UPSMON.CONF(5)			  NUT Manual			UPSMON.CONF(5)

NAME
       upsmon.conf - Configuration for Network UPS Tools upsmon	client

DESCRIPTION
       This file's primary job is to define the	systems	that upsmon(8) will
       monitor,	and to tell it how to shut down	the system when	necessary. It
       will contain passwords, so keep it secure. Ideally, only	the upsmon
       process should be able to read it.

       A minimal configuration should include at least one MONITOR
       instruction, MINSUPPLIES	(may be	0 if this system is only monitoring
       other NUT servers), and a POWERDOWNFLAG if this machine is a "primary"
       system connected	to the UPS and drives its late-shutdown	power-off
       command in case of an emergency.

       Additionally, other optional configuration values can be	set in this
       file.

IMPORTANT NOTES
          Contents of this file should	be pure	ASCII (character codes not in
	   range would be ignored with a warning message).

          Balance the run-time	user permissions to access the file (and
	   perhaps the directory it is in) for only upsmon to be able to read
	   it; write access is not needed. It is common	to use chown root:nut
	   and chmod 640 to set	up acceptable file permissions.

	      Packages	(and build recipes) typically prepare one set of user
	       and group accounts for NUT. Custom builds with minimal
	       configuration might even	use nobody:nogroup or similar, which
	       is inherently insecure.

	      On systems with extra security concerns,	NUT drivers, data
	       server, and any other monitoring, logging, etc. clients,	should
	       run as separate user accounts. This would need some daemons to
	       use customized user, group, RUN_AS_USER and/or RUN_AS_GROUP
	       settings	to override the	single built-in	value.

	      Keep in mind the	security of also any backup copies of this
	       file, e.g. the archive files it might end up in.

CONFIGURATION DIRECTIVES
       DEADTIME	seconds
	   upsmon allows a UPS to go missing for this many seconds before
	   declaring it	"dead".	The default is 15 seconds.

	   upsmon requires a UPS to provide status information every few
	   seconds (see	POLLFREQ and POLLFREQALERT) to keep things updated. If
	   the status fetch fails, the UPS is marked stale. If it stays	stale
	   for more than DEADTIME seconds, the UPS is marked dead.

	   A dead UPS that was last known to be	on battery is assumed to have
	   changed to a	low battery condition. This may	force a	shutdown if it
	   is providing	a critical amount of power to your system. This	seems
	   disruptive, but the alternative is barreling	ahead into oblivion
	   and crashing	when you run out of power.

	   Note: DEADTIME should be a multiple of POLLFREQ and POLLFREQALERT.
	   Otherwise, you'll have "dead" UPSes simply because upsmon isn't
	   polling them	quickly	enough.	Rule of	thumb: take the	larger of the
	   two POLLFREQ	values,	and multiply by	3.

       FINALDELAY seconds
	   When	running	in primary mode, upsmon	waits this long	after sending
	   the NOTIFY_SHUTDOWN to warn the users. After	the timer elapses, it
	   then	runs your SHUTDOWNCMD. By default this is set to 5 seconds.

	   If you need to let your users do something in between those events,
	   increase this number. Remember, at this point your UPS battery is
	   almost depleted, so don't make this too big.

	   Alternatively, you can set this very	low so you don't wait around
	   when	it's time to shut down.	Some UPSes don't give much warning for
	   low battery and will	require	a value	of 0 here for a	safe shutdown.

	       Note
	       If FINALDELAY on	the secondary is greater than HOSTSYNC on the
	       primary,	the primary will give up waiting for that secondary
	       upsmon to disconnect.

       HOSTSYNC	seconds
	   upsmon will wait up to this many seconds in primary mode for	the
	   secondaries to disconnect during a shutdown situation. By default,
	   this	is 15 seconds.

	   When	a UPS goes critical (on	battery	+ low battery, or "FSD":
	   forced shutdown), the secondary systems are supposed	to disconnect
	   and shut down right away. The HOSTSYNC timer	keeps the primary
	   upsmon from sitting there forever if	one of the secondaries gets
	   stuck.

	   This	value is also used to keep secondary systems from getting
	   stuck if the	primary	fails to respond in time. After	a UPS becomes
	   critical, the secondary will	wait up	to HOSTSYNC seconds for	the
	   primary to set the FSD flag.	If that	timer expires, the secondary
	   upsmon will assume that the primary (or communications path to it)
	   is broken and will shut down	anyway.

	   This	keeps the secondaries from shutting down during	a short-lived
	   status change to "OB	LB" and	back that the secondaries see but the
	   primary misses.

       MINSUPPLIES num
	   Set the number of power supplies that must be receiving power to
	   keep	this system running. Normal computers have just	one power
	   supply, so the default value	of 1 is	acceptable.

	   Large/expensive server type systems usually have more, and can run
	   with	a few missing. The HP NetServer	LH4 can	run with 2 out of 4,
	   for example,	so you'd set it	to 2. The idea is to keep the box
	   running as long as possible,	right?

	   Obviously you have to put the redundant supplies on different UPS
	   circuits for	this to	make sense! See	big-servers.txt	in the docs
	   subdirectory	for more information and ideas on how to use this
	   feature.

	   Also	see the	section	on "power values" in upsmon(8).

       MONITOR system powervalue username password type
	   Each	UPS that you need to be	monitor	should have a MONITOR line.
	   Not all of these need supply	power to the system that is running
	   upsmon. You may monitor other systems if you	want to	be able	to
	   send	notifications about status changes on them.

	   You must have at least one MONITOR directive	in upsmon.conf.

	      system is a UPS identifier. It is in this form:

	       <upsname>[@<hostname>[:<port>]]

	       The default hostname is "localhost". Some examples:

	          "su700@mybox" means a UPS called "su700" on a system	called
		   "mybox". This is the	normal form.

	          "fenton@bigbox:5678"	is a UPS called	"fenton" on a system
		   called "bigbox" which runs upsd(8) on port "5678".

	      powervalue is an	integer	representing the number	of power
	       supplies	that the UPS feeds on this system. Most	normal
	       computers have one power	supply,	and the	UPS feeds it, so this
	       value will be 1.	You need a very	large or special system	to
	       have anything higher here.

	       You can set the powervalue to 0 if you want to monitor a	UPS
	       that doesn't actually supply power to this system. This is
	       useful when you want to have upsmon do notifications about
	       status changes on a UPS without shutting	down when it goes
	       critical.

	      The username and	password on this line must match an entry in
	       the upsd	server system's	upsd.users(5) file.

	       If your username	is "observer" and your password	is "abcd", the
	       MONITOR line might look like this (likely on a remote secondary
	       system):

		   MONITOR myups@bigserver 1 observer abcd secondary

	       Meanwhile, the upsd.users on bigserver would look like this:

		   [observer]
			   password = abcd
			   upsmon secondary

		   [upswired]
			   password = blah
			   upsmon primary

	       And the copy of upsmon on that bigserver	would run with the
	       primary configuration:

		   MONITOR myups@bigserver 1 upswired blah primary

	      The type	refers to the relationship with	upsd(8). It can	be
	       either "primary"	or "secondary".	See upsmon(8) for more
	       information on the meaning of these modes. The mode you pick
	       here also goes in the upsd.users	file, as seen in the example
	       above.

       NOCOMMWARNTIME seconds
	   upsmon will trigger a NOTIFY_NOCOMM after this many seconds if it
	   can't reach any of the UPS entries in this configuration file. It
	   keeps warning you until the situation is fixed. By default this is
	   300 seconds.

       POLLFAIL_LOG_THROTTLE_MAX count
	   upsmon normally reports polling failures for	each device that are
	   in place for	each POLLFREQ loop (e.g. "Data stale" or "Driver not
	   connected") to system log as	configured. If your devices are
	   expected to be AWOL for an extended timeframe, you can use this
	   throttle to reduce the stress on syslog traffic and storage,	by
	   posting these messages only once in every several loop cycles, and
	   when	the error condition has	changed	or cleared.

	   A negative value means standard behavior (log on every loop,
	   effectively same as when max=1), and	a zero value means to never
	   repeat the message (log only	on start and end/change	of the failure
	   state).

	   Note	that this throttle only	applies	to one latest-active error
	   state per monitored device.

       NOTIFYCMD command
	   upsmon calls	this to	send messages when things happen.

	   This	command	is called with the full	text of	the message as one
	   argument. The environment string NOTIFYTYPE will contain the	type
	   string of whatever caused this event	to happen.

	   If you need to use upssched(8), then	you must make it your
	   NOTIFYCMD by	listing	it here.

	   Note	that this is only called for NOTIFY events that	have EXEC set
	   with	NOTIFYFLAG. See	NOTIFYFLAG below for more details.

	   Making this some sort of shell script might not be a	bad idea. For
	   more	information and	ideas, see docs/scheduling.txt

	   Remember, this command also needs to	be one element in the
	   configuration file, so if your command has spaces, then wrap	it in
	   quotes.

	   NOTIFYCMD "/path/to/script --foo --bar"

	   This	script is run in the background--that is, upsmon forks before
	   it calls out	to start it. This means	that your NOTIFYCMD may	have
	   multiple instances running simultaneously if	a lot of stuff happens
	   all at once.	Keep this in mind when designing complicated
	   notifiers.

       NOTIFYMSG type message
	   upsmon comes	with a set of stock messages for various events. You
	   can change them if you like.

	       NOTIFYMSG ONLINE	"UPS %s	is getting line	power"

	       NOTIFYMSG ONBATT	"Someone pulled	the plug on %s"

	   Note	that %s	is replaced with the identifier	of the UPS in
	   question.

	   The message must be one element in the configuration	file, so if it
	   contains spaces, you	must wrap it in	quotes.

	       NOTIFYMSG NOCOMM	"Someone stole UPS %s"

	   Possible values for type:

	   ONLINE
	       UPS is back online

	   ONBATT
	       UPS is on battery

	   LOWBATT
	       UPS is on battery and has a low battery (is critical)

	   FSD
	       UPS is being shutdown by	the primary (FSD = "Forced Shutdown")

	   COMMOK
	       Communications established with the UPS

	   COMMBAD
	       Communications lost to the UPS

	   SHUTDOWN
	       The system is being shutdown

	   REPLBATT
	       The UPS battery is bad and needs	to be replaced

	   NOCOMM
	       A UPS is	unavailable (can't be contacted	for monitoring)

	   NOPARENT
	       upsmon parent process died - shutdown impossible

	   CAL
	       UPS calibration in progress

	   NOTCAL
	       UPS calibration finished

	   OFF
	       UPS administratively OFF	or asleep

	   NOTOFF
	       UPS no longer administratively OFF or asleep

	   BYPASS
	       UPS on bypass (powered, not protecting)

	   NOTBYPASS
	       UPS no longer on	bypass

	   ECO
	       UPS in ECO or similar mode (as defined and named	by vendor);
	       for more	details	see upsmon(8).

	   NOTECO
	       UPS no longer in	ECO mode (see above)

	   ALARM
	       UPS has one or more active alarms (check	ups.alarm); for	this
	       notification, the message can contain a second %s placeholder
	       to substitute the current value of ups.alarm.

	   NOTALARM
	       UPS is no longer	in an alarm state (no active alarms)

	   OTHER
	       UPS has at least	one unclassified ups.status token; for this
	       notification, the message can contain a second %s placeholder
	       to substitute the current collection of such tokens.

	   NOTOTHER
	       UPS has no unclassified status tokens anymore

	   SUSPEND_STARTING
	       OS is entering sleep/suspend/hibernate mode

	   SUSPEND_FINISHED
	       OS just finished	sleep/suspend/hibernate	mode, de-activating
	       obsolete	UPS readings to	avoid an unfortunate shutdown

       NOTIFYFLAG type flag[+flag]...
	   By default, upsmon sends walls global messages to all logged	in
	   users) via /bin/wall	and writes to the syslog when things happen.
	   Except for Windows where upsmon only	writes to the Event Log	by
	   default. You	can change this.

	   Examples:

	       NOTIFYFLAG ONLINE SYSLOG
	       NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC

	   Possible values for the flags:

	   SYSLOG
	       Write the message to the	syslog

	   WALL
	       Write the message to all	users with /bin/wall

	   EXEC
	       Execute NOTIFYCMD (see above) with the message

	   IGNORE
	       Don't do	anything

	       If you use IGNORE, don't	use any	other flags on the same	line.

       POLLFREQ	seconds
	   Normally upsmon polls the upsd(8) server every 5 seconds. If	this
	   is flooding your network with activity, you can make	it higher. You
	   can also make it lower to get faster	updates	in some	cases.

	   There are some catches. First, if you set the POLLFREQ too high,
	   you may miss	short-lived power events entirely. You also risk
	   triggering the DEADTIME (see	above) if you use a very large number.

	   Second, there is a point of diminishing returns if you set it too
	   low.	While upsd normally has	all of the data	available to it
	   instantly, most drivers only	refresh	the UPS	status once every 2
	   seconds. Polling any	more than that usually doesn't get you the
	   information any faster.

       POLLFREQALERT seconds
	   This	is the interval	that upsmon waits between polls	if any of its
	   UPSes are on	battery. You can use this along	with POLLFREQ above to
	   slow	down polls during normal behavior, but get quicker updates
	   when	something bad happens.

	   This	should always be equal to or lower than	the POLLFREQ value. By
	   default it is also set 5 seconds.

	   The warnings	from the POLLFREQ entry	about too-high and too-low
	   values also apply here.

       POWERDOWNFLAG filename
	   upsmon creates this file when running in primary mode when the UPS
	   needs to be powered off. You	should check for this file in your
	   late	shutdown scripts and call upsdrvctl shutdown if	it exists;
	   note	that upsmon -K may be called for this effect, if NUT
	   configuration files remain readable at that point (file systems
	   mostly unmounted or changed to read-only).

	   Historically	it was often /etc/killpower but	nowadays you may want
	   it in a temporary filesystem	(e.g. under /run or /run/nut
	   location).

	   Note	that double backslashes	must be	used for Windows paths,	e.g.
	   C:\\Temp\\killpower (modern Windows may also	accept forward slashes
	   like	C:/Temp/killpower but YMMV).

	   This	is done	to forcibly reset the secondary	systems, so they don't
	   get stuck at	the "halted" stage even	if the power returns during
	   the shutdown	process. This usually does not work well on
	   contact-closure UPSes that use the genericups driver.

	       Warning
	       The upsmon binary program does not have a built-in default, so
	       this setting MUST be specified in the configuration, in order
	       for the late shutdown integration to work on the	particular
	       primary-mode system!
	   See the config-notes.txt file in the	docs subdirectory for more
	   information.	Refer to the section:

	   "Configuring	automatic shutdowns for	low battery events", or	refer
	   to the online version.

       OFFDURATION seconds
	   NUT supports	an "administrative OFF"	for power devices which	can be
	   managed to turn off their application workload, while the UPS or
	   ePDU	remains	accessible for monitoring and management. This toggle
	   allows to delay propagation of such state into a known loss of a
	   feed	(possibly triggering FSD on upsmon clients which MONITOR the
	   device and are in fact still	alive -- e.g. with multiple power
	   sources or because they as the load are not really turned off),
	   because when	some devices begin battery calibration,	they report
	   "OFF" for a few seconds and only then they might report "CAL" after
	   switching all the power relays -- thus causing false-positives for
	   upsmon FSD trigger.

	   A negative value means to disable decreasing	the counter of working
	   power supplies in such cases, and a zero makes the effect of
	   detected "OFF" state	immediate. Built-in default value is 30
	   (seconds), to put an	"OFF" state into effect	(decrease known-fed
	   supplies count) if it persists for this many	seconds.

	       Note
	       so far we support the device reporting an "OFF" state which
	       usually means completely	un-powering the	load; a	bug-tracker
	       issue was logged	to design similar support for just some
	       manageable outlets or outlet groups.

       OBLBDURATION seconds
	   NUT normally	raises alarms for immediate shutdown (FSD) for
	   consumers of	an UPS known to	be on battery ("OB") and achieving the
	   low battery status ("LB"), if that is their last remaining power
	   source to satisfy their MINSUPPLIES setting.	In some	special	cases,
	   users may want to delay raising the alarm (using the	OBLBDURATION
	   option) at their discretion and risk	of an ungraceful shutdown.

	   A positive value puts "OB LB" state into effect only	if it persists
	   for this many seconds. A non-positive value makes the FSD effect of
	   detected "OB	LB" state immediate. Built-in default value is 0
	   (seconds).

	       Note
	       If both OBLBDURATION and	HOSTSYNC options are set on the	same
	       (secondary) upsmon client system, and HOSTSYNC is shorter, it
	       would be	effectively ignored: upsmon would wait for up to
	       OBLBDURATION seconds for	the "OB	LB" state to clear, and	then
	       the secondary client logic would	fall through to	immediate
	       shutdown. If the	primary	system issues an FSD on	this UPS, that
	       would take an even higher-priority effect as soon as seen.

       RBWARNTIME seconds
	   When	a UPS says that	it needs to have its battery replaced, upsmon
	   will	generate a NOTIFY_REPLBATT event. By default, this happens
	   every 43200 seconds (12 hours).

	   If you need another value, set it here.

       ALARMCRITICAL 0 | 1
	   NUT normally	considers UPS with active alarms as volatile, meaning
	   they	are observed more closely and may be considered	critical/dead
	   earlier than	in other regular UPS statuses. This is especially true
	   for no-communication	situations, where UPS in an ALARM status will
	   be considered lost and system shutdowns may be triggered as a
	   product.

	   As there is no common standard for what constitutes an alarm, such
	   alarm states	may in fact be mundane in nature and the behavior
	   above unwanted due to possibly resulting in unwarranted system
	   shutdowns.

	   When	this setting is	disabled, upsmon will consider a UPS in	an
	   alarm state as not volatile and make	it treat the ALARM status as
	   any other.

       RUN_AS_USER username
	   upsmon normally runs	the bulk of the	monitoring duties under
	   another user	ID after dropping root privileges. On most systems
	   this	means it runs as "nobody", since that's	the default from
	   compile-time.

	   The catch is	that "nobody" can't read your upsmon.conf, since by
	   default it is installed so that only	root can open it. This means
	   you won't be	able to	reload the configuration file, since it	will
	   be unavailable.

	   The solution	is to create a new user	just for upsmon, then make it
	   run as that user. I suggest "nutmon", but you can use anything that
	   isn't already taken on your system. Just create a regular user with
	   no special privileges and an	impossible password.

	   Then, tell upsmon to	run as that user, and make upsmon.conf
	   readable by it. Your	reloads	will work, and your config file	will
	   stay	secure.

	   This	file should not	be writable by the upsmon user,	as it would be
	   possible to exploit a hole, change the SHUTDOWNCMD to something
	   malicious, then wait	for upsmon to be restarted.

       SHUTDOWNCMD command
	   upsmon runs this command when the system needs to be	brought	down.
	   If it is a secondary, it will do that immediately whenever the
	   current overall power value drops below the MINSUPPLIES value
	   above.

	   When	upsmon is a primary, it	will allow any secondaries to log out
	   before starting the local shutdown procedure.

	   Note	that the command needs to be one element in the	config file.
	   If your shutdown command includes spaces, then put it in quotes to
	   keep	it together, i.e.:

	       SHUTDOWNCMD "/sbin/shutdown -h +0"

       SHUTDOWNEXIT boolean|number
	   After initiating shutdown, should this upsmon daemon	itself exit?
	   By doing so NUT secondary systems can tell the NUT primary that it
	   can proceed with its	own shutdown and eventually tell the UPS to
	   cut power for the load. ("Yes" by default)

	   Some	"secondary" systems with workloads that	take considerable time
	   to stop (e.g. virtual machines or large databases) can benefit from
	   reporting (by virtue	of logging off the data	server)	that they are
	   ready for the "primary" system to begin its own shutdown and
	   eventually to tell the UPS to cut the power -- not as soon as they
	   have	triggered their	own shutdown, but at a later point (e.g. when
	   the upsmon service is stopped AFTER the heavier workloads).

	   Note	that the actual	ability	to complete such shutdown depends on
	   the remaining battery run-time at the moment	when UPS power state
	   becomes considered critical and the shutdowns begin.	You may	also
	   have	to tune	HOSTSYNC on the	NUT primary to be long enough for
	   those secondaries to	stop their services. In	practice, it may be
	   worthwhile to investigate ways to trigger shutdowns earlier on
	   these systems, e.g. by setting up upssched integration, or
	   dummy-ups driver with overrides for stricter	battery.charge or
	   battery.runtime triggers than used by the rest of your servers.

	   This	option supports	Boolean-style strings (yes/on/true or
	   no/off/false) or numbers to define a	delay (in seconds) between
	   calling SHUTDOWNCMD and exiting the daemon. Zero means immediate
	   exit	(default), negative values mean	never exiting on its own
	   accord.

       CERTPATH	certificate file or database
	   When	compiled with SSL support, you can enter the certificate path
	   here.

	   With	NSS:
	       Certificates are	stored in a dedicated database (data split in
	       3 files). Specify the path of the database directory.

	   With	OpenSSL:
	       Directory containing CA certificates in PEM format, used	to
	       verify the server certificate presented by the upsd server. The
	       files each contain one CA certificate. The files	are looked up
	       by the CA subject name hash value, which	must hence be
	       available.

       CERTIDENT certificate name database password
	   When	compiled with SSL support with NSS, you	can specify the
	   certificate name to retrieve	from database to authenticate itself
	   and the password required to	access certificate related private
	   key.

	       Note
	       Be sure to enclose "certificate name" in	double-quotes if you
	       are using a value with spaces in	it.

       CERTHOST	hostname certificate name certverify forcessl
	   When	compiled with SSL support with NSS, you	can specify security
	   directive for each server you can contact.

	   Each	entry maps server name with the	expected certificate name and
	   flags indicating if the server certificate is verified and if the
	   connection must be secure.

	       Note
	       Be sure to enclose "certificate name" in	double-quotes if you
	       are using a value with spaces in	it.

       CERTVERIFY 0 | 1
	   When	compiled with SSL support, make	upsmon verify all connections
	   with	certificates.

	   Without this, there is no guarantee that the	upsd is	the right
	   host. Enabling this greatly reduces the risk	of man-in-the-middle
	   attacks. This effectively forces the	use of SSL, so don't use this
	   unless all of your upsd hosts are ready for SSL and have their
	   certificates	in order.

	   When	compiled with NSS support of SSL, can be overridden for	host
	   specified with a CERTHOST directive.

       FORCESSL	0 | 1
	   When	compiled with SSL, specify that	a secured connection must be
	   used	to communicate with upsd.

	   If you don't	use CERTVERIFY 1, then this will at least make sure
	   that	nobody can sniff your sessions without a large effort. Setting
	   this	will make upsmon drop connections if the remote	upsd doesn't
	   support SSL,	so don't use it	unless all of them have	it running.

	   When	compiled with NSS support of SSL, can be overridden for	host
	   specified with a CERTHOST directive.

       DEBUG_MIN INTEGER
	   Optionally specify a	minimum	debug level for	upsmon daemon, e.g.
	   for troubleshooting a deployment, without impacting foreground or
	   background running mode directly. Command-line option -D can	only
	   increase this verbosity level.

	       Note
	       if the running daemon receives a	reload command,	presence of
	       the DEBUG_MIN NUMBER value in the configuration file can	be
	       used to tune debugging verbosity	in the running service daemon
	       (it is recommended to comment it	away or	set the	minimum	to
	       explicit	zero when done,	to avoid huge journals and I/O system
	       abuse). Keep in mind that for this run-time tuning, the
	       DEBUG_MIN value present in reloaded configuration files is
	       applied instantly and overrides any previously set value, from
	       file or CLI options, regardless of older	logging	level being
	       higher or lower than the	newly found number; a missing (or
	       commented away) value however does not change the previously
	       active logging verbosity.

SEE ALSO
       upsmon(8), upsd(8), nutupsdrv(8).

   Internet resources:
       The NUT (Network	UPS Tools) home	page: https://www.networkupstools.org/

Network	UPS Tools 2.8.2.	  04/17/2025			UPSMON.CONF(5)