NUT(7)				  NUT Manual				NUT(7)

NAME
       nut - Overview of the Network UPS Tools (NUT)

DESCRIPTION
       The Network UPS Tools (NUT) project provides a free and open source
       tool kit	for monitoring and managing different types of power
       distribution devices, first released under such name in 1999 and
       following up from a few earlier projects. Since then, NUT has expanded
       to cover	thousands of devices from hundreds of vendors, and to handle
       various device types (UPS, ePDU,	ATS/STS, solar,	blade server IPMI as a
       sort of PDU for the blades, etc.) all with a consistent API and data
       model, which has	since been published as	The "UPS management protocol",
       Informational RFC 9271.

       While the project is in active development to support ever newer
       devices and their firmwares, as well as operating system	releases, one
       of the internally recognized goals is to	remain compatible with the
       systems NUT could have been once	deployed on: even if vendors of	those
       boxes and operating systems no longer exist, the	venerable hardware
       deserves	to be still protected with new UPS devices.

       Although	the original development involved POSIX-compliant operating
       systems,	over time NUT for Windows support was also implemented
       (however	as of NUT release v2.8.3, it remains not 100% complete)	so it
       is possible to run the whole server and client stack as native Windows
       programs.

       Most operating systems deliver NUT as packages built from a certain
       release,	which for the project is just a	better-tested snapshot of
       on-going	development. Some OS distribution maintainers pick fixes from
       later releases to update	their software packages	while nominally
       remaining on the	same base line version that the	distribution's major
       release originally went with. This allows to balance delivering stable
       programs	with well-known	qualities and minimal downsides	for a long
       stretch of time,	but misses out on new capabilities, features (and yes,
       new bugs) which the on-going development	regularly adds to the current
       code base du-jour.

       As such,	NUT community support for releases (or any other non-current
       code) is	generally limited to suggestions based on experience, but any
       fixes happen on the main	development branch (there are no
       release-tracking	branches to port such solutions	into), and custom
       builds of NUT would be required to apply	them in	an end-user
       environment. This workflow is highly automated in the project code base
       (its recipes and	scripts), and the packaged dependencies	or toolkits
       needed for a build are documented for numerous platforms	(see links at
       the end of this page).

       Thanks to this, the NUT project is also a wider open-source community
       leader and reference in the area	of build recipes and testing
       automation for low-level	multi-platform Autotools/C/C++ projects	in
       general.

   NUT Architecture
       The project follows a multi-tiered architecture which may seem a	bit
       complex,	but allows for flexibility with	very different real-life
       setups to handle. In practice, this involves numerous programs (and
       their configuration files) running on the same or different systems
       (the "network" part in the name).

       Many deployment scenarios are explored in the famous NUT	Configuration
       Examples	book maintained	by Roger Price.

       NUT Drivers

	   The lowest tier comprises NUT drivers, which	are programs that can
	   talk	a particular protocol over certain media. Some protocols
	   follow an industry standard (like USB HID or	SNMP), or are dialects
	   of a	de-facto standard (like	the originally Megatec "Q*" family of
	   protocols used by many other	vendors), but many others are
	   vendor-specific. Some devices support several media connection
	   types (e.g. Serial and/or USB ports,	and/or SNMP for	networked
	   management),	so there may be	several	suitable NUT drivers to	choose
	   from.

	   The NUT drivers are responsible for translation between NUT
	   standard data point or instant command names	and whatever strings
	   need	to be pulled for that particular device. The data is exposed
	   to other programs on	the same machine following the NUT
	   Driver/Server Socket	Protocol, which	relies on operating system
	   access controls for the UNIX	local socket file or a Windows named
	   pipe.

	   For each monitored power distribution device, a NUT driver instance
	   should be running on	a machine that has a communication link	to
	   that	device.

	       Note

	       There is	currently no support for "multiplexing"	information or
	       commands	for devices with multiple-media/multiple-driver
	       access, e.g. to gain redundant connection or a better data
	       collection than any one driver provides.	For some devices it
	       may be possible to run several drivers independently (probably
	       for your	monitoring system to cherry-pick data points from one
	       driver or another), while others	might only enable any one link
	       exclusively.

       NUT Data	Server

	   A NUT Data Server (upsd(8)) represents one or more NUT drivers that
	   run on the same machine as itself, to provide networked access to
	   their data or pass around the instant command requests and replies.

	   On one side the data	server connects	to one or more UNIX local
	   socket files	or Windows named pipes (one for	each running driver),
	   and on another side it listens on the TCP/IP	network	(port 3493 by
	   default) to communicate with	local or remote	client programs. It is
	   also	responsible for	communication security for driver access,
	   whether by defining the NUT user account names and assigned
	   protocol access permissions (for value-setting or commands; read
	   access is anonymous), or by handling	the TLS/SSL part where
	   enabled.

       NUT Clients

	   Practical work visible to end-users is done by a multitude of NUT
	   clients, many of which are delivered	by the project itself and more
	   are created and maintained by the community at large. Some standard
	   clients of note include:

	      upsmon(8) is a daemon to	monitor	primarily the states of	UPSes
	       (as opposed to other device types that NUT can handle) which
	       power some power	source units of	this particular	system,	and
	       based on	how many PSUs are required for the system to run --
	       initiates a local shutdown when too many	UPSes are not in a
	       healthy condition. Instances of this client allow a single UPS
	       powering	a whole	rack or	desk of	computers to be	seen by	each
	       of them (through	a data server running on one of	them, on a
	       machine actually	connected to the UPS --	the "primary" system).

		   Note
		   The upsmon client typically splits into two processes: an
		   unprivileged	one running with credentials of	its
		   RUN_AS_USER configured in the upsmon.conf(5)	file (or a
		   built-in/packaged default like nut, ups, monuser or nobody)
		   which does most of the work (including notification scripts
		   called via NOTIFYCMD	setting), and the part which remains
		   owned by root to initiate the system	shutdown by calling
		   SHUTDOWNCMD when/if the time	comes.
	       NUT deployments which desire higher-fidelity control (e.g.
	       different systems shutting down after different time spent on
	       battery)	often couple the upsmon(8) with	upssched(8) as their
	       NOTIFYCMD handler.

	       The upsmon primary system waits for secondary systems to
	       disconnect as part of their shut	down, and is usually also
	       responsible for commanding the managed UPS to shut itself down
	       and power up when the "wall power" returns (or to reset the
	       load if it is already back), subject to UPS hardware
	       capabilities. Most client integrations also stall the ultimate
	       reboot/power-off	of their machine, if its shut down was
	       triggered by upsmon, and	reboot after a long delay (if the
	       machine is still	alive).	This combined approach allows to avoid
	       the "power race condition", when	systems	would otherwise	remain
	       shut down indefinitely (until someone comes and reboots them)
	       just because external power returned when the shut down spree
	       had already started.

	      upsc(8) is a command-line client	for anonymous read-only
	       access, used to list devices served by a	NUT data server, or to
	       query data points reported by a particular device.

	      NUT-Monitor(8) is a GUI client for read-only or read-write
	       access.

	      A suite of CGI clients can run on a web server like Apache or
	       nginx to	provide	a simple HTML interface	to your	devices.

	   Many	monitoring systems integrate with NUT (and through it -- with
	   a varied assortment of power	devices), using	either simple clients
	   like	upsc or	upslog,	or libraries and bindings provided by the
	   project itself (e.g.	C, C++,	Python,	Java in	a nearby repository)
	   or by third-party efforts (e.g. Perl, Go, C#, REST API).

       NUT Drivers during shutdown

	   Arguably another layer in this three-layer stack is a separate role
	   for the NUT Driver programs on the upsmon(8)	primary	system as
	   mentioned above: actually telling the UPS to	turn off or
	   power-cycle as part of your computer's emergency shut down.

	   While the long-running services for the NUT drivers,	data server
	   and clients are stopped as part of common OS	shutdown, there	may be
	   an "endgame"	integration such as high-numbered SysV init scripts
	   (e.g. /etc/rc0.d/K99nut) or the systemd shutdown hook facility, or
	   even	something built	into the initrd	or similar RAM disk image that
	   originally launched the end-user visible OS and regains control
	   when	the OS says it is done.	Please note that not all operating
	   systems offer ways of such integration, and may resort to other
	   solutions (perhaps calling such logic from the stop method of
	   upsmon init script or service definition).

	   Either way, this integration	has the	effect of detecting that the
	   currently processed shutdown	is due to an upsmon FSD	activity (e.g.
	   that	the flag file specified	by POWERDOWNFLAG configuration option
	   in upsmon.conf(5) exists and	is valid), and launches	the NUT	driver
	   program(s) again to connect to the UPS(es) that this	system is a
	   primary manager of (and has possibly	out-of-band connections	to),
	   just	to send	them the requested command and exit.

	   For an example of such end-game integration please see the
	   nutshutdown script if available in your packaged distribution, or
	   its sources at
	   https://github.com/networkupstools/nut/blob/master/scripts/systemd/nutshutdown.in
	   which also implements a solution to avoid the "power	race
	   condition" (for operating systems that do not limit the duration of
	   shutdown activity).

   NUT Run-time	Nuances
       For many	more notes, please see the Frequently Asked Questions document
       in NUT sources or on the	web site. A copy may be	delivered by your
       packaging.

       "File or	directory not found" messages

	   When	NUT daemon programs start, they	check for existence of certain
	   files they would create themselves (PID files, local	sockets, etc.)
	   and report when such	file does not exist. Similarly,	some programs
	   try to signal an earlier instance (if the PID is known) and would
	   report if that failed.

	   While this does look	scary and confusing to people who use NUT for
	   the first time and it greets	them with what looks like error
	   messages (we	did work on improving the wording during the NUT
	   v2.8.x release lineage due to frequent questions), these messages
	   are in fact just a troubleshooting aspect that is useful at that
	   point in program life cycle:	if you expect "other" program
	   instances to	be running when	they are not seen, this	message	helps
	   catch the error. If this is a first run, so no "other" program
	   instance's artifacts	should be there, the message says just that.
	   If your program starts and sees an older instance already running,
	   further behavior depends on the situation (e.g. did you start a
	   copy	to signal the already running daemon with some command?	did
	   you start a new copy	and so any old one is assumed stuck and	should
	   be terminated automatically?)

	   The "directory" part	of the wording,	which may be present in	these
	   messages, comes from	the standard system library. It	does not mean
	   you should blindly create a directory (or any other object) for the
	   file	names listed in	such reports.

	   That	said, NUT does use directories (known in code and the
	   configure script options as --with-pidpath, --with-altpidpath and
	   --with-statepath) which should be created and assigned certain
	   permissions each (the latter	two may	overlap). Generally this is
	   done	either by packaging, or	by manual steps	according to
	   documentation when building NUT from	sources. On some platforms
	   (e.g. Linux with systemd and	its systemd-tmpfiles subsystem)	they
	   may be maintained at	run-time by configuration files	delivered to
	   the system.

	   The message can also	be seen	from upsmon(8) being unable to
	   populate the	POWERDOWNFLAG if the location it points	to
	   (/etc/killpower by default) does not	exist or is read-only, or from
	   a late shutdown integration script like the nutshutdown hook	if
	   that	location was un-mounted	by the time it runs. It	is recommended
	   to store that file on a volatile file system	(under /run on most
	   modern distributions; typically the pidpath is located there	too),
	   which remains until reboot and disappears during reboot.

       User/Group Accounts

	   Generally NUT daemon	programs avoid running as a highly-privileged
	   root	account	(on POSIX platforms), and drop privileges to run as
	   the configured user and group accounts such as nut:nut.

	      One notable exception is	the upsmon(8) daemon which splits into
	       a root-owned process which may trigger the OS shutdown routine,
	       and an unprivileged process which does everything else.

       File system permissions

	   When	using NUT drivers with local communications media (USB or
	   Serial ports), you must ensure that the unprivileged	run-time
	   account like	nut:nut	is allowed access to those device file system
	   nodes. On many platforms this can be	automated with subsystems like
	   udev, devd, hotplug,	upower;	on others (older ones) you may have to
	   chmod/chown/chgrp particular	devfs nodes (whether on	the persistent
	   filesystem, or using	an init-script for volatile implementations).

	   Note	that there are several run-time	locations for data and socket
	   files of NUT's privileged and unprivileged programs,	and for
	   configuration files.	Access to these	directories and	individual
	   files should	be secured according to	NUT documentation; NUT daemons
	   will	warn about lax permissions in their syslog or console
	   messages. Generally,	root:nut and 0640 permissions are correct for
	   most	of the files (so the run-time NUT programs may only read them
	   but can not rewrite them, not even if there happens to be an
	   exploitable code problem discovered in them over time).

	   It is also important	to note	that (except for upslog(8)) no NUT
	   daemons leave log files on their own: they send syslog messages, or
	   write to stdout/stderr, and either or both of these streams can be
	   saved to disk by the	OS service integration (or a redirection from
	   an init-script).

       NUT Drivers as Service instances

	   Starting with NUT v2.8.0, on	systems	with service management
	   frameworks (like Linux systemd or Solaris/illumos SMF) you may be
	   even	inadvertently using the	nut-driver-enumerator(8) (also known
	   as "NDE") facility. This is a script, which may be also called
	   automatically (via packaging	on supported platforms)	at start-up or
	   may be running continuously as a service, to	process	the
	   ups.conf(5) file and	maintain the service units (with their
	   dependencies) for each driver section separately.

	   This	sometimes raises eyebrows when end-users try to	manually start
	   a NUT driver	program	(either	directly or using upsdrvctl(8) tool),
	   and this either fails (because the device is	already	busy) or gets
	   to conflict with the	copy of	the driver running as a	service
	   instance, and they begin to terminate each other.

       Configuring NUT Drivers

	   To get started with the NUT server system, you should populate the
	   ups.conf(5) file with a section per device, which informs both the
	   respective drivers, and tools like service-aware upsdrvsvcctl(8)
	   and nut-driver-enumerator(8)	or the legacy upsdrvctl(8), and	the
	   upsd(8) data	server,	to name	a few.

	   In many typical cases, the nut-scanner(8) tool can get you started
	   by discovering supported USB, Serial, SNMP, NetXML, IPMI devices,
	   or remote NUT deployments using Avahi mDNS or the good old
	   port-knocking scan. This tool would propose a complete section
	   content that	you can	copy-paste into	your ups.conf file (possibly
	   review and adapt the	contents first,	to e.g.	add a description
	   meaningful to you like "UPS in garage", etc.)

       Other configuration files

	   NUT sample configuration files (packaged or seen in sources under
	   https://github.com/networkupstools/nut/tree/master/conf directory)
	   start with a	heading	comment	about the minimal set of their
	   required options. Note that many of these files can contain
	   credentials (either for NUT roles, or for networked power devices
	   as part of their NUT	driver section configuration) and so these
	   files and any of their backup copies	should be secured accordingly.

	   The nut.conf(5) may be used by init-scripts or other	system
	   integration code (it	notably	contains the MODE setting to choose
	   which profile of NUT	services to start or not on this particular
	   system).

	   On the NUT server you would need at least minimally configured:
	   ups.conf(5),	upsd.conf(5), upsd.users(5).

	   On the majority of NUT clients (meaning each	system monitoring the
	   UPS state so	it knows when to trigger its local shutdown), you
	   would need upsmon.conf(5) and depending on your setup, may need a
	   custom NOTIFYCMD or SHUTDOWNCMD (if you script something complex),
	   and/or upssched.conf(5) and a custom	CMDSCRIPT for it.

	   For NUT CGI clients several files may need to be adapted and	placed
	   into	certain	directories according to their documentation:
	   hosts.conf(5) and upsset.conf(5) for	configuration, and
	   upsstats-single.html	and upsstats.html for HTML UI templates.

	   Other clients, whether delivered by NUT project (NUT-Monitor(8)
	   GUI)	or co-located (WMNut) or third-party (see
	   https://networkupstools.org/projects.html) would probably support
	   saving their	settings or "favorites". Do not	forget to secure
	   access to those files and their copies as well.

USER MANUAL PAGES
	   Note

	   This	build of NUT was configured to deliver only manual pages for
	   programs that were actually built. For more information about the
	   ecosystem please see	the NUT	website	listing	at
	   https://networkupstools.org/docs/man/index.html or the sources of
	   these pages at
	   https://github.com/networkupstools/nut/tree/master/docs/man

   Configuration files
          nut.conf(5)

          ups.conf(5)

          upsd.conf(5)

          upsd.users(5)

          upsmon.conf(5)

          upssched.conf(5)

          hosts.conf(5)

          upsset.conf(5)

          upsstats.html(5)

   Daemons
          upsd(8)

          upsmon(8)

          upssched(8)

          upslog(8)

   Clients commands
          upsc(8)

          upscmd(8)

          upsrw(8)

          NUT-Monitor(8)

   Configuration commands
          nutconf(8)

          nut-scanner(8)

   CGI programs
          upsimage.cgi(8)

          upsset.cgi(8)

          upsstats.cgi(8)

   Platform management
       Windows

	      nut.exe(8)

   Driver control
          upsdrvctl(8)

   Drivers
          nutupsdrv(8)

          adelsystem_cbi(8)

          al175(8)

          apc_modbus(8)

          apcsmart-old(8)

          apcsmart(8)

          apcupsd-ups(8)

          bcmxcp(8)

          bcmxcp_usb(8)

          belkin(8)

          belkinunv(8)

          bestfcom(8)

          bestfortress(8)

          bestuferrups(8)

          bestups(8)

          bicker_ser(8)

          blazer-common(8)

          blazer_ser(8)

          blazer_usb(8)

          clone-outlet(8)

          clone(8)

          dummy-ups(8)

          etapro(8)

          everups(8)

          failover(8)

          gamatronic(8)

          generic_modbus(8)

          genericups(8)

          huawei-ups2000(8)

          isbmex(8)

          ivtscd(8)

          liebert-esp2(8)

          liebert-gxe(8)

          liebert(8)

          masterguard(8)

          metasys(8)

          mge-shut(8)

          mge-utalk(8)

          microdowell(8)

          microsol-apc(8)

          netxml-ups(8)

          nhs_ser(8)

          nut_usb_addvars(8)

          nutdrv_atcl_usb(8)

          nutdrv_hashx(8)

          nutdrv_qx(8)

          nutdrv_siemens_sitop(8)

          oneac(8)

          optiups(8)

          phoenixcontact_modbus(8)

          powercom(8)

          powerman-pdu(8)

          powerpanel(8)

          powervar_cx_ser(8)

          powervar_cx_usb(8)

          rhino(8)

          richcomm_usb(8)

          riello_ser(8)

          riello_usb(8)

          safenet(8)

          sms_ser(8)

          snmp-ups(8)

          socomec_jbus(8)

          solis(8)

          tripplite(8)

          tripplite_usb(8)

          tripplitesu(8)

          upscode2(8)

          usbhid-ups(8)

          ve-direct(8)

          victronups(8)

DEVELOPER MANUAL PAGES
          libupsclient-config(1)

          nut-recorder(8)

          skel(8)

          sockdebug(8)

   Client library
          libnutclient(3)

          libnutclient_commands(3)

          libnutclient_devices(3)

          libnutclient_general(3)

          libnutclient_misc(3)

          libnutclient_tcp(3)

          libnutclient_variables(3)

          upsclient(3)

          upscli_add_host_cert(3)

          upscli_cleanup(3)

          upscli_connect(3)

          upscli_tryconnect(3)

          upscli_disconnect(3)

          upscli_fd(3)

          upscli_get(3)

          upscli_init(3)

          upscli_set_default_connect_timeout(3)

          upscli_get_default_connect_timeout(3)

          upscli_init_default_connect_timeout(3)

          upscli_list_next(3)

          upscli_list_start(3)

          upscli_readline(3)

          upscli_sendline(3)

          upscli_splitaddr(3)

          upscli_splitname(3)

          upscli_ssl(3)

          upscli_strerror(3)

          upscli_upserror(3)

          upscli_str_add_unique_token(3)

          upscli_str_contains_token(3)

   Device discovery library
          nutscan(3)

          nutscan_add_device_to_device(3)

          nutscan_add_ip_range(3)

          nutscan_add_option_to_device(3)

          nutscan_cidr_to_ip(3)

          nutscan_display_parsable(3)

          nutscan_display_sanity_check(3)

          nutscan_display_sanity_check_serial(3)

          nutscan_display_ups_conf(3)

          nutscan_display_ups_conf_with_sanity_check(3)

          nutscan_free_device(3)

          nutscan_free_ip_ranges(3)

          nutscan_get_serial_ports_list(3)

          nutscan_init(3)

          nutscan_init_ip_ranges(3)

          nutscan_ip_ranges_iter_inc(3)

          nutscan_ip_ranges_iter_init(3)

          nutscan_new_device(3)

          nutscan_scan_avahi(3)

          nutscan_scan_eaton_serial(3)

          nutscan_scan_ipmi(3)

          nutscan_scan_nut(3)

          nutscan_scan_nut_simulation(3)

          nutscan_scan_snmp(3)

          nutscan_scan_usb(3)

          nutscan_scan_xml_http_range(3)

          nutscan_stringify_ip_ranges(3)

       :!included-skip-title:

INTERNET RESOURCES
          The NUT (Network UPS	Tools) home page:
	   https://www.networkupstools.org/ and	specifically the NUT
	   Documentation collection with the FAQ page and several books	on
	   different aspects of	NUT usage and development, maintained as part
	   of the project code base

          The NUT Configuration Examples book,	maintained by Roger Price

          Project GitHub repository, wiki and issue tracker:
	   https://github.com/networkupstools/nut

          Commonly referenced articles	include:

	      The NUT FAQ page

	      Changing	NUT daemon debug verbosity should be your first	step
	       in any troubleshooting

	      Build prerequisites to make NUT from scratch on various
	       Operating Systems documents the packages	you might need to
	       build NUT on about a dozen operating system distributions (most
	       of those	the NUT	CI farm	tests each development iteration on)

	      Building	NUT for	in-place upgrades or non-disruptive tests
	       details how to build a newer version of NUT than	your system
	       packaging provides (as a	potential replacement of the older
	       installation), e.g. to test if some issue got resolved or if an
	       updated driver sees more	information from your device; most
	       such tests can be done without installing the new build into
	       your system (not	until you like it better than the current
	       deployment)

	      Specific	bits of	know-how and caveats regarding NUT for Windows

          Related projects

          We are on Wikipedia:
	   https://en.wikipedia.org/wiki/Network_UPS_Tools

          The "UPS management protocol", Informational	RFC 9271:
	   https://datatracker.ietf.org/doc/html/rfc9271

Network	UPS Tools 2.8.4.	  11/02/2025				NUT(7)