MGE-UTALK(8)			  NUT Manual			  MGE-UTALK(8)

NAME
       mge-utalk - Driver for MGE UPS SYSTEMS UTalk protocol equipment

SYNOPSIS
       mge-utalk -h

       mge-utalk -a UPS_NAME [OPTIONS]

	   Note

	   This	man page only documents	the hardware-specific features of the
	   mge-utalk driver. For information about the core driver, see
	   nutupsdrv(8).

SUPPORTED HARDWARE
       mge-utalk supports the following	legacy units, using the	MGE UTalk
       protocol:

          Pulsar ESV+

          Pulsar ES+

          Pulsar EL

          Pulsar EX

          Pulsar EXtreme

          Comet EXtreme

          Comet (Utalk	Serial Card, ref 66060)

          Galaxy (Utalk Serial	Card, ref 66060)

       This driver also	support	some newer models with backward	UTalk
       compatibility, such as Pulsar Evolution and Pulsar EXtreme C. As	these
       models also support the SHUT protocol, prefer mge-shut(8) for serial
       communication, or use the USB port, if available, with the usbhid-
       ups(8)] driver.

EXTRA ARGUMENTS
       This driver supports the	following optional settings in the
       ups.conf(5):

       lowbatt=num
	   Set the low battery warning threshold at which shutdown is
	   initiated by	upsmon(8).

	   The factory default value is	30 (in percent), and can be settable
	   depending on	the exact model.

       offdelay=num
	   Set the timer before	the UPS	is turned off after the	kill power
	   command is sent (via	the -k switch).

	   The default value is	20 (in seconds).

       ondelay=num
	   Set the delay before	the UPS	is turned on, after the	power returns.

	   The default value is	1 (in minutes).

       oldmac
	   Set this flag if you	are running Linux on an	Oldworld Macintosh box
	   (all	beige Apple Macintosh).	This might also	be needed for other
	   OSs (like *BSD) running on PowerMac.

KNOWN ISSUES
   Repetitive timeout and staleness
       Older models, such as ES/ESV ones, might	report repetitive "data	stale"
       errors. This is due to the fact that these models don't support too
       much polling. To	solve this problem, add	pollinterval=20	in ups.conf,
       and change the value of MAXAGE to 25 in upsd.conf, and DEADTIME to 25
       in upsmon.conf.

AUTHORS
          Hans	Ekkehard Plesser

          Arnaud Quette

          Martin Loyer

          Patrick Agrain

          Nicholas Reilly

          Dave	Abbott

          Marek Kralewski

SEE ALSO
   The core driver
       nutupsdrv(8)

   Internet resources
       The NUT (Network	UPS Tools) home	page: https://www.networkupstools.org/

Network	UPS Tools 2.8.2.	  04/17/2025			  MGE-UTALK(8)