HUAWEI_UPS2000(8)		  NUT Manual		     HUAWEI_UPS2000(8)

NAME
       huawei-ups2000 -	Driver for Huawei UPS2000 (1kVA-3kVA) UPS with USB or
       RS-232 serial Modbus connection.

SYNOPSIS
       huawei-ups2000 -h

       huawei-ups2000 -a DEVICE_NAME [OPTIONS]

	   Note

	   This	man page only documents	the hardware-specific features of the
	   huawei-ups2000 driver. For information about	the core driver, see
	   nutupsdrv(8).

SUPPORTED HARDWARE
       This driver supports Huawei UPS2000 series, online (double conversion)
       UPS with	the following characteristics.

	1. Output power: 1 kVA to 3 kVA	(higher	power models are unsupported).

	2. Connection: USB or RS-232 (for most UPS models, USB is only
	   supported on	Linux 5.12 and newer kernels, but there	are
	   exceptions, read the	section	Cabling	carefully).

       The UPS2000 series has two variants: UPS2000-A with a tower chassis,
       and UPS2000-G with a rack-mount chassis.	Within these two variants,
       there are also two sub-variants:	a standard runtime model powered by an
       internal	battery	pack denoted by	an "S" suffix, and a long runtime
       model powered by	an external battery pack denoted by an "L" suffix.

       All of these models should be equally supported,	but more testers are
       needed. Currently, it has been tested on	the following models.

          UPS2000-A-1KTTS (firmware: UPS2000A,	V2R1C1SPC40, P1.0-D1.0)

          UPS2000-A-1KTTS (firmware: UPS2000A,	V2R1C1SPC50, P1.0-D1.0)

          UPS2000-A-2KTTS (firmware: UPS2000A,	V2R1C1SPC50, P1.0-D1.0)

          UPS2000-G-1KRTS (firmware: UPS2000A,	V2R1C1SPC40, P1.0-D1.0)

          UPS2000-G-1KRTS (firmware: UPS2000G,	V2R1C1SPC50, P1.0-D1.0)

          UPS2000-G-3KRTS (firmware: UPS2000A,	V2R1C1SPC40, P1.0-D1.0)

          UPS2000-G-3KRTS (firmware: UPS2000G,	V2R1C1SPC50, P1.0-D1.0)

          UPS2000-G-3KRTL (firmware: UPS2000A,	V2R1C1SPC40, P1.0-D1.0)

       If your model is	not in the list, we encourage you to report successful
       or unsuccessful results to the bug tracker or the mailing list. Make
       sure to include the full	model number of	your UPS manually in your
       report, because many units only report themselves as "UPS2000-A"
       regardless of their models, including the G series.

       As of 2022, there is also a new hardware	variant	with a WCH CH341
       USB-to-serial chip instead of a MaxLinear/Exar RX21V1410	chip and
       reports itself as "UPS2000G". Driver support has	been added since
       v0.03.

       huawei-ups2000 uses the libmodbus project, for Modbus implementation.

CABLING
       The UPS has a USB port and a RS-232 port. Both are supported, but on
       most UPS	models,	USB is only usable on Linux 5.12 and later, via	the
       xr_serial kernel	module.	But for	the newer hardware variant with	a WCH
       CH341 chip, it should have better compatibility via the ch341 kernel
       module. See subsection USB for details. On the other hand, RS-232 is
       always supported	on all operating systems.

       Only one	port can be used at a time. When USB is	used, RS-232 should be
       unplugged from the UPS, and vice	versa. Further,	optional adapter
       cards, such as RS-485 or	SNMP, are not supported. They should be
       removed from the	UPS.

       Because the UPS port can	be unresponsive	under certain circumstances,
       it's recommended	to power cycle your UPS	after making a cabling change,
       especially after	changing the port type.	That is, turn off the UPS
       power output via	the front panel, then unplug the UPS from line power
       input. Wait for the LCD screen to go black. Finally reconnect line
       power and restart your UPS.

   USB
       The USB port on the UPS2000 is originally powered by a MaxLinear/Exar
       RX21V1410 USB-to-serial converter chip, it's only supported by Linux
       5.12 or newer, via the xr_serial	kernel module. Its lsusb report	is:

	   04e2:1410 Exar Corp.	XR21V1410 USB-UART IC

       However,	a recent hardware variant switched to the WCH CH341 serial
       chip:

	   1a86:5523 QinHeng Electronics CH341 in serial mode, usb to serial port converter

       If your unit has	a WCH CH341 chip (likely only found in units made
       after 2022), when the UPS2000 is	connected via USB, you should see the
       following logs in dmesg.

	   ch341 2-1.2:1.0: ch341-uart converter detected
	   usb 2-1.2: ch341-uart converter now attached	to ttyUSB0

       If so, you should be able to proceed without worrying about kernel
       compatibility. This CH341 chip has been around for a decade and should
       be compatible with your system.

       On the other hand, if your unit has a MaxLinear/Exar XR21V1410 chip,
       like most users do, when	the UPS2000 is connected via USB to a
       supported Linux system, you should see the following logs in dmesg.

	   xr_serial 1-1.2:1.1:	xr_serial converter detected
	   usb 1-1.2: xr_serial	converter now attached to ttyUSB0

       The driver must be xr_serial. If	your system doesn't have the necessary
       device driver, you will get this	message	instead:

	   cdc_acm 1-1.2:1.0: ttyACM0: USB ACM device

       The generic driver cdc_acm is incompatible and cannot be	used. You
       should upgrade your Linux kernel	to Linux 5.12 or newer.

	   Warning

	   On an unsupported system, the XR21V1410 USB device can still	be
	   recognized as a USB ACM device, but communication is	impossible,
	   please don't	waste your time	on cdc_acm.

       If you're already running on Linux 5.12 or newer	kernels, but still
       cannot see the xr_serial	driver,	it means the driver is not enabled in
       your kernel build. If you're a regular user, you	should file a bug
       report to your Linux distro maintainers and ask them to enable
       xr_serial (kernel option	CONFIG_USB_SERIAL_XR).

       When upgrading the Linux	kernel isn't an	option,	or when	you are	using
       another operating system	(e.g. FreeBSD),	RS-232 must be used. Even for
       CH341 users, one	can try	this option if USB somehow refuses to work.

   RS-232
       RS-232 is supported on all operating systems, either via	a built-in
       serial port on your computer, or	by using an external USB-to-RS-232
       converter. If you plan to use an	USB-to-RS-232 converter, make sure
       it's supported by your operating	system.

INSTALLATION
       This driver may be not built by default.	You can	build it by installing
       libmodbus (with development packages) and running

	   configure --with-serial=yes --with-modbus=yes

       You also	need to	give proper (R/W) permissions on the local serial
       device file to allow the	NUT driver run-time user to access it. This
       may need	additional setup for start-up scripting, udev or upower	rules,
       to apply	the rights on every boot -- especially if your device nodes
       are tracked by a	virtual	filesystem.

       For example, a USB-to-serial converter can be identified	as
       /dev/ttyACM0 or /dev/ttyUSB0 on Linux, or /dev/ttyU0 on FreeBSD (note
       the capital "U"). A built-in serial port	can be identified as
       /dev/ttyS0 on Linux or one of /dev/cua* names on	FreeBSD.

EXTRA ARGUMENTS
       This driver supports the	following optional settings in the ups.conf(5)
       file:

       offdelay=value
	   Time	to wait	before shutting	down the UPS (seconds),	acceptable
	   range is 6 seconds (0.1 minutes) to 5940 seconds (99	minutes).
	   Defaults to 60 seconds. Must	be a multiple of 6 seconds. To ensure
	   your	system has adequate time to shut down after a power failure,
	   it's	highly recommended to adjust offdelay.

       rebootdelay=value
	   Time	to wait	before rebooting the UPS (seconds), acceptable range
	   is 6	seconds	(0.1 minutes) to 5940 seconds (99 minutes). Defaults
	   to 60 seconds. Must be a multiple of	6 seconds. This	is used	by the
	   shutdown.reboot.graceful instant command. If	you've adjusted
	   offdelay, you should	also adjust rebootdelay.

       ondelay=value
	   Time	to wait	before switching on the	UPS (seconds), acceptable
	   range is 60 seconds (1 minutes) to 5940 seconds (99 minutes).
	   Defaults to 60 seconds. Must	be a multiple of 60 seconds (not 6
	   seconds). You don't need to adjust this delay unless	you have
	   special requirements.

	   Note

	   Due to hardware limitation, in this driver, ondelay is respected
	   only	when line power	is available. If a power failure has occurred,
	   the UPS and the load	is always immediately switched on, as soon (or
	   as late) as line power is restored.

INSTANT	COMMANDS
       This driver supports some instant commands (see upscmd(8)):

       shutdown.stayoff
	   After an offdelay, turn off the load. When line power is back,
	   remain off.

       shutdown.return
	   After an offdelay, turn off the load. When line power is back, turn
	   on the load,	possibly after an ondelay.

	   Note

	   Normally, the load is turned	on as soon as line power is back. But
	   if line power is never lost,	or has came back unexpectedly in the
	   middle of an	ongoing	shutdown (an undesirable "power	race"
	   condition that many entry-level products on the market fail to
	   recover from), the load is turned on	after an ondelay. Thus,
	   UPS2000 is unaffected by a power race, the load is guaranteed to
	   always restart.

       shutdown.reboot
	   Like	shutdown.return, except	that the load is turned	off
	   immediately (6 seconds in this implementation).

       shutdown.reboot.graceful
	   Like	shutdown.return, except	that the load is turned	off after a
	   rebootdelay,	not an offdelay.

       beeper.enable
	   Enable the UPS beeper.

       beeper.disable
	   Disable the UPS beeper.

       beeper.toggle
	   Toggle the UPS beeper.

       bypass.start
	   Put the UPS in bypass mode. Use with	caution. It exposes your
	   equipment to	unregulated line power and provides no protection from
	   power failures. Also, the UPS may shut down whenever	the bypass
	   input voltage is out	of the nominal range. As a warning, the	UPS
	   beeps once every 10 seconds in bypass mode.

	   Note

	   The driver has a basic foolproof mechanism. If the bypass input is
	   already abnormal due	to a power failure, the	driver refuses to
	   enter bypass	mode by	aborting the command and logging an error.
	   However, it offers no protection after the UPS has entered (or in
	   the middle of entering) bypass mode.	Thus, again, use with caution.

       bypass.stop
	   Put the UPS out of bypass mode.

       load.on
	   Turn	on the load immediately.

       load.off
	   Turn	off the	load immediately. Use with caution, everything on the
	   UPS will lost power.

       test.battery.start.quick
	   Perform a short battery test.

       test.battery.start.deep
	   Perform a long battery test.

       test.battery.stop
	   Stop	a running battery test.

VARIABLES
       This driver supports some writable runtime variables (see upsrw(8)):

       ups.beeper.status
	   Enable or disable the UPS beeper, disabled or enabled.

	   Note

	   The beeper can only be disabled completely, it cannot be temporally
	   muted until the next	alarm, but the option muted is also accepted
	   for convenience, muted is treated as	an alias of disabled.

       ups.delay.shutdown
	   Seconds to wait after shutdown with delay command. It's the runtime
	   equivalent of offdelay. See description of offdelay.

       ups.delay.reboot
	   Seconds to wait before rebooting the	UPS, it's the runtime
	   equivalent of rebootdelay. See description of rebootdelay.

       ups.delay.start
	   Seconds to wait before restarting the load, it's the	runtime
	   equivalent of ondelay. See description of ondelay.

KNOWN ISSUES AND BUGS
   Battery status has a	non-fatal read failure
       It's usually harmless and can be	safely ignored.	It's only logged for
       informative purposes (LOG_INFO),	not as a warning or error.

   Data	stale
       Under certain circumstances, some registers can return invalid values
       and trigger a "data stale" error. Once a	data stale error has occurred,
       you should see error messages similar to	the example below in the
       system log.

	   huawei-ups2000: register 2002 has invalid value a000,
	   upsd: Data for UPS [huawei] is stale	- check	driver
	   upsd: UPS [huawei] data is no longer	stale

       So far all known	problems have been fixed by the	author,	but an unknown
       one cannot be ruled out.	If you have encountered	"data stale" problems
       during normal uses, please file a bug report with full logs attached.

       Before troubleshooting or reporting a problem, it's important to	check
       your dmesg log for USB connect and disconnect events to avoid wasting
       time on the NUT driver when the actual problem is USB.

       For example, if someone yanks the cable out of the USB port, or if a
       new USB device is plugged into a	USB host/hub that is struggling	to
       power its ports (common on single-board computers like Raspberry	Pi),
       or if you have flaky cabling or EMI noise, due to all these and similar
       reasons the serial converter can	get disconnected from USB, at least
       briefly.

       This creates a permanent	data stale situation, and the driver must be
       restarted (plugging the USB back	won't fix it, since the	driver is
       still using the nonexistent serial device, if the system	kernel
       initializes a new device	driver instance	internally).

       These USB problems usually have nothing to do with NUT. If it's the
       case, you should	solve the underlying USB problem -- check the cable,
       check the converter, try	a powered USB hub, try a full-speed USB
       isolator, etc.

   Serial port becomes unresponsive
       Some malformed commands are known to lock up the	serial port (including
       USB, which is a USB-to-serial device). Upon receiving them, UPS2000
       stops all serial	communications.	The result is a	completely
       unresponsive UPS, regardless of what you	do -- restarting NUT,
       rebooting the computer -- can not restore connectivity, as if someone
       has unplugged the RS-232	cable.

       To recover, simply power	cycle the UPS: Turn off	the UPS	output via the
       front panel, then unplug	the UPS	from line power. Wait for the LCD
       front screen to go black. Finally reconnect line	power and restart your
       UPS.

       That being said,	a serial port lockup is	unlikely to happen. To our
       best knowledge, this driver never sends malformed commands to the UPS
       (it was only a problem during early development). Furthermore, due to a
       CRC checksum, they're unlikely to be accidentally generated.

       Still, we recommend to power cycle your UPS after making	a cabling
       change, especially after	changing from RS-485/USB to RS-232, just to
       ensure the UPS selects the correct communication	interface. Also, if
       you have	discovered a reproducible serial port lockup problem, it can
       be a previously unknown bug, so please make sure	to file	a bug report.

   USB chip (MaxLinear/Exar RX21V1410) is unsupported
       As previously stated, only RS-232 is supported on all systems. On most
       UPS units, the USB chip RX21V1410 is used, and it requires a
       device-specific driver xr_serial, which is only available on Linux 5.12
       and newer kernels.

       On an unsupported system, the USB device	can still be recognized	as a
       USB ACM device, but in reality, communication is	impossible. It can
       only be fixed by	implementing a driver for your system, nothing can be
       done within NUT.	Please use the RS-232 port instead.

       Alternatively, if your unit has a WCH CH341 chip	(likely	only found in
       units made after	2022), it should have better compatibility.

       See the previous	section	Cabling	for more information.

       Finally,	in the unlike scenario that you	are using NUT on Microsoft
       Windows,	you should be able to install the USB device driver following
       the steps in the	Huawei UPS2000 (1 kVA-3	kVA) Modbus Protocol
       Development Guide.

AUTHOR
       Yifeng Li <tomli@tomli.me>

SEE ALSO
   The core driver:
       nutupsdrv(8)

   Internet resources:
          The NUT (Network UPS	Tools) home page:
	   https://www.networkupstools.org/

          Huawei UPS2000-A (1 kVA-3 kVA) User Manual:
	   https://support.huawei.com/enterprise/en/doc/EDOC1000084260

          Huawei UPS2000 (1 kVA-3 kVA)	Modbus Protocol	Development Guide:
	   https://support.huawei.com/enterprise/en/doc/EDOC1000110696

          libmodbus home page:	http://libmodbus.org

Network	UPS Tools 2.8.2.	  04/17/2025		     HUAWEI_UPS2000(8)