NAME
       generic_modbus -	Driver for contact (direct) signal UPS devices
       connected via modbus remote I/O gateways

SYNOPSIS
       generic_modbus -h

       generic_modbus -a DEVICE_NAME [OPTIONS]

	   Note

	   This	man page only documents	the specific features of the
	   generic_modbus driver. For information about	the core driver, see
	   nutupsdrv(8).

SUPPORTED HARDWARE
       This is a generic modbus	driver expected	to work	with contact (direct)
       signal UPS devices, connected via modbus	RIO (remote I/O) either	serial
       or TCP/IP.

       The driver has been tested against PULS UPS (model UB40.241) via	MOXA
       ioLogikR1212 (RS485) and	ioLogikE1212 (TCP/IP).

       More information	about this UPS can be found here:
	   https://products.pulspower.com/ca/ubc10-241-n1.html

       More information	about Moxa ioLogik R1212, E1212	can be found here:
	   https://www.moxa.com/en/products/industrial-edge-connectivity/controllers-and-ios

       The PULS	UPS UB40.241 supports the following signals:

	   Ready contact      (DO) <-->	HB
	   Buffering contact  (DO) <-->	OL | OB
	   Battery-low	      (DO) <-->	LB
	   Replace Battery    (DO) <-->	RB
	   Inhibit	      (DI) <-->	FSD

       Digital port direction (DI/DO) assumes the device perspective

       The driver's concept is to map the UPS states (as defined in NUT) onto
       UPS contacts' states. The driver	has an extended	configuration
       interface implemented using variables defined in	ups.conf.

HARDWARE INTERCONNECTION
       The commission of modbus	remote I/O server as well as UPS device	is
       carried out following the corresponding instruction manuals. The
       following figure	depicts	the anticipated	communication path and
       hardware	interconnection:

	   +------+	  +----------------+	   +------------+	+------------+
	   | UPSD | <---> | GENERIC_MODBUS | <---> | MODBUS RIO	| <--->	| UPS DEVICE |
	   +------+  (1)  +----------------+  (2)  +------------+  (3)	+------------+
	      |			  |
	      +-------------------+
		 HOST CONTROLLER

	   (1) Unix IPC
	   (2) RS232 | TCP/IP
	   (3) contacts

EXTRA ARGUMENTS
       This driver supports the	following optional settings in the ups.conf(5)
       file:

   Generic:
       device_mfr=value
	   A string specifying the manufacturer	of the UPS device (default
	   UNKNOWN).

       device_model=value
	   A string specifying the model of the	UPS device (default UNKNOWN).

   Serial:
       ser_baud_rate=value
	   A integer specifying	the serial port	baud rate (default 9600).

       ser_data_bit=value
	   A integer specifying	the serial port	data bit (default 8).

       ser_parity=value
	   A character specifying the serial port parity (default N).

       ser_stop_bit=value
	   An integer specifying the serial port stop bit (default 1).

   Modbus:
       rio_slave_id=value
	   An integer specifying the RIO modbus	slave ID (default 1).

   States (X = OL, OB, LB, HB, RB, CHRG, DISCHRG, FSD)
       <X>_addr=value
	   A number specifying the modbus address for the X state.

       <X>_regtype=value
	   A number specifying the modbus register type	for the	X state

       Default values:

	       1 for X = OL, OB, LB ,HB, RB, CHRG, DISCHRG
	       0 for X = FSD

       Valid values:

	       0:COIL, 1:INPUT_B, 2:INPUT_R, 3:HOLDING

       <X>_noro=value
	   A number specifying the contact configuration for the X state
	   (default 1).

       Valid values:

	       0:NC, 1:NO

	       Note
	       NO stands for normally open and NC for normally closed contact

   Shutdown
       FSD_pulse_duration=value
	   A number specifying the duration in ms for the inhibit pulse. If
	   it's	not defined, signal has	only one transition depending on
	   FSD_noro configuration.

	   Examples for	FSD signal configuration:

	   FSD_noro = 1
	   FSD_pulse_duration =	150

				+-----+
				|     |
	   inhibit pulse  >-----+     +------------------>
				 <--->
				 150ms

	   FSD_noro = 0

	   inhibit pulse  >-----+
				|
				+------------------------>

CONFIGURATION
       Here is an example of generic_modbus driver configuration in ups.conf
       file:

	   [generic_modbus]
	     driver = generic_modbus
	     port = /dev/ttyUSB0
	     desc = "generic ups driver"
	     # device info
	     device_mfr	= "PULS"
	     device_model = "UB40.241"
	     # serial settings
	     ser_baud_rate = 9600
	     ser_parity	= N
	     ser_data_bit = 8
	     ser_stop_bit = 1
	     # modbus slave id
	     rio_slave_id = 5
	     # UPS signal state	attributes
	     OB_addr = 0x0
	     OB_regtype	= 1
	     OB_noro = 0
	     LB_addr = 0x1
	     LB_regtype	= 1
	     HB_addr = 0x2
	     HB_regtype	= 1
	     RB_addr = 0x3
	     RB_regtype	= 1
	     FSD_addr =	0x0
	     FSD_regtype = 0
	     FSD_pulse_duration	= 150

INSTANT	COMMANDS
       This driver support the following instant commands:

       load.off
	   executes "instant poweroff"

INSTALLATION
       This driver may be not built by default.	You can	build it by installing
       libmodbus and running configure --with-modbus=yes.

       You also	need to	give proper permissions	on the local serial device
       file (/dev/ttyUSB0 for example) to allow	the run-time NUT driver	user
       account to access it.

OTHER NOTES
       The generic_modbus driver intends to support generic UPS	devices	with
       contact signals through modbus TCP/RTU gateways (also known as RIO --
       remote I/Os). The data and signal path looks like this:

	   [UPSD] <--- IPC --->	[GENERIC_UPS] <--- modbus TCP/RTU ---> MODBUS-RIO <--- contacts	---> [UPS DEVICE]

       On the other hand, you can setup	any kind of modbus server, and
       configure the generic_modbus driver to connect and read or write
       specific	registers. Your	application / modbus server could then drive
       NUT statuses (e.g. OL, OB, HB etc) by writing over those	registers.

AUTHOR
       Dimitris	Economou <dimitris.s.economou@gmail.com>

SEE ALSO
   The core driver:
       nutupsdrv(8), ups.conf(5)

   Internet resources:
          The NUT (Network UPS	Tools) home page:
	   https://www.networkupstools.org/

          libmodbus home page:	http://libmodbus.org

Network	UPS Tools 2.8.2.	  04/17/2025		     GENERIC_MODBUS(8)