NAME
       optiups - Driver	for Opti-UPS (Viewsonic) UPS and Zinto D (ONLINE-USV)
       equipment

SYNOPSIS
       optiups -h

       optiups -a UPS_NAME [OPTIONS]

	   Note

	   This	man page only documents	the hardware-specific features of the
	   optiups driver. For information about the core driver, see
	   nutupsdrv(8).

SUPPORTED HARDWARE
       optiups was originally written against a	PowerES	280es in nut-0.45. It
       was revised for nut-2.0.1 and tested against a PowerES 420E. It is
       expected	to work	with at	least the PowerES, PowerPS, and	PowerVS
       models.

       This driver additionally	supports a Zinto D from	ONLINE USV-Systeme AG
       because of their	very similar commands, but it is unknown if it also
       works with other	UPS from them.

       This driver will	not work with the PowerES stock	serial cable. You will
       need to construct your own three	conductor cable:

	   UPS 6 -> PC 3
	   UPS 9 -> PC 2
	   UPS 4 -> PC 5

       The cable for Online-USV	uses pin UPS 7 (not UPS	4)  PC 5.

EXTRA ARGUMENTS
       This driver supports the	following optional settings in the ups.conf(5)
       file:

       status_only
	   Only	poll for critical status information. Without this, optiups
	   (and	all NUT	drivers) poll all sorts	of information from the	UPS
	   fairly often. It is probably	not often enough to hurt anything, so
	   this	option probably	is not very useful, unless you have a flaky
	   serial connection or	a highly loaded	machine.

       nowarn_noimp
	   Does	not print warnings when	the UPS	reports	that a variable	is not
	   implemented or not pollable.	Without	the option you will get	a
	   message sent	to your	system logs each time NUT polls	the UPS. If
	   you specify nowarn_noimp, this message will only be logged once.

       fake_lowbatt
	   This	forces the low battery flag true. Without it, if you want to
	   test	your UPS, you will have	to unplug it and wait until the
	   battery drops to a low/critical voltage level before	NUT will
	   respond and power down your system. With the	flag, NUT should power
	   down	the system soon	after you pull the plug. When you are done
	   testing, you	should remove this flag.

	   For basic shutdown configuration testing, the command upsmon	-c fsd
	   is preferred.

       powerup
	   Zinto D from	ONLINE-USV cannot be identified	when switched to
	   standby. Set	this flag to allow the driver to power-up your Zinto
	   UPS.	This will also power-up	your equipment connected to the	UPS!

BUGS
       On the 420E, ups.serial and ups.temperature are unsupported features.
       This is not a bug in NUT	or the NUT driver, just	the way	things are
       with this UPS.

AUTHORS
          Russell Kroll

          Scott Heavner

          Matthias Goebl

SEE ALSO
   The core driver:
       nutupsdrv(8)

   Internet resources:
       The NUT (Network	UPS Tools) home	page: https://www.networkupstools.org/

Network	UPS Tools 2.8.2.	  04/17/2025			    OPTIUPS(8)