UPSCODE2(8)			  NUT Manual			   UPSCODE2(8)

NAME
       upscode2	- Driver for UPScode II	compatible UPS equipment

SYNOPSIS
       upscode2	-h

       upscode2	-a UPS_NAME [OPTIONS]

	   Note

	   This	man page only documents	the hardware-specific features of the
	   upscode2 driver. For	information about the core driver, see
	   nutupsdrv(8).

SUPPORTED HARDWARE
       This driver supports UPS	equipment which	can be controlled via the
       UPScode II protocol. This is mainly Fiskars, Powerware equipment, but
       also some (probably OEM'ed) products from Compaq.

EXTRA ARGUMENTS
       This driver supports the	following optional settings in the
       ups.conf(5):

       manufacturer=value
	   Autodetection of this parameter is not possible yet (and it
	   probably never will be). Therefore, this user-defined string
	   accepts any name. The default is unknown.

       input_timeout=value
	   The timeout waiting for a response from the UPS. Some UPS models
	   have	shown to be rather slow, resulting in frequent messages	about
	   empty responses from	the UPS. If you	see this, try increasing this
	   value.

       output_pace=value
	   Delay between characters sent to the	UPS. This was added for
	   completeness	with the above parameter. It has not shown to be
	   needed yet.

       baudrate=value
	   The default baudrate	is 1200, which is the standard for the UPScode
	   II protocol.

       full_update_timer=value
	   Number of seconds between collection	of normative values.

       use_crlf
	   Flag	to set if commands towards to UPS need to be terminated	with
	   CR-LF, and not just CR.

       use_pre_lf
	   Flag	to set if commands towards to UPS need to be introduced	with
	   an LF. A Compaq T1500h is known to need this.

COMMANDS
       The driver supports the following commands for those UPSes that support
       them. The available commands are	autodetected during initialization, so
       you should check	availability with upscmd -l.

          test.panel.start - Start UPS	self test

          test.battery.start -	Start battery self test

          beeper.enable - Enable UPS beeper

          beeper.disable - Disable UPS	beeper

          shutdown.return - Shut down in 1 second and wait for	power to
	   return

          shutdown.stayoff - Shut down	in 1 seconds

          shutdown.reboot - Shut down in 1 seconds and	reboot after 1 minute

          shutdown.reboot.graceful - Shut down	in 20 seconds and reboot after
	   1 minute

NOTES
       The Powerware UPS models	that this driver has been tested against until
       now have	not returned a value for battery.charge. Therefore, the	driver
       will guesstimate	a value	based on the nominal battery min/max and the
       current battery voltage.

AUTHORS
          Hvard Lygre <hklygre@online.no>

          Niels Baggesen <niels@baggesen.net>

SEE ALSO
   The core driver:
       nutupsdrv(8)

   Internet resources:
       The NUT (Network	UPS Tools) home	page: https://www.networkupstools.org/

Network	UPS Tools 2.8.2.	  04/17/2025			   UPSCODE2(8)