NAME
       upsmon -	UPS monitor and	shutdown controller

SYNOPSIS
       upsmon -h

       upsmon -c command [-P pid]

       upsmon [-D] [-F | -B] [-K] [-p] [-u user]

DESCRIPTION
       upsmon is the client process that is responsible	for the	most important
       part of UPS monitoring -- shutting down the system when the power goes
       out. It can call	out to other helper programs for notification purposes
       during power events.

       upsmon can monitor multiple systems using a single process. Every UPS
       that is defined in the upsmon.conf(5) configuration file	is assigned a
       power value and a type (primary or secondary).

OPTIONS
       -h
	   Display the help message.

       -c command
	   Send	the command command to the existing upsmon process. Valid
	   commands are:

	   fsd
	       shutdown	all primary-mode UPSes (use with caution)

	   stop
	       stop monitoring and exit

	   reload
	       reread upsmon.conf(5) configuration file. See "reloading
	       nuances"	below if this doesn't work.

       -P pid
	   Send	the command signal above using specified PID number, rather
	   than	consulting the PID file. This can help define service units
	   which start main upsmon as a	foreground process so it does not have
	   to rely on a	PID file.

       -D
	   Raise the debugging level. upsmon will run in the foreground	by
	   default, and	will print information on stdout about the monitoring
	   process. Use	this option multiple times for more details.

       -F
	   upsmon will run in the foreground, regardless of debugging
	   settings.

       -B
	   upsmon will run in the background, regardless of debugging
	   settings.

       -K
	   Test	for the	shutdown flag. If it exists and	contains the magic
	   string from upsmon, then upsmon will	exit with EXIT_SUCCESS.	Any
	   other condition will	make upsmon exit with EXIT_FAILURE.

	   You can test	for a successful exit from upsmon -K in	your shutdown
	   scripts to know when	to call	upsdrvctl(8) to	shut down the UPS.

       -p
	   Run privileged all the time.	Normally upsmon	will split into	two
	   processes. The majority of the code runs as an unprivileged user,
	   and only a tiny stub	runs as	root. This switch will disable that
	   mode, and run the old "all root all the time" system.

	   This	is not the recommended mode, and you should not	use this
	   unless you have a very good reason.

       -u user
	   Set the user	for the	unprivileged monitoring	process. This has no
	   effect when using -p.

	   The default user is set at build configuration time with configure
	   --with-user=.... Typically this is nobody (if not otherwise
	   configured),	which is far from ideal, so most packaged
	   distributions will probably have a specific nut user	for this task.
	   If your notification	scripts	need to	run as a specific user,	set it
	   here.

	   You can also	set this in the	upsmon.conf(5) file with the
	   RUN_AS_USER directive.

UPS DEFINITIONS
       In the upsmon.conf(5), you must specify at least	one UPS	that will be
       monitored. Use the MONITOR directive like this:

	   MONITOR 'system' 'powervalue' 'username' 'password' 'type'

       The system refers to a upsd(8) server, in the form
       upsname[@hostname[:port]]. The default hostname is "localhost", and
       default port is 3493. Some examples follow:

          "su700@mybox" means a UPS called "su700" on a system	called
	   "mybox". This is the	normal form.

          "fenton@bigbox:5678"	is a UPS called	"fenton" on a system called
	   "bigbox" which runs upsd(8) on port "5678".

       The powervalue refers to	how many power supplies	on this	client system
       are being driven	this UPS. This is typically set	to 1, but see the
       section on power	values below.

       The username is a section in your upsd.users(5) file. Whatever password
       you set in that section must match the password set in this file	for
       the corresponding data server instance.

       The type	set in that section of the data	server configuration must also
       match the type here -- primary or secondary (consider it	an "upsmon
       role"). In general, a "primary" client process is one running on	the
       system with the UPS actually plugged into a serial or USB port, and a
       "secondary" is drawing power from the UPS but can't talk	to it
       directly. See the section on UPS	types for more.

NOTIFY EVENTS
       upsmon senses several events as it monitors each	UPS. They are called
       "notify events",	as they	can be used to tell the	users and admins about
       the change in status. See the additional	NOTIFY-related sections	below
       for information on customizing the delivery of these messages.

       ONLINE
	   The UPS is back on line.

       ONBATT
	   The UPS is on battery.

       LOWBATT
	   The UPS battery is low (as determined by the	driver).

       FSD
	   The UPS has been commanded into the "forced shutdown" mode.

       COMMOK
	   Communication with the UPS has been established.

       COMMBAD
	   Communication with the UPS was just lost.

       SHUTDOWN
	   The local system is being shut down.

       REPLBATT
	   The UPS needs to have its battery replaced.

       NOCOMM
	   The UPS can't be contacted for monitoring.

       NOPARENT
	   upsmon parent process died -	shutdown impossible.

       CAL
	   UPS calibration in progress.

       NOTCAL
	   UPS calibration finished.

       OFF
	   UPS administratively	OFF or asleep.

       NOTOFF
	   UPS no longer administratively OFF or asleep.

       BYPASS
	   UPS on bypass (powered, not protecting).

       NOTBYPASS
	   UPS no longer on bypass.

       ECO
	   UPS in ECO or similar mode (as defined and named by vendor);	other
	   names include High Efficiency mode and Energy Saver System.

	   For example,	Eaton docs define High Efficiency mode as a sort of
	   hardware-monitored bypass with switch-over under 10ms into Online
	   mode	in case	of troubles (so	what was known as Line-Interactive in
	   the older days), which can be chosen	instead	of always running in a
	   dual-conversion mode	(safer,	but more wasteful and with a toll on
	   battery life). Older	devices	only implemented one or	the other.

       NOTECO
	   UPS no longer in ECO	mode (see above).

       ALARM
	   UPS has one or more active alarms (look at ups.alarm	for details).

       NOTALARM
	   UPS is no longer in an alarm	state (no active alarms).

       OTHER
	   UPS has at least one	unclassified status token.

       NOTOTHER
	   UPS has no unclassified status tokens anymore.

       SUSPEND_STARTING
	   OS is entering sleep/suspend/hibernate mode.

       SUSPEND_FINISHED
	   OS just finished sleep/suspend/hibernate mode, de-activating
	   obsolete UPS	readings to avoid an unfortunate shutdown.

NOTIFY COMMAND
       In upsmon.conf(5), you can configure a program called the NOTIFYCMD
       that will handle	events that occur.

       The syntax is: NOTIFYCMD	"path to program"

       Example:

          NOTIFYCMD "/usr/local/bin/notifyme"

       Remember	to wrap	the path in "double quotes" if it contains any spaces.
       It should probably not rely on receiving	any command-line arguments.

       The program you run as your NOTIFYCMD can use the environment variables
       NOTIFYTYPE and UPSNAME to know what has happened	and on which UPS. It
       also receives the notification message (see below) as the first (and
       only) argument, so you can deliver a pre-formatted message too.

       Note that the NOTIFYCMD will only be called for a given event when you
       set the EXEC flag by using the notify flags, as detailed	below.

NOTIFY FLAGS
       By default, all notify events (see above) generate a global message
       (wall) to all users, plus they are logged via the syslog. Except	for
       Windows where upsmon only writes	to the syslog by default. You can
       change this with	the NOTIFYFLAG directive in the	configuration file:

       The syntax is: NOTIFYFLAG notifytype flags

       Examples:

          NOTIFYFLAG ONLINE SYSLOG

          NOTIFYFLAG ONBATT SYSLOG+WALL

          NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC

       The flags that can be set on a given notify event are:

       SYSLOG
	   Write this message to the syslog.

       WALL
	   Send	this message to	all users on the system	via wall(1).

       EXEC
	   Execute the NOTIFYCMD.

       IGNORE
	   Don't do anything. If you use this, don't use any of	the other
	   flags.

       You can mix these flags;	for example, SYSLOG+WALL+EXEC does all three
       for a given event.

NOTIFY MESSAGES
       upsmon comes with default messages for each of the NOTIFY events. These
       can be changed with the NOTIFYMSG directive.

       The syntax is: NOTIFYMSG	type "message"

       Examples:

          NOTIFYMSG ONLINE "UPS %s is getting line power"

          NOTIFYMSG ONBATT "Someone pulled the	plug on	%s"

       The first instance of %s	is replaced with the identifier	of the UPS
       that generated the event. These messages	are used when sending walls to
       the users directly from upsmon, and are also passed to the NOTIFYCMD.

	   Note

	   Certain notifications, such as NOTIFY_ALARM and NOTIFY_OTHER, can
	   accept a second instance of %s that would be	replaced with the
	   alarm text or the unrecognized token, respectively.

POWER VALUES
       The "current overall power value" is the	sum of all UPSes that are
       currently able to supply	power to the system hosting upsmon. Any	UPS
       that is either on line or just on battery contributes to	this number.
       If a UPS	is critical (on	battery	and low	battery) or has	been put into
       "forced shutdown" mode, it no longer contributes.

       The syntax is: MONITOR upsname powervalue username password type

       A "power	value" on a MONITOR line in the	config file is the number of
       power supplies that the UPS runs	on the current system.

          Normally, you only have one power supply, so	it will	be set to 1.

	   Example:

	      MONITOR myups@myhost 1 username mypassword primary

          On a	large server with redundant power supplies, the	power value
	   for a UPS may be greater than 1. You	may also have more than	one of
	   them	defined.

	   Examples for	a server with four power supply	modules	and two	UPSes
	   (each feeding two power supplies of that server):

	      MONITOR ups-alpha@myhost	2 username mypassword primary

	      MONITOR ups-beta@myhost 2 username mypassword primary

          You can also	set the	power value for	a UPS to 0 if it does not
	   supply any power to that system. This is generally used when	you
	   want	to use the upsmon notification features	for a UPS even though
	   it's	not actually powering the system that hosts this instance of
	   the upsmon client.

	   Don't set this to "primary" unless you really want to power this
	   UPS off when	this instance of upsmon	needs to shut down for its own
	   reasons.

	   Example:

	      MONITOR faraway@anotherbox 0 username mypassword	secondary

       The "minimum power value" is the	number of power	supplies that must be
       receiving power in order	to keep	this upsmon client's computer running.

       The syntax is: MINSUPPLIES value

          Typical PCs only have 1, so most users will leave this at the
	   default.

	   Example:

	      MINSUPPLIES 1

          If you have a server	or similar system with redundant power,	then
	   this	value will usually be set higher. One that requires three
	   power supplies out of 4 to be running at all	times would simply set
	   it to 3.

	   Example:

	      MINSUPPLIES 3

	   When	the current overall healthy UPS-protected external power value
	   drops below the minimum required power value, upsmon	starts the
	   shutdown sequence. This design allows you to	lose some of your
	   power supplies in a redundant power environment without bringing
	   down	the entire system, while still working properly	for smaller
	   systems.

UPS TYPES
       upsmon and upsd(8) don't	always run on the same system. When they do,
       any UPSes that are directly attached to the upsmon host should be
       monitored in "primary" mode. This makes upsmon take charge of that
       equipment, and it will wait for the "secondary" systems to disconnect
       before shutting down the	local system. This allows the distant systems
       (monitoring over	the network) to	shut down cleanly before upsdrvctl
       shutdown	runs locally and turns them all	off.

       When upsmon runs	as a secondary,	it is relying on the distant system to
       tell it about the state of the UPS. When	that UPS goes critical (on
       battery and low battery), it immediately	invokes	the local shutdown
       command.	This needs to happen quickly. Once all secondaries disconnect
       from the	distant	upsd(8)	server,	its primary-mode upsmon	will start its
       own shutdown process. Your secondary systems must all quiesce and shut
       down before the primary turns off the shared power source, or
       filesystem damage may result.

       upsmon deals with secondaries that get wedged, hang, or otherwise fail
       to gracefully disconnect	from upsd(8) in	a timely manner	with the
       HOSTSYNC	timer. During a	shutdown situation, the	primary	upsmon will
       give up after this interval and it will shut down anyway. This keeps
       the primary from	sitting	there forever (which would endanger that host)
       if a secondary should break somehow. This defaults to 15	seconds.

       If your primary system is shutting down too quickly, set	the FINALDELAY
       interval	to something greater than the default 15 seconds. Don't	set
       this too	high, or your UPS battery may run out of power before the
       primary upsmon process shuts down that system.

TIMED SHUTDOWNS
       For those rare situations where the shutdown process can't be completed
       between the time	that low battery is signalled and the UPS actually
       powers off the load, use	the upssched(8)	helper program.	You can	use it
       along with upsmon to schedule a shutdown	based on the "on battery"
       event. upssched can then	come back to upsmon to initiate	the shutdown
       once it has run on battery too long.

       This can	be complicated and messy, so stick to the default critical UPS
       handling	if you can.

REDUNDANT POWER	SUPPLIES
       If you have more	than one power supply for redundant power, you may
       also have more than one UPS feeding your	computer. upsmon can handle
       this. Be	sure to	set the	UPS power values appropriately and the
       MINSUPPLIES value high enough so	that it	keeps running until it really
       does need to shut down.

       For example, the	HP NetServer LH4 by default has	3 power	supplies
       installed, with one bay empty. It has two power cords, one per side of
       the box.	This means that	one power cord powers two power	supply bays,
       and that	you can	only have two UPSes supplying power.

       Connect UPS "alpha" to the cord feeding two power supplies, and UPS
       "beta" to the cord that feeds the third and the empty slot. Define
       alpha as	a powervalue of	2, and beta as a powervalue of 1. Set the
       MINSUPPLIES to 2.

       When alpha goes on battery, your	current	overall	power value will stay
       at 3, as	it's still supplying power. However, once it goes critical (on
       battery and low battery), it will stop contributing to the current
       overall power value. That means the value will be 1 (beta alone), which
       is less than 2. That is insufficient to run the system, and upsmon will
       invoke the shutdown sequence.

       However,	if beta	goes critical, subtracting its contribution will take
       the current overall value from 3	to 2. This is just high	enough to
       satisfy the minimum, so the system will continue	running	as before. If
       beta returns later, it will be re-added and the current value will go
       back to 3. This allows you to swap out UPSes, change a power
       configuration, or whatever, as long as you maintain the minimum power
       value at	all times.

MIXED OPERATIONS
       Besides being able to monitor multiple UPSes, upsmon can	also monitor
       them as different roles.	If you have a system with multiple power
       supplies	serviced by separate UPS batteries, it's possible to be	a
       primary on one UPS and a	secondary on the other.	This usually happens
       when you	run out	of serial or USB ports and need	to do the monitoring
       through another system nearby.

       This is also complicated, especially when it comes time to power	down a
       UPS that	has gone critical but doesn't supply the local system. You can
       do this with some scripting magic in your notify	command	script,	but
       it's beyond the scope of	this manual.

FORCED SHUTDOWNS
       When upsmon is forced to	bring down the local system, it	sets the "FSD"
       (forced shutdown) flag on any UPSes that	it is running in primary mode.
       This is used to synchronize secondary systems in	the event that a
       primary which is	otherwise OK needs to be brought down due to some
       pressing	event on the UPS manager system.

       You can manually	invoke this mode on the	system with primary-mode
       upsmon by starting another copy of the program with -c fsd command line
       argument. This is useful	when you want to initiate a shutdown before
       the critical stage through some external	means, such as upssched(8).

	   Warning

	   Please note that by design, since we	require	power-cycling the load
	   and don't want some systems to be powered off while others remain
	   running if the "wall	power" returns at the wrong moment as usual,
	   the "FSD" flag can not be removed from the data server unless its
	   daemon is restarted.	If we do take the first	step in	critical mode,
	   then	we normally intend to go all the way --	shut down all the
	   servers gracefully, and power down the UPS.

       Keep in mind that some UPS devices and corresponding drivers would also
       latch or	otherwise resurface the	"FSD" state again even if "wall	power"
       is available, but the remaining battery charge is below a threshold
       configured as "safe" in the device (usually if you manually power on
       the UPS after a long power outage). This	is by design of	respective UPS
       vendors,	since in such situation	they can not guarantee that if a new
       power outage happens, their UPS would safely shut down your systems
       again. So it is deemed better and safer to stay dark until batteries
       become sufficiently charged.

       When it is time to shut down, upsmon creates POWERDOWNFLAG to
       communicate to the operating system that	the UPS	should be commanded
       off late	in the shutdown	sequence. This file is removed if present when
       upsmon starts, so that the next normal shutdown does not	cause the UPS
       to be turned off. (The file can't in general be removed during shutdown
       because the filesystem might be read only. If the file is in a
       RAM-backed filesystem, the it won't be present and the check to remove
       it won't	fire.)

SIMULATING POWER FAILURES
       To test a synchronized shutdown without pulling the plug	on your
       UPS(es),	you need only set the forced shutdown (FSD) flag on them. You
       can do this by calling upsmon again to set the flag, i.e.:

	   :; upsmon -c	fsd

       After that, the primary and the secondary will do their usual shutdown
       sequence	as if the battery had gone critical, while you can time	how
       long it takes for them. This is much easier on your UPS equipment, and
       it beats	crawling under a desk to find the plug.

       Note you	can also use a dummy SHUTDOWNCMD setting to just report	that
       the systems would shut down at this point, without actually disrupting
       their work.

	   Warning

	   After such "dummy" experiments you may have to restart the NUT data
	   server upsd to clear	its "FSD" flag for the devices and clients
	   involved, and make sure no files named by POWERDOWNFLAG option
	   (e.g. /etc/killpower) remain	on the upsmon primary systems under
	   test.

DEAD UPSES
       In the event that upsmon	can't reach upsd(8), it	declares that UPS
       "dead" after some interval controlled by	DEADTIME in the
       upsmon.conf(5). If this happens while that UPS was last known to	be on
       battery,	it is assumed to have gone critical and	no longer contributes
       to the overall power value.

       upsmon will alert you to	a UPS that can't be contacted for monitoring
       with a "NOCOMM" notifier	by default every 300 seconds. This can be
       changed with the	NOCOMMWARNTIME setting.

       Also upsmon normally reports polling failures for each device that are
       in place	for each POLLFREQ loop (e.g. "Data stale" or "Driver not
       connected") to system log as configured.	If your	devices	are expected
       to be AWOL for an extended timeframe, you can use
       POLLFAIL_LOG_THROTTLE_MAX to reduce the stress on syslog	traffic	and
       storage,	by posting these messages only once in every several loop
       cycles, and when	the error condition has	changed	or cleared. A negative
       value means standard behavior (log on every loop, effectively same as
       when max=1), and	a zero value means to never repeat the message (log
       only on start and end/change of the failure state).

       Note that this throttle only applies to one latest-active error state
       per monitored device.

UPS ALARMS
       UPS manufacturers and UPS drivers may implement device-specific alarms
       to notify the user about	potentially severe conditions of the UPS. The
       status "ALARM" will be set on such UPS as a common denominator for the
       different implementations throughout the	various	UPS drivers and
       generally anytime that a	"ups.alarm" variable is	seen reported by the
       specific	UPS driver.

       Alarms can be acted upon	by the user using the "ALARM" and "NOTALARM"
       notifiers, which	are reported by	the upsmon when	the "ALARM" status
       occurs or disappears.

       As alarms raised	by the UPS are usually severe in nature, the upsmon
       watches a UPS in	such a state more closely, bumping up the polling
       frequency as needed.

       When connection loss occurs in such an alarm state, the upsmon will by
       default consider	the volatile UPS as critical/dead and this may lead to
       false shutdowns if the actual alarm was in fact mundane in nature (e.g.
       caused by a HE/ECO mode). This can be changed by	utilizing the
       ALARMCRITICAL setting within upsmon.conf.

RELOADING NUANCES
       upsmon usually gives up root powers for the process that	does most of
       the work, including handling signals like SIGHUP	to reload the
       configuration file. This	means your upsmon.conf(8) file must be
       readable	by the non-root	account	that upsmon switches to.

       If you want reloads to work, upsmon must	run as some user that has
       permissions to read the configuration file. I recommend making a	new
       user just for this purpose, as making the file readable by "nobody"
       (the default user) would	be a bad idea.

       See the RUN_AS_USER section in upsmon.conf(8) for more on this topic.

       Additionally, you can't change the SHUTDOWNCMD or POWERDOWNFLAG
       definitions with	a reload due to	the split-process model. If you	change
       those values, you must stop upsmon and start it back up.	upsmon will
       warn you	in the syslog if you make changes to either of those values
       during a	reload.

ENVIRONMENT VARIABLES
       NUT_DEBUG_LEVEL sets default debug verbosity if no -D arguments were
       provided	on command line, but does not request that the daemon runs in
       foreground mode.

       NUT_CONFPATH is the path	name of	the directory that contains
       upsmon.conf and other configuration files. If this variable is not set,
       upsmon uses a built-in default, which is	often /usr/local/etc.

       NUT_QUIET_INIT_UPSNOTIFY=true can be used to prevent daemons which can
       notify service management frameworks (such as systemd) about passing
       their lifecycle milestones from emitting	such notifications (including
       those about lack	of system support for such modern features, once per
       run).

       NUT_QUIET_INIT_BANNER=true can be used to suppress NUT tool name	and
       version banner. NOT recommended for services due	to adverse
       troubleshooting impact, but may be helpful in shell profiles or scripts
       which process NUT tool outputs.

FILES
       upsmon.conf(5)

SEE ALSO
   Server:
       upsd(8)

   Clients:
       upsc(8),	upscmd(8), upsrw(8), upsmon(8)

   CGI programs:
       upsset.cgi(8), upsstats.cgi(8), upsimage.cgi(8)

   Internet resources:
       The NUT (Network	UPS Tools) home	page: https://www.networkupstools.org/

Network	UPS Tools 2.8.2.	  04/17/2025			     UPSMON(8)