HUAWEI-UPS2000(8)		   NUT Manual		       HUAWEI-UPS2000(8)

NAME
     huawei-ups2000  -	Driver	for  Huawei  UPS2000 (1kVA-3kVA) UPS with USB or
     RS-232 serial Modbus connection.

SYNOPSIS
     huawei-ups2000 -h

     huawei-ups2000 -a DEVICE_NAME [OPTIONS]

	 Note

	 This man page only documents  the  hardware-specific  features  of  the
	 huawei-ups2000  driver.  For information about the core driver, see nu-
	 tupsdrv(8).

SUPPORTED HARDWARE
     This driver supports Huawei UPS2000 series, online (double conversion)  UPS
     with the following characteristics.

      1. Output power: 1 kVA to 3 kVA (higher power models are unsupported).

       2. Connection: USB or RS-232 (driver compatibility issues exist, read the
	 section Cabling carefully).

	 *   USB: For most models, Linux 5.12 or a  newer  kernel  is  required,
	     Windows  also  requires an additional serial port driver. For other
	     Unix-like systems, driver incompatibility exists, use RS-232.

	 *   RS-232: Always supported.

	 *   RS-485: Untested. Testers needed.

      3. Operating system: Unix/Linux supported by default, Windows requires NUT
	 v2.8.5 or newer.

     The UPS2000 series has two variants: UPS2000-A with a  tower  chassis,  and
     UPS2000-G	with  a rack-mount chassis. Within these two variants, there are
     also two sub-variants: a standard runtime model powered by an internal bat-
     tery pack denoted by an "S" suffix, and a long runtime model powered by  an
     external battery pack denoted by an "L" suffix.

     All  of  these  models  should be equally supported, currently, it has been
     tested on the following models.

     *	 UPS2000-A-1KTTS (firmware: UPS2000A, V2R1C1SPC40, P1.0-D1.0)

     *	 UPS2000-A-1KTTS (firmware: UPS2000A, V2R1C1SPC50, P1.0-D1.0)

     *	 UPS2000-A-2KTTS (firmware: UPS2000A, V2R1C1SPC50, P1.0-D1.0)

     *	 UPS2000-G-1KRTS (firmware: UPS2000A, V2R1C1SPC40, P1.0-D1.0)

     *	 UPS2000-G-1KRTS (firmware: UPS2000G, V2R1C1SPC50, P1.0-D1.0)

     *	 UPS2000-G-3KRTS (firmware: UPS2000A, V2R1C1SPC40, P1.0-D1.0)

     *	 UPS2000-G-3KRTS (firmware: UPS2000G, V2R1C1SPC50, P1.0-D1.0)

     *	 UPS2000-G-3KRTL (firmware: UPS2000A, V2R1C1SPC40, P1.0-D1.0)

     If your model is not in the list, we encourage you to report successful  or
     unsuccessful  results  to the bug tracker or the mailing list. Make sure to
     include the full model number of your UPS manually in your report,  because
     many  units  only report themselves as "UPS2000-A" regardless of their mod-
     els, including the G series.

     As of 2022, there	is  also  a  new  hardware  variant  with  a  WCH  CH341
     USB-to-serial  chip  instead of a MaxLinear/Exar RX21V1410 chip and reports
     itself as "UPS2000G". Driver support has been added since v0.03.

     huawei-ups2000 uses the libmodbus project, for Modbus implementation.

CABLING
     The UPS has a USB port and a RS-232 port. USB is  conditionally  supported,
     depending	on  hardware  driver availability. RS-232 is always supported on
     all operating systems, which can be used as a fallback.

     On most  UPS  models,  USB  is  powered  by  the  Exar/MaxLinear  RX21V1410
     USB-to-serial chip. On Linux, it's only usable on Linux 5.12 and later, via
     the  xr_serial kernel module. On Windows, it's also suggested to install an
     additional device driver. On some newer UPS hardware variants, a WCH  CH341
     chip is used instead, these should have better compatibility (via the ch341
     Linux  kernel module, or Windows Update). See subsection Linux USB and Win-
     dows USB for details.

     Only one port can be used at a time. When USB is used, RS-232 should be un-
     plugged from the UPS, and vice versa. Further, optional adapter cards, such
     as RS-485 or SNMP, are not supported. They should be removed from the UPS.

     Because the UPS port can be unresponsive under certain circumstances,  it's
     recommended  to  power  cycle your UPS after making a cabling change, espe-
     cially after changing the port type. That is, turn off the UPS power output
     via the front panel, then unplug the UPS from line power  input.  Wait  for
     the  LCD  screen to go black. Finally reconnect line power and restart your
     UPS.

   Linux USB
     The USB port on the UPS2000  is  originally  powered  by  a  MaxLinear/Exar
     RX21V1410	USB-to-serial  converter chip, it's only supported by Linux 5.12
     or newer, via the xr_serial kernel module. Its lsusb report is:

	 04e2:1410 Exar Corp. XR21V1410 USB-UART IC

     However, a recent hardware variant switched to the WCH CH341 serial chip:

	 1a86:5523 QinHeng Electronics CH341 in serial mode, usb to serial port converter

     If your unit has a WCH CH341 chip (likely only found in  units  made  after
     2022),  when the UPS2000 is connected via USB, you should see the following
     logs in dmesg.

	 ch341 2-1.2:1.0: ch341-uart converter detected
	 usb 2-1.2: ch341-uart converter now attached to ttyUSB0

     If so, you should be able to proceed without worrying about kernel compati-
     bility. This CH341 chip has been around for a decade and should be compati-
     ble with your system.

     On the other hand, if your unit has a MaxLinear/Exar XR21V1410  chip,  like
     most  users  do, when the UPS2000 is connected via USB to a supported Linux
     system, you should see the following logs in dmesg.

	 xr_serial 1-1.2:1.1: xr_serial converter detected
	 usb 1-1.2: xr_serial converter now attached to ttyUSB0

     The driver must be xr_serial. If your system doesn't have the necessary de-
     vice driver, you will get this message instead:

	 cdc_acm 1-1.2:1.0: ttyACM0: USB ACM device

     The generic driver cdc_acm is incompatible and cannot be used.  You  should
     upgrade your Linux kernel to Linux 5.12 or newer.

	 Warning

	 On  an unsupported system, the XR21V1410 USB device can still be recog-
	 nized as a USB ACM device,  but  communication  is  impossible,  please
	 don't waste your time on cdc_acm.

     If  you're already running on Linux 5.12 or newer kernels, but still cannot
     see the xr_serial driver, it means the driver is not enabled in your kernel
     build. If you're a regular user, you should file a bug report to your Linux
     distro maintainers and ask them to enable	xr_serial  (kernel  option  CON-
     FIG_USB_SERIAL_XR).

     When  upgrading the Linux kernel isn't an option, or when you are using an-
     other operating system (e.g. FreeBSD), RS-232 must be used. Even for  CH341
     users, one can try this option if USB somehow refuses to work.

   Windows USB
     Windows  Update  should  automatically install appropriate drivers for your
     USB device, however, manual intervention  may  be	required  in  case  this
     process fails.

     MaxLinear/Exar RX21V1410

	 For  UPS models with a MaxLinear/Exar RX21V1410 USB-to-serial converter
	 chip, an additional device driver may be required.

	 According to the official manual, it instructs users to install a  spe-
	 cial	MaxLinear   device  driver  called  XR21x141x-XP2KVista7-Driver-
	 sOnly-Vers1.7.0.0. See Huawei UPS2000 (1 kVA-3 kVA) Modbus Protocol De-
	 velopment Guide.

	 The driver described in the official manual may be outdated  or  diffi-
	 cult  to  obtain.  If so, please also try downloading the latest driver
	 from MaxLinear XR21V1410 product page on the Web. At the time of  writ-
	 ing,  the  latest driver is named XR21x_Win10_V2.7.0.0.zip in the Soft-
	 ware: Drivers, Windows 10 and newer category.

	 URLs are available at the bottom of the manual.

     WCH CH341

	 For UPS models with a WCH CH341 USB-to-serial converter chip, an  addi-
	 tional device driver may be required.

	 At  the time of writing, the latest driver is named CH341SER.EXE (v3.9,
	 2024/10/16) as a self-installer, available on WCH official website.  An
	 alternative  .zip  archive named CH341SER.ZIP with the same version can
	 also be used for manual installation via Device Manager.

	 URLs are available the bottom of the manual.

   RS-232
     RS-232 is supported on all operating systems, either via a built-in  serial
     port  on your computer, or by using an external USB-to-RS-232 converter. If
     you plan to use an USB-to-RS-232 converter, make  sure  it's  supported  by
     your operating system.

   RS-485
     RS-485  support is provided by UPS2000 using an optional adapter card. This
     driver is untested on RS-485, but the author suspects that RS-485 uses  the
     same  serial  protocol  as RS-232, which should be supported. If you have a
     RS-485 adapter, we encourage you to report successful or  unsuccessful  re-
     sults to the bug tracker or the mailing list.

INSTALLATION
     This  driver  may	be  not built by default. You can build it by installing
     libmodbus (with development packages) and running

	 configure --with-serial=yes --with-modbus=yes

     You also need to give proper (R/W) permissions on the local  serial  device
     file  to allow the NUT driver run-time user to access it. This may need ad-
     ditional setup for start-up scripting, udev or upower rules, to  apply  the
     rights  on  every	boot -- especially if your device nodes are tracked by a
     virtual filesystem.

     For example, a USB-to-serial converter can be identified as /dev/ttyACM0 or
     /dev/ttyUSB0 on Linux, or /dev/ttyU0 on FreeBSD (note the capital	"U").  A
     built-in  serial  port  can  be identified as /dev/ttyS0 on Linux or one of
     /dev/cua* names on FreeBSD.

EXTRA ARGUMENTS
     This driver supports the following optional  settings  in	the  ups.conf(5)
     file:

     offdelay=value
	 Time  to  wait before shutting down the UPS (seconds), acceptable range
	 is 6 seconds (0.1 minutes) to 5940 seconds (99 minutes). Defaults to 60
	 seconds. Must be a multiple of 6 seconds. To ensure your system has ad-
	 equate time to shut down after a power failure, it's highly recommended
	 to adjust offdelay.

     rebootdelay=value
	 Time to wait before rebooting the UPS (seconds), acceptable range is  6
	 seconds (0.1 minutes) to 5940 seconds (99 minutes). Defaults to 60 sec-
	 onds. Must be a multiple of 6 seconds. This is used by the shutdown.re-
	 boot.graceful	instant command. If you've adjusted offdelay, you should
	 also adjust rebootdelay.

     ondelay=value
	 Time to wait before switching on the UPS (seconds), acceptable range is
	 60 seconds (1 minutes) to 5940 seconds (99  minutes).	Defaults  to  60
	 seconds.  Must  be  a multiple of 60 seconds (not 6 seconds). You don't
	 need to adjust this delay unless you have special requirements.

	 Note

	 Due to hardware limitation, in this driver, ondelay is  respected  only
	 when  line power is available. If a power failure has occurred, the UPS
	 and the load is always immediately switched on, as soon (or as late) as
	 line power is restored.

INSTANT COMMANDS
     This driver supports some instant commands (see upscmd(8)):

     shutdown.stayoff
	 After an offdelay, turn off the load. When line power is  back,  remain
	 off.

     shutdown.return
	 After	an offdelay, turn off the load. When line power is back, turn on
	 the load, possibly after an ondelay.

	 Note

	 Normally, the load is turned on as soon as line power is back.  But  if
	 line  power  is never lost, or has came back unexpectedly in the middle
	 of an ongoing shutdown (an undesirable "power race" condition that many
	 entry-level products on the market fail to recover from), the	load  is
	 turned  on  after  an	ondelay.  Thus, UPS2000 is unaffected by a power
	 race, the load is guaranteed to always restart.

     shutdown.reboot
	 Like shutdown.return, except that the load is turned off immediately (6
	 seconds in this implementation).

     shutdown.reboot.graceful
	 Like shutdown.return, except that the load is turned off  after  a  re-
	 bootdelay, not an offdelay.

     beeper.enable
	 Enable the UPS beeper.

     beeper.disable
	 Disable the UPS beeper.

     beeper.toggle
	 Toggle the UPS beeper.

     bypass.start
	 Put the UPS in bypass mode. Use with caution. It exposes your equipment
	 to  unregulated  line power and provides no protection from power fail-
	 ures. Also, the UPS may shut down whenever the bypass input voltage  is
	 out  of  the  nominal	range. As a warning, the UPS beeps once every 10
	 seconds in bypass mode.

	 Note

	 The driver has a basic foolproof mechanism. If the bypass input is  al-
	 ready	abnormal due to a power failure, the driver refuses to enter by-
	 pass mode by aborting the command and logging an error. However, it of-
	 fers no protection after the UPS has entered (or in the middle  of  en-
	 tering) bypass mode. Thus, again, use with caution.

     bypass.stop
	 Put the UPS out of bypass mode.

     load.on
	 Turn on the load immediately.

     load.off
	 Turn  off the load immediately. Use with caution, everything on the UPS
	 will lost power.

     test.battery.start.quick
	 Perform a short battery test.

     test.battery.start.deep
	 Perform a long battery test.

     test.battery.stop
	 Stop a running battery test.

VARIABLES
     This driver supports some writable runtime variables (see upsrw(8)):

     ups.beeper.status
	 Enable or disable the UPS beeper, disabled or enabled.

	 Note

	 The beeper can only be disabled completely,  it  cannot  be  temporally
	 muted	until  the next alarm, but the option muted is also accepted for
	 convenience, muted is treated as an alias of disabled.

     ups.delay.shutdown
	 Seconds to wait after shutdown with delay  command.  It's  the  runtime
	 equivalent of offdelay. See description of offdelay.

     ups.delay.reboot
	 Seconds  to  wait before rebooting the UPS, it's the runtime equivalent
	 of rebootdelay. See description of rebootdelay.

     ups.delay.start
	 Seconds to wait before restarting the load, it's the runtime equivalent
	 of ondelay. See description of ondelay.

KNOWN ISSUES AND BUGS
   Fixed bugs
     Driver v0.03 (NUT v2.8.1) added support  for  UPS2000G  with  a  WCH  CH341
     USB-to-serial interface, these models were previously unsupported.

     Driver  v0.04  (NUT v2.8.1) fixed a timeout recovery bug that leads to end-
     less read failures and permanent data stalls.

     Driver v0.12 (NUT v2.8.5) fixed support for Microsoft Windows, Windows  was
     previously unsupported due to a file locking bug.

     See Historical bugs at the bottom of this manual for links.

   Battery status has a non-fatal read failure
     It's  usually  harmless and can be safely ignored. It's only logged for in-
     formative purposes (LOG_INFO), not as a warning or error.

   Data stale
     Under certain circumstances, some registers can return invalid  values  and
     trigger  a  "data	stale"	error. Once a data stale error has occurred, you
     should see error messages similar to the example below in the system log.

	 huawei-ups2000: register 2002 has invalid value a000,
	 upsd: Data for UPS [huawei] is stale - check driver
	 upsd: UPS [huawei] data is no longer stale

     So far all known problems have been fixed by the author, but an unknown one
     cannot be ruled out. If you have encountered "data stale"	problems  during
     normal uses, please file a bug report with full logs attached.

     Before troubleshooting or reporting a problem, it's important to check your
     dmesg  log  for  USB connect and disconnect events to avoid wasting time on
     the NUT driver when the actual problem is USB.

     For example, if someone yanks the cable out of the USB port, or  if  a  new
     USB  device  is plugged into a USB host/hub that is struggling to power its
     ports (common on single-board computers like Raspberry Pi), or if you  have
     flaky cabling or EMI noise, due to all these and similar reasons the serial
     converter can get disconnected from USB, at least briefly.

     This  creates  a  permanent  data	stale  situation, and the driver must be
     restarted (plugging the USB back won't fix it, since the  driver  is  still
     using the nonexistent serial device, if the system kernel initializes a new
     device driver instance internally).

     These  USB  problems usually have nothing to do with NUT. If it's the case,
     you should solve the underlying USB problem -- check the cable,  check  the
     converter, try a powered USB hub, try a full-speed USB isolator, etc.

   Serial port becomes unresponsive
     Some  malformed  commands	are  known to lock up the serial port (including
     USB, which is a USB-to-serial device). Upon receiving them,  UPS2000  stops
     all serial communications. The result is a completely unresponsive UPS, re-
     gardless  of  what  you do -- restarting NUT, rebooting the computer -- can
     not restore connectivity, as if someone has unplugged the RS-232 cable.

     To recover, simply power cycle the UPS: Turn off the  UPS	output	via  the
     front  panel,  then  unplug the UPS from line power. Wait for the LCD front
     screen to go black. Finally reconnect line power and restart your UPS.

     That being said, a serial port lockup is unlikely to happen.  To  our  best
     knowledge,  this  driver  never sends malformed commands to the UPS (it was
     only a problem during early development). Furthermore, due to a CRC  check-
     sum, they're unlikely to be accidentally generated.

     Still,  we recommend to power cycle your UPS after making a cabling change,
     especially after changing from RS-485/USB to RS-232, just to ensure the UPS
     selects the correct communication interface. Also, if you have discovered a
     reproducible serial port lockup problem, it can  be  a  previously  unknown
     bug, so please make sure to file a bug report.

   USB chip (MaxLinear/Exar RX21V1410) is unsupported
     As  previously stated, only RS-232 is supported on all systems. On most UPS
     units, the USB chip RX21V1410 is used, and it  requires  a  device-specific
     driver xr_serial, which is only available on Linux 5.12 and newer kernels.

     On  an  unsupported system, the USB device can still be recognized as a USB
     ACM device, but in reality, communication is impossible.  It  can	only  be
     fixed  by implementing a driver for your system, nothing can be done within
     NUT. Please use the RS-232 port instead.

     Alternatively, if your unit has a WCH CH341  chip	(likely  only  found  in
     units made after 2022), it should have better compatibility.

     See the previous section Cabling for more information.

AUTHOR
     Yifeng Li <tomli@tomli.me>

SEE ALSO
   The core driver:
     nutupsdrv(8)

   Historical bugs:
     *	 Commit:  support newer UPS2000G/CH341 variants: https://github.com/net-
	 workupstools/nut/commit/59af0780af0db7341ff81d460fc10736458722aa

     *	 Issue 1846: huawei-ups2000: Data Stale with  Endless  "Register  has  a
	 read  failure.  Retrying..." https://github.com/networkupstools/nut/is-
	 sues/1846

     *	 Commit:  fix  broken  timeout	recovery  behavior   in   Issue   #1846:
	 https://github.com/networkupstools/nut/com-
	 mit/3dae58f403f88dace52e2caac3c0690e45b8ef22

     *	 Issue 3244: USB and serial ports work on Linux but not on Windows (file
	 locking): https://github.com/networkupstools/nut/issues/3244

     *	 Commit:   call   ser_close()	before	 modbus_connect(),   fix  #3244:
	 https://github.com/networkupstools/nut/com-
	 mit/db2e148503d654726d5520d68e20e71117335813

   Windows Drivers:
     *	 Huawei  UPS2000  (1  kVA-3  kVA)  Modbus  Protocol  Development  Guide:
	 https://support.huawei.com/enterprise/en/doc/EDOC1000110696

     *	 MaxLinear XR21V1410 Product Page: https://www.maxlinear.com/product/in-
	 terface/uarts/usb-uarts/xr21v1410

     *	 CH341SER.EXE	 -    Nanjing	QinHeng   Microelectronics   Co.,   Ltd:
	 https://www.wch-ic.com/downloads/CH341SER_EXE.html

     *	 CH341SER.ZIP	-   Nanjing   QinHeng	Microelectronics    Co.,    Ltd:
	 https://www.wch-ic.com/downloads/CH341SER_ZIP.html

     If a download link expires, use a snapshot from the Internet Archive:

     *	 XR21x_Win10_V2.7.0.0.zip:
	 https://web.archive.org/web/20260310005640if_/https://www.maxlin-
	 ear.com/Document/index?id=23338&languageid=1033&type=Software%3A%20Dri-
	 vers&partnumber=XR21V1410

     *	 CH341SER.EXE:
	 https://web.archive.org/web/20260112182437if_/https://www.wch-ic.com/down-
	 load/file?id=65

     *	 CH341SER.ZIP:
	 https://web.archive.org/web/20260217145229if_/https://www.wch-ic.com/down-
	 load/file?id=5

   Internet resources:
     *	 The NUT (Network UPS Tools) home page: https://www.networkupstools.org/

     *	 Huawei    UPS2000-A   (1   kVA-3   kVA)   User   Manual:   https://sup-
	 port.huawei.com/enterprise/en/doc/EDOC1000084260

     *	 Huawei  UPS2000  (1  kVA-3  kVA)  Modbus  Protocol  Development  Guide:
	 https://support.huawei.com/enterprise/en/doc/EDOC1000110696

     *	 libmodbus home page: http://libmodbus.org

Network UPS Tools 2.8.5.	   08/04/2026		       HUAWEI-UPS2000(8)