to	offdelay and issuing
       an FSD via ups.status):

          shutdown.return -- power the	outlet back on after ondelay;

          shutdown.stayoff -- keep the	outlet off.

       Such commands are propagated to the "real" driver using the NUT socket
       protocol	(using command names specified in the load.off and load.on
       driver configuration options), if the shutdown or start timers are set
       at the moment, or if the	"real" device is not "online" and its known
       battery charge or runtime are below the configured "low"	thresholds.

       The outlet status is determined using the name specified	by the
       load.status driver option if set, or is just assumed by latest
       completed shutdown/start	operation (using unknown outlet	number).

       The driver does not support a common NUT	device shutdown	operation as
       such (clone -k just prints an error and bails out).

       This driver also	supports setting certain NUT variables at run-time:

          battery.charge.low -- see mincharge in driver options;

          battery.runtime.low -- see minruntime in driver options.

       Compared	to the "real" driver's readings, this driver also adds (or
       overrides) the following	data points: ups.delay.shutdown,
       ups.delay.start,	ups.timer.shutdown and ups.timer.start.	It keeps track
       of "real" driver's values of battery.charge and battery.runtime (actual
       current readings) to decide on automated	outlet shutdown	later on.

IMPORTANT
       Unlike a	real UPS, you should not configure a upsmon primary mode for
       this driver. When a upsmon(8) primary sees the OB LB flags and tells
       the upsd(8) data	server that it is OK to	initiate the shutdown
       sequence, the server will latch the FSD status, and it will not be
       possible	to restart the systems connected without restarting the	upsd
       server.

       This will be a problem if the power returns after the clone UPS
       initiated the shutdown sequence on its outlet, but returns before the
       real UPS	begins shutting	down. The solution is in the clone driver
       itself, that will insert	the FSD	flag if	needed without the help	of an
       upsmon primary.

CAVEATS
       The clone UPS will follow the status on the real	UPS driver. You	can
       only make the clone UPS shutdown	earlier	than the real UPS driver, not
       later. If the real UPS driver initiates a shutdown, the clone UPS
       driver will immediately follow.

       Be aware	that the commands to shutdown/restart an outlet	on the real
       UPS drivers are not affected, so	if you tell the	real UPS driver	to
       shutdown	the outlet of the clone	UPS driver, your clients will lose
       power without warning.

       If you use service management frameworks	like systemd or	SMF to manage
       the dependencies	between	driver instances and other units, then you may
       have to set up special dependencies (e.g. with systemd "drop-in"
       snippet files) to queue your clone drivers to start after the "real"
       device drivers.

AUTHOR
       Arjen de	Korte <adkorte-guest@alioth.debian.org>

SEE ALSO
       upscmd(1), upsrw(1), ups.conf(5), clone-outlet(8), nutupsdrv(8)

   Dummy driver:
       The "repeater" mode of dummy-ups	driver is in some ways similar to the
       clone and clone-outlet drivers, by relaying information from a locally
       or remotely running "real" device driver	(and NUT data server).

       dummy-ups(8)

   Internet Resources:
       The NUT (Network	UPS Tools) home	page: https://www.networkupstools.org/

Network	UPS Tools 2.8.2.	  04/17/2025			      CLONE(8)