POWERPANEL(8)			   NUT Manual			   POWERPANEL(8)

NAME
     powerpanel - Driver for serial PowerPanel Plus compatible UPS equipment

SYNOPSIS
     powerpanel -h

     powerpanel -a UPS_NAME [OPTIONS]

	 Note

	 This man page only documents the hardware-specific features of the pow-
	 erpanel  driver.  For	information  about  the core driver, see nutups-
	 drv(8).

SUPPORTED HARDWARE
     This driver supports CyberPower BC1200, PR2200 and many other  similar  de-
     vices,  both  for the text and binary protocols. The driver will autodetect
     which protocol is used.

     If your Cyber Power Systems UPS has a USB port, you may wish to use the us-
     bhid-ups(8) driver. The snmp-ups(8) driver supports several  network  cards
     via SNMP.

EXTRA ARGUMENTS
     This driver supports the following optional settings in ups.conf(5):

     protocol=[text,binary]
	 Override the default autodetection of the protocol.

     manufacturer=value
	 If you don't like the autodetected value, you can override this by set-
	 ting it here.

     model=value
	 Like manufacturer above.

     serial=value
	 Like manufacturer above.

     ondelay=value
	 Time  to  wait before switching on the UPS (1 - 9999 minutes, 0=indefi-
	 nite). Only available with the text protocol driver (see  Support  Sta-
	 tus).

     offdelay=value
	 Time to wait before shutting down the UPS (6 - 600 seconds). Values be-
	 low  60  seconds will be truncated to 6 seconds intervals, values above
	 60 seconds to 60 seconds intervals. Only available with the text proto-
	 col driver (see Support Status).

VARIABLES
     Depending on the type of your UPS unit, some of the following variables may
     be changed with upsrw(8). If the driver can't read a variable from the UPS,
     it will not be made available.

     input.transfer.high
	 writable: high transfer voltage point in V

     input.transfer.low
	 writable: low transfer voltage point in V

     battery.charge.low
	 writable: remaining battery charge percentage for low battery warning

     output.voltage.nominal
	 writable: nominal output voltage in V

     ups.start.battery
	 writable: allow cold start from battery

COMMANDS
     Depending on the type of your UPS unit, some of the following commands  may
     be available.

     *	 test.battery.start.quick, test.battery.stop

     *	 beeper.enable, beeper.disable, beeper.toggle

     *	 shutdown.return, shutdown.reboot, shutdown.stayoff

     On  many  devices,  these commands are unreliable, so before using them you
     must verify that these work as expected (see Shutdown Issues).

     *	 shutdown.stop

SUPPORT STATUS
     Vendor support is absent for this driver, so if you need some features that
     are currently not available, provide ample documentation on what the driver
     should sent to the UPS in order to make  this  work.  If  more  information
     would be available on the binary protocol, it would probably be possible to
     make  ondelay  and offdelay configurable. So far, nobody has taken the time
     to investigate what we should tell the UPS to make this  work,  and  Cyber-
     Power isn't willing to share this with us.

SHUTDOWN ISSUES
     If  the  shutdown.return  command on your UPS doesn't seem to work, chances
     are that your UPS is an older model. Try a couple of different settings for
     offdelay. If no value in the range 6..600 works, your  UPS  likely  doesn't
     support  this.  In  order	to get the expected behaviour, it requires shut-
     down.stayoff (when on battery) and shutdown.reboot  (when	on  mains).  The
     driver  will  automatically  fallback  to these commands if shutdown.return
     fails, and tries to detect which one should be used when called with the -k
     option (or through upsdrvctl shutdown).

     This isn't bullet-proof, however, and you should be prepared that the power
     will either not be shutdown or that it doesn't return when the power  comes
     back.  All  models  supported  by	the  binary  protocol and many supported
     through the text protocol are affected by this.

KNOWN PROBLEMS
     The CyberPower OP series don't offer direct voltage, charge, frequency  and
     temperature  readings.  Instead, they will return a binary value that needs
     conversion to the actual value.

     The exact conversion needed is unknown at the time of this  writing,  hence
     an  estimation  was  made	based  om readings from actual devices. This may
     (probably will) be off, possibly a lot. Unless you can tell  us  the  exact
     mapping  between  values  from the UPS and actual readings, don't bother to
     complain. We've done the best we  can  based  on  the  limited  information
     available. Remember, a UPS isn't a measuring instrument.

AUTHORS
     Arjen de Korte <arjen@de-korte.org>, Doug Reynolds <mav@wastegate.net>

SEE ALSO
   The core driver:
     nutupsdrv(8)

   Other drivers:
     usbhid-ups(8), snmp-ups(8)

   Internet resources:
     The NUT (Network UPS Tools) home page: https://www.networkupstools.org/

Network UPS Tools 2.8.5.	   08/04/2026			   POWERPANEL(8)