UPS.CONF(5)			   NUT Manual			     UPS.CONF(5)

NAME
     ups.conf - UPS definitions for Network UPS Tools

DESCRIPTION
     This  file  is  read by the driver controller upsdrvctl(8), the UPS drivers
     which use the common core (see nutupsdrv(8)), nut-driver-enumerator(8), and
     the NUT data server upsd(8). The file begins with	global	directives,  and
     then  each UPS has a section which contains a number of directives that set
     parameters for that UPS.

     A UPS section begins with the name of the UPS in  brackets,  and  continues
     until  the  next  UPS  name in brackets or until EOF. The name "default" is
     used internally in upsd(8), so you can't use it in this file.

     You must define the driver and port elements for each entry. Anything after
     that in a section is optional. A simple example might look like this:

	 [myups]
		 driver = blazer_ser
		 port = /dev/ttyS0
		 desc = "Web server UPS"

     A slightly more complicated version includes  some  extras  for  the  hard-
     ware-specific part of the driver:

	 [bigups]
		 driver = apcsmart
		 port = /dev/cua00
		 cable = 940-0095B
		 sdtype = 2
		 desc = "Database server UPS"

     In  this case, the apcsmart(8) driver will receive variables called "cable"
     and "sdtype" which have special meanings. See the man pages  of  your  dri-
     ver(s) to learn which variables are supported and what they do.

     Here is another example, when connecting a serial UPS on Windows:

	 [windows-ups]
		 driver = mge-shut
		 port = "\\\\.\\COM10"
		 desc = "UPS on a Windows machine"

IMPORTANT NOTES
     *	 Contents  of  this  file  should  be pure ASCII (character codes not in
	 range would be ignored with a warning message).

     *	 Balance the run-time user permissions to access the file  (and  perhaps
	 the  directory  it  is  in) for only upsd and the drivers to be able to
	 read it; write access is not needed. It is common to use chown root:nut
	 and chmod 640 to set up acceptable file permissions.

	 *   Packages (and build recipes) typically prepare one set of user  and
	     group  accounts  for  NUT. Custom builds with minimal configuration
	     might even use nobody:nogroup or similar, which is inherently inse-
	     cure.

	 *   On systems with extra security concerns, NUT drivers,  data  server
	     should  run as separate user accounts which would be members of one
	     same group for shared access to local Unix socket files and the di-
	     rectory they are in, as well for reading  ups.conf,  but  different
	     groups  for  other  configuration file access. This would need some
	     daemons  to  use  customized  user,   group,   RUN_AS_USER   and/or
	     RUN_AS_GROUP settings to override the single built-in value.

	 *   Note that the monitoring, logging, etc. clients are networked-only.
	     They do not need access to these files and directories, and can run
	     as an independent user and group altogether.

	 *   Keep  in  mind the security of also any backup copies of this file,
	     e.g. the archive files it might end up in.

GLOBAL DIRECTIVES
     chroot
	 Optional. The driver will chroot(2) to this directory	during	initial-
	 ization. This can be useful when securing systems.

     driverpath
	 Optional.  Path  name of the directory in which the UPS driver executa-
	 bles reside. If you don't specify this, the programs look in a built-in
	 default directory, which is often /usr/local/bin.

     statepath
	 Optional. Path name of the directory in which the  UPS  drivers  should
	 place	their  state  sockets  for  local  communication  with upsd data
	 server, rather than the default location that	was  compiled  into  the
	 program, which is often /var/state/ups.

	 Note  that  the  drivers  must  use  the same path as upsd, so the data
	 server would prefer this  setting  from  ups.conf  global  section,  if
	 present, over its own in upsd.conf.

	 Environment variable NUT_STATEPATH set by caller can override this set-
	 ting.

     maxstartdelay
	 Optional.  Same  as the UPS field of the same name, but this is the de-
	 fault for UPSes that don't have the field.

     maxretry
	 Optional. Specify the number of attempts to  start  the  driver(s),  in
	 case  of  failure,  before giving up. A delay of retrydelay is inserted
	 between each attempt. Caution should be taken when using  this  option,
	 since it can impact the time taken by your system to start.

	 The default is 1 attempt.

     nowait
	 Optional.  Specify to upsdrvctl to not wait at all for the driver(s) to
	 execute the request command.

	 The default (omission) is to wait.

	 It can be overridden by NUT_IGNORE_NOWAIT  environment  variable  (e.g.
	 used to work around certain issues with systemd otherwise).

     retrydelay
	 Optional.  Specify  the  delay between each restart attempt of the dri-
	 ver(s), as specified by maxretry. Caution should be  taken  when  using
	 this  option,	since  it  can	impact	the time taken by your system to
	 start.

	 The default is 5 seconds.

     pollinterval
	 Optional. The status of the UPS will be refreshed after a maximum delay
	 which is controlled by this setting. This is normally 2  seconds.  This
	 setting  may  be useful if the driver is creating too much of a load on
	 your monitoring system or network.

	 Note that some drivers (such as  usbhid-ups(8),  snmp-ups(8)  and  nut-
	 drv_qx(8))  also have an option called pollfreq which controls how fre-
	 quently some of the less critical parameters are  polled.  Details  are
	 provided in the respective driver man pages.

     synchronous
	 Optional.  The  drivers  work by default in asynchronous mode initially
	 but can fall back to synchronous mode if writes to server socket failed
	 (i.e synchronous=auto). This means that all data are pushed by the dri-
	 ver on the communication socket to upsd (Unix	socket	on  Unix,  Named
	 pipe  on  Windows)  without  waiting for these data to be actually con-
	 sumed. With some HW, such as ePDUs, that can produce  a  lot  of  data,
	 asynchronous mode may cause some congestion, resulting in the socket to
	 be  full,  and the driver to appear as not connected. In such case, the
	 driver will provide the following debug message:

	     write XX bytes to socket Y failed

	 By enabling the synchronous flag (value = yes), the  driver  will  wait
	 for  data to be consumed by upsd, prior to publishing more. This can be
	 enabled either globally or per driver.

	 The default of auto acts like no (i.e. asynchronous mode) for	backward
	 compatibility	of the driver behavior, until communications fail with a
	 "Resource temporarily unavailable" condition, which  happens  when  the
	 driver  has many data points to send in a burst, and the server can not
	 handle that quickly enough so the buffer fills up.

     user
	 Optional. Overrides the compiled-in default unprivileged  username  for
	 all  NUT device drivers. See the discussion of the -u option in nutups-
	 drv(8) for details.

     group
	 Optional. Overrides the compiled-in (and/or global-section) default un-
	 privileged group name for all NUT device drivers, used for  the  socket
	 file  access.	See  the discussion of the -g option in nutupsdrv(8) for
	 details. This may be specifically useful for ensuring access to dynamic
	 device filesystem nodes, such as USB (or serial-over-USB) hot-plug sup-
	 port, or with device filesystems re-generated by an OS  for  every  re-
	 boot.

     debug_min INTEGER
	 Optional.  Specify a minimum debug level for all driver daemons and for
	 the upsdrvctl(8) tool, e.g. for troubleshooting  a  deployment  without
	 changing  init scripts, without impacting foreground or background run-
	 ning mode directly. Command-line option -D can only increase this  ver-
	 bosity level.

     LIBUSB_DEBUG INTEGER
	 Optional.  For run-time troubleshooting of USB-capable NUT drivers, you
	 can specify verbosity of LibUSB specific debugging as a  numeric  value
	 such  as  4 ("All messages are emitted"). Should not have any practical
	 impact on other NUT drivers.

	 For more details, including the currently  supported  values  for  your
	 version of the library, see e.g.:

	 *   https://libusb.sourceforge.io/api-1.0/

	 *   https://libusb.sourceforge.io/api-1.0/group__libusb__lib.html

UPS FIELDS
     driver
	 Required. This specifies which program will be monitoring this UPS. You
	 need  to specify the one that is compatible with your hardware. See nu-
	 tupsdrv(8) for more information on drivers in general and  pointers  to
	 the man pages of specific drivers.

     port
	 Required.  This  is  the  serial  port where the UPS is connected. On a
	 Linux system, the first serial port usually is /dev/ttyS0.  On  FreeBSD
	 and  similar  systems,  it probably will be /dev/cuaa0. On Windows, the
	 first serial port will be "\\\\.\\COM1" (note the escaped slashes).

     user
	 Optional. Overrides the compiled-in (and/or global-section) default un-
	 privileged username for a particular NUT device driver. See the discus-
	 sion of the -u option in nutupsdrv(8) for details. This may be specifi-
	 cally useful for ensuring access to dynamic  device  filesystem  nodes,
	 such  as  USB	(or  serial-over-USB)  hot-plug  support, or with device
	 filesystems re-generated by an OS for every reboot.

     group
	 Optional. Overrides the compiled-in (and/or global-section) default un-
	 privileged group name for a particular NUT device driver, used for  the
	 socket file access. See the discussion of the -g option in nutupsdrv(8)
	 for details. This may be specifically useful for ensuring access to dy-
	 namic	device	filesystem  nodes,  such  as  USB  (or	serial-over-USB)
	 hot-plug support, or with device filesystems re-generated by an OS  for
	 every reboot.

     sdorder
	 Optional. When you have multiple UPSes on your system, you usually need
	 to  turn  them off in a certain order. upsdrvctl shuts down all the 0s,
	 then the 1s, 2s, and so on. To exclude a  UPS	from  the  shutdown  se-
	 quence, set this to -1.

	 The default value for this parameter is 0.

     sdcommands
	 Optional.  Comma-separated  list  of instant command name(s) to send to
	 the UPS when you request its shutdown.

	 Default logic is built into each driver (where supported)  and  can  be
	 referenced here as the shutdown.default value.

	 The  primary  use-case  is for devices whose drivers "natively" support
	 trying several commands, but the built-in order of those calls  a  com-
	 mand  that is mis-handled by the specific device model (so the handling
	 is reported as successful and the loop stops, but  nothing  happens  as
	 far as the load power-down is concerned).

	 Another  use-case  is	differentiation of automated power-off scenarios
	 where the UPS and its load should stay "OFF" (e.g.  by  building  emer-
	 gency	power-off)  vs. those where the load should return to work auto-
	 matically when it is safe to do so. NOTE:  This  would  currently  need
	 editing  of  ups.conf	for such cases before nutshutdown sees the file;
	 but could be better automated in future NUT releases.

	     Note
	     User-provided commands may be something other than actual shutdown,
	     e.g. a beeper to test that the INSTCMD happened such and  when  ex-
	     pected,  and  the	device was contacted, without impacting the load
	     fed by the UPS.

     allow_killpower
	 Optional. This allows you to request driver.killpower instant	command,
	 to  immediately call the driver-specific default implementation of ups-
	 drv_shutdown() method, for same effect as when a NUT driver is  started
	 with  -k command-line flag. This option can be toggled with upsrw(8) as
	 driver.flag.allow_killpower during run-time.

     desc
	 Optional. This allows you to set a brief  description	that  upsd  will
	 provide to clients that ask for a list of connected equipment.

     nolock
	 Optional. When you specify this, the driver skips the port locking rou-
	 tines every time it starts. This may allow other processes to seize the
	 port if you start more than one accidentally.

	 You should only use this if your system won't work without it.

	 This may be needed on Mac OS X systems.

     ignorelb
	 Optional.  When you specify this, the driver ignores a low battery con-
	 dition flag that is reported by the UPS (some devices will  switch  off
	 almost immediately after setting this flag, or will report this as soon
	 as the mains fails). Instead it will use either of the following condi-
	 tions to determine when the battery is low:

	     battery.charge < battery.charge.low
	     battery.runtime < battery.runtime.low

	 The  idea  is	to set the battery.charge.low and/or battery.runtime.low
	 levels in ups.conf to a value that gives enough time to  cleanly  shut-
	 down your system:

	     override.battery.charge.low = 30
	     override.battery.runtime.low = 180

	 In order for this to work, your UPS should be able to (reliably) report
	 charge and/or runtime remaining on battery. Use with caution!

     maxstartdelay
	 Optional. This can be set as a global variable above your first UPS de-
	 finition  and	it can also be set in a UPS section. This value controls
	 how long upsdrvctl will wait for the driver to  finish  starting.  This
	 keeps your system from getting stuck due to a broken driver or UPS.

	 Note  that  after  this  time	upsdrvctl would just move along with its
	 business (whether retrying the same driver if maxretry>1, or trying an-
	 other driver if starting them all, or just eventually	exit);	however,
	 each  such  most recently started "stuck" driver process may be further
	 initializing in the background, and might even succeed eventually.

	 They would not be actively killed by upsdrvctl after this  timeout  ex-
	 pires.

	 The default is 75 seconds.

     maxretry
	 Optional. This can be set as a global variable above your first UPS de-
	 finition  and	it  can  also  be  set in a UPS section. See explanation
	 above, in the global section.

     retrydelay
	 Optional. This can be set as a global variable above your first UPS de-
	 finition and it can also be set  in  a  UPS  section.	See  explanation
	 above, in the global section.

     synchronous
	 Optional.  Same  as  the global directive of the same name, but this is
	 for a specific device.

     usb_set_altinterface[=altinterface]
	 Optional. Force the USB code to call  usb_set_altinterface(0),  as  was
	 done  in NUT 2.7.2 and earlier. This should not be necessary, since the
	 default for bAlternateSetting (as shown in lsusb) is zero  on	all  USB
	 devices seen to date. However, this redundant call to usb_set_altinter-
	 face() prevents certain UPSes from working on Mac OS X. If your UPS re-
	 quires  explicitly  setting the alternate interface, include this flag,
	 and email the nut-upsdev list with details about your UPS and operating
	 system.

     usb_config_index,	usb_hid_rep_index,  usb_hid_desc_index,   usb_hid_ep_in,
     usb_hid_ep_out
	 Optional.  Force  use of specific interface, endpoint, descriptor index
	 etc. numbers, rather than defaulting to 0 (rarely other values in  cer-
	 tain drivers for some devices known to use non-zero numbers). Specified
	 as a hexadecimal number.

	 As a rule of thumb for usb_hid_desc_index discovery, you can see larger
	 wDescriptorLength  values  (roughly  600+ bytes) in reports of lsusb or
	 similar tools.

     default.<variable>
	 Optional. Set a default value for <variable> which is used in case  the
	 UPS  doesn't  provide	a  value,  but will be overwritten if a value is
	 available from the UPS:

	     default.input.voltage.nominal = 230

	 The above will report the nominal input voltage to be 230,  unless  the
	 UPS tells us differently.

     override.<variable>
	 Optional.  Set a value for <value> that overrides any value that may be
	 read from the UPS. Used for overriding values from  the  UPS  that  are
	 clearly wrong (some devices report wrong values for battery voltage for
	 instance):

	     override.battery.voltage.nominal = 12

	 Use  with caution! This will only change the appearance of the variable
	 to the outside world, internally in the UPS the original value is used.

     All other fields are passed through to the hardware-specific  part  of  the
     driver. See those manuals for the list of what is allowed.

     debug_min INTEGER
	 Optional.  Specify  a	minimum debug level for this driver daemon, e.g.
	 for troubleshooting a deployment, without impacting foreground or back-
	 ground running mode directly. If the global debug_min is also set, this
	 driver-level setting overrides it. Command-line option -D can only  in-
	 crease this verbosity level.

     LIBUSB_DEBUG INTEGER
	 Optional.  For run-time troubleshooting of USB-capable NUT drivers, you
	 can specify verbosity of LibUSB specific debugging as a  numeric  value
	 such as 4 ("All messages are emitted").

	 For  more  details,  including  the currently supported values for your
	 version of the library, see e.g.:

	 *   https://libusb.sourceforge.io/api-1.0/

	 *   https://libusb.sourceforge.io/api-1.0/group__libusb__lib.html

INTEGRATION
     upsdrvctl(8) uses this file to start and stop the drivers.

     The drivers themselves also obtain configuration data from this file.  Each
     driver looks up its section and uses that to configure itself.

     upsd(8)  learns  about  which UPSes are installed on this system by reading
     this file. If this system is called "doghouse" and you have defined  a  UPS
     in  your  ups.conf called "snoopy", then you can monitor it from upsc(8) or
     similar as "snoopy@doghouse".

SEE ALSO
     upsd(8), nutupsdrv(8), upsdrvctl(8), upsdrvsvcctl(8)

   Internet resources
     The NUT (Network UPS Tools) home page: https://www.networkupstools.org/